background image

1-WAY CASSETTE

TC-18002

 2-9

2.11  Control System

2.11.1  Refrigerant System

Models:  (H,Y,C)IC1006B21S, (H,Y,C)IC1008B21S, (H,Y,C)IC1012B21S and (H,Y,C)IC1015B21S 

Mark

Part Name

1

Heat Exchanger

2

Distributor

3

Strainer

4

Electronic Expansion Valve

Unit: inch (mm)

Model

Distributor

(A) Gas Pipe 

 Connection

(B) Liquid Pipe 

 Connection

(C) (OD×T)

(D) (OD×T)

(H,Y,C)IC1006B21S

3 Pass

f

1/2

(12.7)

f

1/4

(6.35)

f

1/2×t0.031

(12.7×0.8)

f

1/2×t0.031

(12.7×0.8)

(H,Y,C)IC1008B21S

3 Pass

f

1/2

(12.7)

f

1/4

(6.35)

f

1/2×t0.031

(12.7×0.8)

f

1/2×t0.031

(12.7×0.8)

(H,Y,C)IC1012B21S

5 Pass

f

1/2

(12.7)

f

1/4

(6.35)

f

1/2×t0.031

(12.7×0.8)

f

1/2×t0.031

(12.7×0.8)

(H,Y,C)IC1015B21S

5 Pass

f

1/2

(12.7)

f

1/4

(6.35)

f

1/2×t0.031

(12.7×0.8)

f

1/2×t0.031

(12.7×0.8)

Содержание CIC1006B21S

Страница 1: ...INVERTER DRIVEN MULTI SPLIT SYSTEM HEAT PUMP AIR CONDITIONERS Engineering Manual TC 18002 Technical Catalog for Outdoor Unit Indoor Units 1 Way Cassette H Y C IC1006B21S H Y C IC1008B21S H Y C IC1012B21S H Y C IC1015B21S ...

Страница 2: ......

Страница 3: ...gainst possible damage or injury that might occur in an earthquake if the unit is not installed correctly injuries may occur due to a falling unit Use appropriate Personal Protective Equipment PPE such as gloves and protective goggles and where appropriate have a gas mask nearby Also use electrical protection equipment and tools suited for electrical operation purposes Keep a wet cloth and a fire ...

Страница 4: ...n any location where animals and plants can come into direct contact with the outlet air stream Exposure could adversely affect the animals and plants Do not install the unit with any downward slope to the side of the drain adapter If you do you may have condensate flowing back which may cause leaks Be sure the condensate hose discharges water properly If connected incorrectly it may cause leaks D...

Страница 5: ...es can be generated from decomposition Do not position the condensate pipe for the indoor unit near any sanitary sewers where corrosive gases may be present If you do toxic gases can seep into breathable air spaces and can cause respiratory issues If the condensate pipe is installed incorrectly water leakage and damage to the ceiling floor furniture or other possessions may result If condensate pi...

Страница 6: ... cycle the sizes of the charging connections have been changed from R407C type and R22 type It is necessary to verify the appropriate tools are on hand before performing installation work Use refrigerant pipes and joints which are approved for use with R410A A compressor unit comprises a pressurized system Never loosen threaded joints while the system is under pressure and never open pressurized s...

Страница 7: ...cable must be a minimum of AWG18 0 82mm2 2 Conductor Stranded Copper Shielded cable must be used for applications and routing in areas of high EMI and other sources of potentially excessive electrical noise to reduce the potential for communication errors When shielded cabling is applied proper bonding and termination of the cable shield is required as per Johnson Controls guidelines Plenum and ri...

Страница 8: ...ter PD 100 3 4 3 5 Grille for Front Discharge DG 56SW1 3 5 3 6 Air Outlet Shutter Plate PIS 56LS 3 6 3 7 Infrared IR Receiver Kit C1RK01 3 7 3 7 1 Specifications 3 7 3 7 2 Dimensions 3 7 3 7 3 Applicable Models 3 7 3 7 4 Accessories Options 3 8 3 7 5 Installation 3 8 3 7 6 Optional Functions 3 12 3 7 7 Identifying Indoor Units Installed in a Side by Side Operation 3 13 3 7 8 Simultaneous Operation...

