52
E8 Malfunction of Indoor Fan Motor
Malfunction of
indoor fan motor
Check if the
control wire of indoor fan motor is
connected on the outdoor
mainboard correctly
Replace
the indoor fan motor and then
restart the unit to see if there still
is malfunction of indoor
fan motor
Correctly connect the
control wire of fan motor
on the mainboard
Operate the unit with
the new motor
Replace the
indoor
mainboard
Yes
No
No
Yes
11
.2 Troubleshooting Flow Chart of Drive Malfunction
Note:
For Outdoor Unit Drive (Inverter) by Single-phase Motor
P0 Drive module reset
P7 IPM or PFC temperature sensor error
PA AC current protection (input side)
PC Current sens
or
circuit error
HC PFC protection (48k only)
P0
ǃ
P7
ˆ
PA
ˆ
HC
or
PC
is
displayed
on
wired zone
controller
P0
ˆ
P7
ˆ
PA
ˆ
Hc
or
PC
is
displayedin
the
mainboard
88
Indicating
L
ight
Replace the
mainboard
Work
s
Normally
Service Manual