AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin
36
1. In the Operator Menu, press
UP or DOWN
to scroll to the BACnet Temperature Alarm Configuration submenu.
2. Press
ENTER
.
3. Scroll through the submenu options and make any necessary updates. See Table 16 for a description of the
BACnet Temperature Alarm Configuration submenu selection options and their configurable options.
Alarm Deadband
Setpoint
Choose a value of temperature the controller must reach above the Alarm Low Setpoint for Alarm
Low or below the Alarm High Setpoint for Alarm High before an activated alarm resets. The
display units are the same as those chosen in the
submenu.
Alarm Delay
Select the amount of time between any alarm condition and the BACnet Temperature Alarm Low
and High activation. This value is adjustable between 0 and 10 minutes.
Table 16: BACnet Temperature Alarm Configuration Submenu Selections and Configurable Options (Part 2
of 2)
BACnet Temperature
Alarm Configuration
Submenu Selections
Configurable Options
Figure 62: BACnet Temperature Alarm Configuration Selection Menu