Страница 9: ...ven combination of the scroll compressor and inverter provides the best air conditioning for small and medium office buildings VRF System Johnson Controls has developed the VRF system with its customers in mind This system allows the interconnection of indoor units for all our VRF air conditioners This system provides the consumer with greater flexibility for installation which means that the air ...

Страница 10: ... using the wired controller depending on the ceiling height as shown in the table below Slim and Stylish Design The unit height is only 9 1 4 inches 235mm It can be installed at a small installation height such as a clipped ceiling Decorative panel design is simple and stylish The shutter function closes the air outlet with the louver when the operation is stopped Highly Advanced Low Sound Pressur...

Страница 11: ... Adjustment 3 Ability to embed receiver kit optional part in decorative panel Even after installing the decorative panel there is the ability to embed the receiver kit optional part to the decorative panel while still providing a stylish appearance Easy Maintenance The silver ions antibacterial agent is in the condensate pan and inhibits the generation of mold or bacteria which is the cause of clo...

Страница 12: ... Height 8 9ft 2 7m In case the ceiling height is 8 9ft 2 7m Viewed from Top Unit 23ft 7m 23ft 7m 2 6ft 0 8m From Floor Surface Detecting Area 23ft 7m 23ft 7m Non Detecting Area NOTE The motion sensor detects human activity However if someone is in a room with very little activity the motion sensors may not detect motion The motion sensor may detect human activity if the indoor unit with the motion...

Страница 13: ...ndoor Unit I Indoor Unit Type C1 1 Way Cassette Type C1 Capacity MBH 006 Refrigerant Type B R410A B Power Supply 2 208 230Volts 1Phase 60Hz 2 1 1st Generation 1 S Standard Type S 2 2 Line up Type Capacity Model RT MBH Indoor Unit 1 Way Cassette 0 5 6 H Y C IC1006B21S 0 7 8 H Y C IC1008B21S 1 0 12 H Y C IC1012B21S 1 3 15 H Y C IC1015B21S Model Descriptions Example ...

Страница 14: ...0 27 15 16 710 Net Weight lbs kg 55 25 55 25 57 26 57 26 Refrigerant Indoor Fan Airflow Rate cfm Hi2 Hi Me Lo m 3 min External Pressure in W G Pa Motor Nominal Output W Connections Refrigerant Piping Liquid Line in mm 1 4 6 35 1 4 6 35 1 4 6 35 1 4 6 35 Gas Line in mm 1 2 12 70 1 2 12 70 1 2 12 70 1 2 12 70 Condensate Drain OD in mm 1 1 4 32 1 1 4 32 1 1 4 32 1 1 4 32 ID in mm 1 25 1 25 1 25 1 25 ...

Страница 15: ... H Y C IC1008B21S with Decorative Panel P AP36CNA H Y C IC1012B21S and H Y C IC1015B21S with Decorative Panel P AP56CNA NOTE Distance between the wall and louver side panel edge must be a minimum of 59 1 16 inches 1500mm to prevent short circuiting Unit inch mm Decorative Panel ...

Страница 16: ... with fb Flare Nut 10 Condensate Pipe Connection VP25 OD f1 1 4 32 11 Condensate Mechanism 12 Float Switch 13 Condensate Pan 14 Rubber Plug for Drain 15 Decorative Panel P AP36CNA P AP56CNA Optional 16 Air Inlet Grille 17 Air Filter 18 Air Outlet 19 Air Inlet 20 Cover for Corner Pocket P AP36CNA P AP56CNA Model a b H Y C IC1006B21S 1 2 12 7 1 4 6 35 H Y C IC1008B21S 1 2 12 7 1 4 6 35 H Y C IC1012B...

Страница 17: ...tity Insulation Class E Multi Pass Cross Finned Tube Copper Tube Drip Proof Type Enclosure DC Motor Multi Blade Centrifugal Fan Aluminum 1 1 2 2 6 5 16 6 5 16 161 161 459 406 353 300 32 80 32 80 10 00 10 00 1 512 459 388 335 13 11 5 10 8 5 14 5 13 11 9 5 50 H Y C IC1012B21S H Y C IC1015B21S 3 3 40 40 8 5 7 5 6 5 6 2 6 5 16 6 5 16 161 335 300 265 229 9 5 8 5 7 5 6 5 161 300 265 229 212 Model Heat E...

Страница 18: ...dicates the minimum service space There are no obstacles which may hamper incoming and discharged air Unit Height in False Ceiling Clearance Down Slope Gradient 1 25 to 1 100 Condensate Piping 9 1 4 235 Min 3 8 10 Unit inch mm Model SHF H Y C IC1006B21S 0 79 H Y C IC1008B21S 0 80 H Y C IC1012B21S 0 83 H Y C IC1015B21S 0 83 NOTE SHF is based on combinations within the VRF system and the following c...

Страница 19: ...wer Applicable Voltage Power Supply Indoor Fan Motor Unit VOL PH HZ Maximum Minimum MCA MFA OPT FLA H Y C IC1006B21S 208 230 1 60 253 188 0 2 15 0 050 0 2 H Y C IC1008B21S 0 3 15 0 050 0 2 H Y C IC1012B21S 0 4 15 0 050 0 3 H Y C IC1015B21S 0 5 15 0 050 0 4 NOTE Power supply voltage should be satisfied with the following Supply Voltage Rated Voltage within 10 Starting Voltage Rated Voltage within 1...

Страница 20: ...18002 2 10 Sound Data NOTE Operation sound is equivalent to an anechoic chamber free space Noise level will be increased by the surrounding noise and echoes H Y C IC1006B21S H Y C IC1008B21S H Y C IC1015B21S H Y C IC1012B21S ...

Страница 21: ...ve Unit inch mm Model Distributor A Gas Pipe Connection B Liquid Pipe Connection C OD T D OD T H Y C IC1006B21S 3 Pass f1 2 12 7 f1 4 6 35 f1 2 t0 031 12 7 0 8 f1 2 t0 031 12 7 0 8 H Y C IC1008B21S 3 Pass f1 2 12 7 f1 4 6 35 f1 2 t0 031 12 7 0 8 f1 2 t0 031 12 7 0 8 H Y C IC1012B21S 5 Pass f1 2 12 7 f1 4 6 35 f1 2 t0 031 12 7 0 8 f1 2 t0 031 12 7 0 8 H Y C IC1015B21S 5 Pass f1 2 12 7 f1 4 6 35 f1 ...

Страница 22: ...e outdoor unit model to be connected Refer to the Outdoor Unit Engineering Manual for details Dry Operation The sequence may be different depending on the outdoor unit model to be connected Refer to the Outdoor Unit Engineering Manual for details Heating Operation The sequence may be different depending on the outdoor unit model to be connected Refer to the Outdoor Unit Engineering Manual for deta...

Страница 23: ...n Is it continuous for more than 3 min 6 min in case of Dry Operation Is compressor operated for more than 15 min The check interval differs depending on the conditions I U Electronic Expansion Valve Completely Closed No No Yes MIF Operation at Set Fan Speed In case of Dry Operation MIF Operation OFF for 6 min Either Gas or Liquid Pipe Surface Temp of Indoor Heat Exchanger Yes Elapsed Time 15 min ...

Страница 24: ...ON Set Temp is lower than Air Intake Temp Prevention Control for Excessively High Outlet Air Temperature High Outlet Air Temperature Heat Lockout NOTE Thermo ON The outdoor unit and some indoor units are running Thermo OFF The outdoor unit and some indoor units stay on but don t run Activating Protections The sequence may be different depending on the outdoor unit model to be connected Refer to th...

Страница 25: ...sensed or the setting is changed for the motion sensor on the wired controller Much human activity is accumulated for 5 times within 5 minutes or the setting is changed for the motion sensor on the wired controller Much or little human activity is sensed or the setting is changed for the motion sensor on the wired controller Much human activity is sensed or the setting is changed for the motion se...

Страница 26: ...H Y C IC1006B21S H Y C IC1008B21S H Y C IC1012B21S H Y C IC1015B21S For Evaporator Fan Motor Thermostat Cut Out o F 212 7 o C 100 4 Cut In o F 203 7 o C 95 4 For Control Circuit Fuse Capacity A 5 2 11 3 Safety and Control Device Setting ...

Страница 27: ...1 WAY CASSETTE TC 18002 2 15 2 11 4 Wiring Diagram Models H Y C IC1006B21S H Y C IC1008B21S H Y C IC1012B21S and H Y C IC1015B21S ...

Страница 28: ......

Страница 29: ...r Plate PIS 56LS 3 7 Infrared IR Receiver Kit C1RK01 3 8 3P Connector Cable PCC 1A 3 9 Remote Sensor THM R2A 3 10 Relay and 3 Pin Connector Kit PSC 5RA 3 11 Wired Controller CIW01 3 12 Simplified Wired Controller CIS01 3 13 Wireless Controller CIR01 3 14 Mini Central Controller CCM01 3 15 Large Central Controller CCL01 3 16 Computerized Central Controller Software Adapter CCCS01 CCCA01 Refer to th...

Страница 30: ... filter net needs to be maintained periodically If dust accumulates on the net vacuum the net 4 Change the filter if its operating time appears to be no longer useful 5 Select the function selection mode with the wired controller and set the high speed mode to High Speed 1 before using this antibacterial air filter Refer to the Installation Manual for Anti bacterial Air Filter for high speed mode ...

Страница 31: ...g for the motion sensor kit to the connector CN10 on the indoor unit PCB in the electrical control box Do not run the connecting cable for the motion sensor kit and the power source cable 208 230V in parallel This could cause electromagnetic interference EMI resulting in a malfunction of the motion sensor kit 3 Refer to the Installation Manual for Motion Sensor Kit for installation and setting det...

Страница 32: ...o could cause condensation 2 Do not install the unit where abnormal odors are in the atmosphere 3 The duct adapter provides a maximum quantity of fresh air intake of approximately 18cfm 0 5m3 min for 3 3 ft 1m straight pipe duct When more fresh air intake is required be sure to install the dedicated outside air system In this case do not utilize the dedicated outside air system 4 Insulate the duct...

Страница 33: ... to Installation Manual for Grille for Front Discharge for more details Frame of Grille Vertical Blade Horizontal Blade Decorative Panel Option A A 6 M4 Screw Accessory Connecting Grille for Front Discharge Cut out the front plate steel metal of the indoor unit along the score lines using heavy duty cutting shears Flexible Duct Accessory Air Outlet Clipped Ceiling Height of Indoor Unit 27 15 16 71...

Страница 34: ...he air outlet shutter plate must be used 2 Refer to the Installation Manual for Air Outlet Shutter Plate for more details Specifications Model Item PI 160LS1 Applicable Indoor Unit Model H Y C IC1 B21S MBH 006 to 015 Quantity per unit 1 Material Shutter Plate Polyethylenes Sheet Non woven Fabric Flame Resistance UL94V 0 Unit inch mm ...

Страница 35: ...h the 1 way cassette for use with the wireless controller 3 7 2 Dimensions 3 7 3 Applicable Models Model C1IRK01 Applicable Indoor Unit Model 1 Way Cassette Type Applicable Wireless Controller CIR01 3 7 1 Specifications Model C1IRK01 Outer Dimension W H D 4 1 2 4 5 16 1 inch 115 110 25 mm Unit inch mm ...

Страница 36: ...r a fire Perform securely the electrical wiring work If the electrical work is not completed heat generation at the connection a fire or an electric shock may occur Make sure that the electrical wires are securely fixed in order not to apply an external force to the terminal connections of the wirings Not doing so may cause heat generation or a fire When the IR receiver kit is near ambient lightin...

Страница 37: ... Inlet Grille Grille Support two or three Fastening Positions for Supporting String Supporting String Decorative Panel 3 Open the air inlet grille The air inlet grille can be removed by pushing the extruded part of the grille in the direction of the arrow and pulling the air inlet grille downward as shown in the figure at the right Decorative Panel Grille Support Indoor Unit Decorative Panel Air I...

Страница 38: ...Remove the connectors at the indoor unit side and the decorative panel side 5 Twist the optional decorative panel in a horizontal direction to remove Do not apply excessive force removing the side pocket covers Doing so may cause damage of the coupling hooks of the side pocket covers or may result in injury Hold the decorative panel securely to prevent it from falling when it is removed Do not app...

Страница 39: ...he cable clamp accessory according to the required position If not condensation may occur because of a space between decorative panel and the indoor unit Decorative Panel Cable Clamp Accessory Attaching Position 1 Insert the IR receiver kit and cable into the attachment position Attach the coupling hooks three portions of the IR receiver kit and the notches at the attachment positions securely 3 P...

Страница 40: ... temperature set point and the heating upper limit for temperature set point are not available The setting is available beyond the upper and lower limit for temperature set point from the wireless controller The optional function setting Fixing of Setting Temperature is not available When the operation mode is changed from the wireless controller the indicated temperature on the wired controller b...

Страница 41: ...ual for the Wireless Controller Up to 16 indoor units can be simultaneously controlled using one wireless controller When multiple indoor units are installed in a large room all the indoor units can be controlled to start stop with only one wireless controller NOTE Do not apply a simultaneous operation for the indoor units installed separately in different rooms Some units may be left without turn...

Страница 42: ...230V Keep a separation of more than 12 inches or run the cable through a grounded metal conduit and ground the tube end OFF ON Unit Number Setting DSW6 Tens Digit RSW1 Units Digit 1 2 3 4 5 6 Set No 1 pin ON OFF ON 1 2 3 4 5 6 DSW6 RSW1 Ex Set for No 16 Unit Setting Position Set by inserting slotted screwdriver into the groove Set at 6 Factory setting for DSW6 and RSW1 were set to 0 Max 63 units a...

Страница 43: ...unit and the IR receiver kit When the IR receiver kit is connected to multiple indoor units the alarm code is indicated for each indoor unit in order Alarm Code Table For alarm code details refer to the Installation and Maintenance Manual for the indoor units After all installations are completed a test run should be performed 1 Perform the test run according to the installation manual for the wir...

Страница 44: ...plied wires AWG22 0 3 to 0 5mm2 with soldering Name 3P Connector Cable Model PCC 1A Remarks One set contains five 3P connector cables Specifications Item Specification Model THM R2A Case Material ABS Resin Color Silky White Base Material ABS Resin Color Silky White Sensor Part Name Thermistor Cord Length approx 26 ft 8m 3 9 Remote Sensor THM R2A When a remote temperature sensor is installed with a...

Страница 45: ...1 Input level signal or pulse signal for voltage from the third party controller or BMS Voltage 12VDC 10mA Voltage 24VDC 10mA Pulse Range 500ms or more Input 2 Third Party Controller or BMS Output 1 Output signal from the wired controller 24VDC From 10mA to 1A Output 2 Refer to the Indoor Unit Manual for Input Output mode setting by the wired controller Refer to Service Manual for connector number...

Страница 46: ......

Страница 47: ... 9 6 6 9 1 6 6 7 5 6 2 7 7 6 2 7 8 6 2 8 0 6 3 8 3 6 5 8 5 6 5 8 7 6 5 5 4 5 1 5 3 5 0 5 2 5 0 5 1 4 9 5 1 4 9 5 2 5 0 5 2 5 0 4 5 4 4 4 5 4 5 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 5 4 5 3 7 3 6 3 7 3 6 3 7 3 7 3 7 3 6 3 7 3 7 3 7 3 7 3 7 3 7 12 4 10 2 12 7 10 4 12 9 10 3 13 0 10 4 13 5 10 5 13 8 10 6 14 2 10 8 12 1 10 0 12 3 10 1 12 5 10 1 12 6 10 2 13 0 10 4 13 4 10 5 13 7 10 5 11 3 9 6 11 5 9 7 11 ...

Страница 48: ...13 5 12 8 7 6 7 5 7 3 7 2 6 7 6 4 15 3 15 1 14 8 14 4 13 5 12 8 7 6 7 5 7 3 7 2 6 7 6 4 15 3 15 1 14 8 14 4 13 5 12 8 7 1 7 1 7 1 7 1 7 0 7 0 13 4 13 4 13 4 13 4 13 3 13 1 7 4 7 4 7 4 7 4 7 3 7 2 14 0 14 0 14 0 14 1 13 8 13 7 7 8 7 8 7 8 7 8 7 6 7 5 14 7 14 7 14 7 14 7 14 4 14 2 8 1 8 1 8 1 8 1 8 0 7 8 15 4 15 4 15 4 15 4 15 0 14 8 8 5 8 5 8 5 8 5 8 3 8 1 16 0 16 0 16 0 16 0 15 6 15 3 8 8 8 8 8 8 ...

Страница 49: ......

Страница 50: ... 2018 Johnson Controls Inc TC 18002 Code No LIT 12013003 Issued February 2018 ...

Отзывы: