background image

536636-UIM-A-1209

2

Johnson Controls Unitary Products

1.

Install this air handler only in a location and position as specified in
SECTION III of these instructions.

2.

Always install the air handler to operate within the air handler’s
intended maximum outlet air temperature. Only connect the air
handler to a duct system which has an external static pressure
within the allowable range, as specified on the air handler rating
plate.

3.

When an air handler is installed so that supply ducts carry air cir-
culated by the air handler to areas outside the space containing
the air handler, the return air shall also be handled by duct(s)
sealed to the air handler casing and terminating in the space to be
cooled/heated.

4.

The air handler is not to be used for temporary heating of buildings
or structures under construction.

5.

The size of the unit should be based on an acceptable heat loss or
gain calculation for the structure. ACCA, Manual J or other
approved methods may be used.

SAFETY REQUIREMENTS

1.

This air handler should be installed in accordance with all national
and local building/safety codes and requirements, local plumbing
or wastewater codes, and other applicable codes.

2.

Refer to the unit rating plate for the air handler model number, and
then see the dimensions page of this instruction for supply air ple-
num dimensions in Figure 4. The plenum must be installed accord-
ing to the instructions.

3.

Provide clearances from combustible materials as listed under
Clearances to Combustibles.

4.

Provide clearances for servicing ensuring that service access is
allowed for electric heaters and blower.

5.

Failure to carefully read and follow all instructions in this manual
can result in air handler malfunction, death, personal injury and/or
property damage.

6.

Check the rating plate and power supply to be sure that the electri-
cal characteristics match.

7.

Air handler shall be installed so the electrical components are pro-
tected from water.

8.

Installing and servicing heating/cooling equipment can be hazard-
ous due to the electrical components. Only trained and qualified
personnel should install, repair, or service heating/cooling equip-
ment. Untrained service personnel can perform basic maintenance
functions such as cleaning and replacing the air filters. When
working on heating/cooling equipment, observe precautions in the
manuals and on the labels attached to the unit and other safety
precautions that may apply.

9.

These instructions cover minimum requirements and conform to
existing national standards and safety codes. In some instances
these instructions exceed certain local codes and ordinances,
especially those who have not kept up with changing residential
and non-HUD modular home construction practices. These
instructions are required as a minimum for a safe installation.

INSPECTION

As soon as a unit is received, it should be inspected for possible dam-
age during transit. If damage is evident, the extent of the damage
should be noted on the carrier’s freight bill. A separate request for
inspection by the carrier’s agent should be made in writing. Also, before
installation the unit should be checked for screws or bolts, which may
have loosened in transit. There are no shipping or spacer brackets
which need to be removed.

Also check to be sure all accessories such as heater kits, suspension
kits, and coils are available. Installation of these accessories or field
conversion of the unit should be accomplished before setting the unit in
place or connecting any wiring, electric heat, ducts or piping.

LIMITATIONS

These units must be wired and installed in accordance with all national
and local safety codes.

Voltage limits are as follows: 

Airflow must be within the minimum and maximum limits approved for
electric heat, evaporator coils and outdoor units.

SECTION III: UNIT INSTALLATION

CLEARANCES

Clearances must be taken into consideration, and provided for as fol-
lows:

1.

Refrigerant piping and connections - minimum 12” recommended.

2.

Maintenance and servicing access - minimum 36” from front of unit
recommended for blower motor / coil replacement.

3.

Condensate drain lines routed to clear filter and panel access.

4.

Filter removal - minimum 36” recommended.

5.

The ductwork and plenum connected to this unit are designed for
zero clearance to combustible materials.

6.

A combustible floor base accessory is available for downflow
applications of this unit, if required by local code.

LOCATION

Location is usually predetermined. Check with owner’s or dealer’s
installation plans. If location has not been decided, consider the follow-
ing in choosing a suitable location:

1.

Select a location with adequate structural support, space for ser-
vice access, clearance for air return and supply duct connections.

2.

Use hanging brackets to wall mount this single piece air handler
unit, is not recommended.

3.

Normal operating sound levels may be objectionable if the air han-
dler is placed directly over some rooms such as bedrooms, study,
etc.

4.

Select a location that will permit installation of condensate line to
an open drain or outdoors allowing condensate to drain away from
structure.

5.

Proper electrical supply must be available.

6.

If unit is located in an area of high humidity (ie: an unconditioned
garage or attic), nuisance sweating of casing may occur. On these
installations, unit duct connections and other openings should be
properly sealed and a wrap of 2” fiberglass insulation with vinyl
vapor barrier should be used.

