YCCS TEC2603-4 BACnet® MS/TP Networked Multi-Stage Thermostat Controllers Installation Instructions 

9

676292-YIM-A-0111

Follow these steps to change the password:

1.

From the System Manager home screen, press the 
Setup icon. The Setup screen appears.

2.

Press System Manager. The System Manager 
Setup screen appears.

3.

Press Security (password). The Security 
(Passwords Required) screen appears.

4.

Press Change TEC Configuration Password. If you 
are not logged on as the Administrator, you are 
prompted for the Administrator password. After you 
have entered this password, the Change TEC 
Configuration Password appears. 

5.

Enter a new value between 1 and 1,000. You do 
not need to enter 0s preceding any number less 
than four digits.

6.

Press OK. The new password is automatically 
assigned to every TEC on the System bus.

Table 1:  Parameters Set at System Manager

1, 2

Parameter

Description and Default

Selection Options

System Mode

Selects the operating status of the 
Rooftop Unit (RTU).
Default: 

Auto

Cooling: 

RTU provides cooling.

Heating: 

RTU provides heating.

Off: 

No heating or cooling is provided.

Auto: 

RTU operates according to the user-set schedule

Setpoint 
Deadband

Sets the minimum deadband 
between the heating and cooling 
setpoints.
Default: 

2.0 Deg F (1.0 Deg C)

Options: 

2.0 Deg F

,

 3.0 Deg F

4.0 Deg F 

(1.0 Deg C, 1.5 Deg C, 2.0 Deg C)

Cooling Unocc 
Setpoint

Sets the unoccupied cooling 
setpoints.
Default: 

78.0 Deg F (25.6 Deg C)

Range: 

72.0

 to 

86.0 Deg F (22.2 to 30.0 Deg C)

Cooling Occ 
Setpoint

Sets the occupied cooling setpoints.
Default: 

72.0 Deg F (22.2 Deg C)

Range: 

70.0

 to 

78.0 Deg F (21.1 to 25.6 Deg C)

Heating Occ 
Setpoint

Sets the occupied heating 
setpoints.
Default:

 68.0 Deg F (20.0 Deg C)

Range: 

62.0

 to 

70.0

 

Deg F (16.7 to 21.1 Deg C)

Heating Unocc 
Setpoint

Sets the unoccupied heating 
setpoints.
Default: 

62.0 Deg F (16.7 Deg C)

Range: 

55.0

 to 

68.0

 

Deg F (12.8 to 20.0 Deg C)

TEC Configuration 
Password

Sets the protective access 
password to prevent unauthorized 
access to the Installer Configuration 
Menu.
Default: 

227

Range: 

1

 to 

1,000

See the 

Setting the Thermostat Controller Password

 section for 

setup information.

Temporary 
Occupancy Time

Sets the duration of temporary 
occupancy time.
Default: 

120 min

Range: 15 to 240 min

Display Units

Sets the display units of 
measurement. 
Default: 

Deg F

Options: 

Deg C

 or 

Deg F

1.

Default values and selection options are shown as they appear on screen. For example, °F at the System Manager appears 
as Deg F.

2.

The System Manager automatically overrides any values set locally at the thermostat controller every 15 minutes.

Содержание YCCS TEC2603-4 BACnet

Страница 1: ...ler Skip this step if the screw is not installed on the bottom of the cover 2 Pull the bottom edge of the thermostat controller cover and open the thermostat controller as illustrated in Figure 1 IMPO...

Страница 2: ...rs and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mount appl...

Страница 3: ...tat controller continue in a daisy chained fashion to the next YCCS System Bus device Note The bus wiring must be twisted pair lines Do not run the bus wiring in the same conduit as line voltage wirin...

Страница 4: ...ipment Transformer 24 VAC for Heating Stages Energizes on a Call for First Stage Heating Energizes on a Call for Second Stage Heating Auxiliary Output Digital Input 1 Filter Only Digital Input 2 Disab...

Страница 5: ...128 O N 24V COM 24V CO M COM J2 COM AI1 AI2 COM AI3 AI4 1 64 32 1 6 8 4 2 128 O N 24V COM 24V CO M Drain Wire Drain Wire Tape back Drain Wire Drain Wire Address 4 Address 6 Address 7 VAV Rooftop Unit...

Страница 6: ...AI 4 Monitored Contact To Temperature RH CO2 Sensor Building Pressure Light Sensor Refrigerant Sensor To 24VAC BO 3 BO 2 BO 1 BO 4 COM Monitored Contact To Scheduled Item 1 To Scheduled Item 2 To Sch...

Страница 7: ...NO key to decline a parameter change and to advance to the next menu item Use the MENU key to access the Main User Menu or to exit the menu see the Main User Menu section access the Installer Configu...

Страница 8: ...he configured password is required to proceed Use the UP DOWN arrow keys to enter the configured password then press the MENU key to proceed through the Installer Configuration Menu parameters 2 Once...

Страница 9: ...eadband between the heating and cooling setpoints Default 2 0 Deg F 1 0 Deg C Options 2 0 Deg F 3 0 Deg F 4 0 Deg F 1 0 Deg C 1 5 Deg C 2 0 Deg C Cooling Unocc Setpoint Sets the unoccupied cooling set...

Страница 10: ...removed and reapplied before any operation fan heating or cooling is authorized Also can be used to sequence the startup of multiple units in one location Default 10 0 sec Range 10 0 to 120 0 sec Fro...

Страница 11: ...ables the thermostat controller to activate the fan in response to a call for heating Fan del Fan delay extends fan operation after a heating or cooling cycle has ended Default off Note The fan delay...

Страница 12: ...the fan output is also disabled Requires that an outside air temperature sensor be installed and connected Default 120 F 49 C Range 15 F 26 C to 120 F 49 C adjustable in 5F 5C increments C lock Disabl...

Страница 13: ...ne where communication is unreliable partition disconnect and isolate a portion of the system Bus for testing purposes and test the Bus portion connected to the System Manager Correcting Physical Comm...

Страница 14: ...om Probable Causes Multiple Symptoms The baud rate may have been changed on some devices on the network but not all devices A download may be in progress There may be a fault at a device A repeater ma...

Страница 15: ...on Repair Information If the TEC2603 4 Thermostat Controller fails to operate within its specifications replace the unit For a replacement thermostat controller contact the nearest Johnson Controls re...

Страница 16: ...F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditions Operating 32 to 122 F 0 to 50 C 95...