FIRE OR ELECTRICAL HAZARD
Failure to follow the safety warnings exactly could result in serious
injury, death or property damage.
A fire or electrical hazard may result causing property damage, per-
sonal injury or loss of life.

Air Handler Voltage

Voltage code

1

Normal Operating 

Voltage Range

1. Rated in accordance with ARI Standard 110, utilization range “A”.

208/230-1-60

06

187-253

Entering Air Temperature Limits

Wet Bulb Temp.°F

Dry Bulb Temp. °F

Min.

Max.

Min.

Max.

57

72

65

95

The primary and secondary drain line must be trapped to allow
proper drainage of condensate water. If the secondary drain line is
not used, it must be capped. The coil is provided with a secondary
drain. It should be piped to a location that will give the occupant a
visual warning that the primary drain is clogged. If the secondary
drain is not used it must be capped.

NOTICE

Содержание AV Series

Страница 1: ...flow or horizontal application These versatile models may be used for cooling or heat pump operation with or without electric heat A BRAND LABEL available from Distribution may be applied to the center of the blower access panel on AVG models The unit can be positioned for bottom return air in the upflow position top return air in the downflow position and right or left return in the hor izontal p...

Страница 2: ...ier s agent should be made in writing Also before installation the unit should be checked for screws or bolts which may have loosened in transit There are no shipping or spacer brackets which need to be removed Also check to be sure all accessories such as heater kits suspension kits and coils are available Installation of these accessories or field conversion of the unit should be accomplished be...

Страница 3: ...panel cladding This label should be applied after the air handler is placed in its proper orientation so the label is right side up When an evaporator coil is installed in an attic or above a finished ceiling an auxiliary drain pan should be provided under the coil as is specified by most local building codes In severe high humidity high temperature indoor unit environments an accessory insulation...

Страница 4: ...ladding must be removed to gain access to the sheet metal cover plate Some local codes may require that the circuit breaker remain visible If so do not re install circuit breaker cover cladding NOTICE FIGURE 3 Dimensions Duct Connection Dimensions 10 3 8 F CIRCUIT BREAKER PANEL BOTTOM INLET DIMENSIONS DRAIN PAN CONNECTIONS FOR HORIZONTAL APPLICATIONS BLOWER COMPARTMENT REFRIGERANT CONNECTIONS DRAI...

Страница 5: ...ng the heating season or through an uncooled space during the cooling season The use of a vapor barrier is recommended to prevent absorp tion of moisture from the surrounding air into the insulation The supply air duct should be properly sized by use of a transition to match unit opening All ducts should be suspended using flexible hang ers and never fastened directly to the structure This unit is...

Страница 6: ...ion WW XX 24B 20 46 36C 24 52 AV 48D 60D 28 57 FIGURE 7 Typical Horizontal Installation FIGURE 8 TXV WW XX SUSPENSION SUPPORT LOCATIONS FOR HORIZONTAL APPLICATIONS 2 1 1 2 MIN 1 1 2 x 1 1 2 Angle Recommended length 26 minimum with 2 clearance on both sides of Air Handler MIN 3 8 THREADED ROD YY VAPOR LINE THERMAL EXPANSION VALVE BULB Required insulation not shown for clarity THERMAL EXPANSION VALV...

Страница 7: ... required for listed combination of Air Handler and Heater Kit For Upflow Downflow and Horizontal right hand applications the kits can be installed without modification Field modification is required for Horizontal left hand airflow application only Follow instructions with heater for modification NOTE If a heat kit with a circuit breaker is installed in the air handler the circuit breaker cover c...

Страница 8: ...d FIGURE 10 Air Handler Control Board Communications Connections SPARE JUMPER HEAT ENABLE JUMPER HUMIDIFIER OUT PUT EAC OUTPUT THERMOSTAT CONNECTIONS CONTINUOUS FAN JUMPER BLOWER SPEED JUMPERS HUMIDSTAT JUMPER AC HP JUMPER All wiring must comply with local and national electrical code requirements Read and heed all unit caution labels It is possible to vary the amount of electric heat turned on du...

Страница 9: ...ve humidistat jumper on air handler control board 3 For heat pump applications set MODE jumper on air handler control board to the HP position 4 To change quantity of heat during HP defrost cycle reverse connections at W1 and W2 on air handler control board FIGURE 11 Cooling Models with and without Electric Heat Wiring Air Handler Control Wiring Typical A C Cooling only Applications THERMOSTAT AIR...

Страница 10: ...ng as short as possible inside the control box To further minimize air leakage seal the wiring entry point at the outside of the unit The field wiring is to be connected at the screw terminals of the control board Refer to Figures 11 or 12 The low voltage connections may be connected to the screw terminals or the quick connect terminals The screw terminals and the quick con nect terminals are phys...

Страница 11: ...OUT The HUM OUT output can be used to drive an external relay or solenoid 24 VAC coil to control a humidifier The output is energized when the HUM input is energized the HUM STAT is in the YES position and the control has a thermostat call for heating heat pump or electric heat EAC The EAC output can be used to drive an external relay 24 VAC coil to control an electronic air cleaner The output is ...

Страница 12: ...f the limit switch closes and re opens during the one hour soft lockout period the control will enter a hard lockout condition and continue to indicate a fault code 5 If the limit switch opens twice when no call for electric heat is present fault code 2 the control will enter a hard lockout condition If the limit switch opens multiple times soon after a soft lockout reset fault code 6 the control ...

Страница 13: ... CFM for high heat tap selection on Table 16 Fan Only CFM When the connection is made from R to G the fan only mode is acti vated In this mode the airflow will depend on the position of the CONT Fan jumper In the H position the blower will deliver 85 90 of full capacity In the M position the blower will deliver 60 65 of full capacity In the L position the blower will deliver 30 35 of full capac it...

Страница 14: ...0506 0 5 Heat D 3 6 4 8 12 3 16 4 3 6 4 8 3 6 4 8 3 6 4 8 4HK 6500806 0 5 Heat C 5 6 7 5 19 2 25 6 2 8 3 75 5 6 7 5 5 6 7 5 4HK 6501006 0 5 Heat B 7 2 9 6 24 6 32 8 3 6 4 8 7 2 9 6 7 2 9 6 4HK165N1506 0 5 Heat A 10 8 14 4 36 9 49 1 3 6 4 8 7 2 9 6 10 8 14 4 36C 4HK 6500506 0 5 Heat C 3 6 4 8 12 3 16 4 3 6 4 8 3 6 4 8 3 6 4 8 4HK 6500806 0 5 Heat C 5 6 7 5 19 2 25 6 2 8 3 75 5 6 7 5 5 6 7 5 4HK 650...

Страница 15: ... 53 08 58 75 60 60 6 6 4HK16501506 60 0 74 75 83 75 90 90 3 3 4HK16501806 73 3 89 19 100 38 90 110 3 2 4HK16502006 80 0 96 42 108 75 100 125 3 1 4HK16502506 100 0 118 08 133 75 125 150 1 1 0 1 O C P Over Current Protection device must be HACR type Circuit Breaker or Time Delay fuse TABLE 12 Electrical Data For Multi Source Power Supply Copper Wire 208 230 1 60 Models Heater Models Min Circuit Ampa...

Страница 16: ... See conversion Table 10 TABLE 14 Electrical Data For Single Source Power Supply Copper Wire 208 230 3 60 Models Heat Kit Three Phase Heater Amps 240V Field Wiring Min Circuit Ampacity Max O C P 1 Amps Type 75 C Wire Size AWG 208V 230V 208V 230V 208V 230V 24B 4HK06501025 23 1 28 5 32 4 30 35 10 8 36C 4HK06501025 23 1 30 4 34 3 30 35 10 8 4HK06501525 34 7 42 9 48 8 45 50 8 8 48D 4HK06501025 23 1 31...

Страница 17: ...88 828 1387 908 30 8 23 4 39 3 25 7 A Any 954 714 1228 804 27 0 20 2 34 8 22 8 B Any 829 614 1151 756 23 5 17 4 32 6 21 4 C Any 678 523 923 609 19 2 14 8 26 1 17 2 D 48D 60D 48D 60D JUMPER SETTINGS High Low High Low High Low High Low HEAT Tap ADJ Tap 2111 1417 2363 1488 59 8 40 1 66 9 42 1 A Any 1858 1252 2174 1252 52 6 35 4 61 5 35 4 B Any 1480 985 1868 1061 41 9 27 9 52 9 30 0 C Any 1250 840 138...

Страница 18: ...mix one part CalClean to seven parts water Allow solution to remain on coil for 30 minutes before rinsing with clean water Solution should not be permitted to come in contact with painted surfaces LUBRICATION The bearings of the blower motor are permanently lubricated CONDENSATE DRAINS During the cooling season check the condensate drain lines to be sure that condensate is flowing from the primary...

Страница 19: ...536636 UIM A 1209 Johnson Controls Unitary Products 19 NOTES ...

Страница 20: ...change without notice Published in U S A 536636 UIM A 1209 Copyright 2009 by Johnson Controls Inc All rights reserved Supersedes 282849 UIM E 0309 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 ...

Отзывы: