Johnson Controls Unitary Products YCCS TEC2603-4 BACnet Скачать руководство пользователя страница 2

676292-YIM-A-0111

YCCS TEC2603-4 BACnet® MS/TP Networked Multi-Stage Thermostat Controllers Installation Instructions

2

3.

Carefully pull the locking tabs on the right side of 
the thermostat controller mounting base and 
unlock the Printed Circuit Board (PCB). Open the 
PCB to the left as illustrated in Figure 2. 

4.

Pull approximately 6 in. (152 mm) of wire from the 
wall and insert the wire through the hole in the 
thermostat controller mounting base.

5.

Align the thermostat controller mounting base on 
the wall and use the base as a template to mark 
the two mounting hole locations.

6.

Position the thermostat controller mounting base 
so that the arrow on the base points upward to 
indicate the top of the thermostat controller.

Note:

If you need to install the thermostat on an 

electrical junction box, use 2-1/2 x 4 in. 
(63 x 101 mm) square boxes with mud ring covers, 
and avoid smaller 1-1/2 x 4 in. (38 x 101 mm) 
square or 3 x 2 in. (76 x 51 mm) boxes. This 
procedure ensures you have enough space for 
cabling and end-of-line devices, if needed.

Note:

For surface-mount applications, use 

durable mounting hardware such as Molly bolt 
anchors that cannot be easily pulled out of the 
mounting surface.

7.

Secure the base to the wall surface using two 
mounting screws as illustrated in Figure 3.

Note:

Be careful not to overtighten the mounting 

screws. 

8.

Swing the PCB back to the right and carefully snap 
it into the locking tabs on the thermostat controller 
mounting base.

9.

Remove the screw terminal blocks that are 
attached to a disposable adhesive. Figure 4 
illustrates the locations of the screw terminal 
blocks on the thermostat controller.

FI

G:

cv

r_

rm

vl

Figure 1: Removing the 

Thermostat Controller Cover

Figure 2: Opening the Thermostat Controller PCB

PCB
Locking
Tabs

F

IG

:p

rn

td

_

c

rc

t_

b

rd

Figure 3: Securing the Thermostat Controller 

Mounting Base to the Wall

F

IG

:m

n

tn

g

_

b

s

Figure 4: Removing the Screw Terminal Blocks

F

IG

:t

rm

n

l_

b

lc

k

s

Содержание YCCS TEC2603-4 BACnet

Страница 1: ...ler Skip this step if the screw is not installed on the bottom of the cover 2 Pull the bottom edge of the thermostat controller cover and open the thermostat controller as illustrated in Figure 1 IMPO...

Страница 2: ...rs and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mount appl...

Страница 3: ...tat controller continue in a daisy chained fashion to the next YCCS System Bus device Note The bus wiring must be twisted pair lines Do not run the bus wiring in the same conduit as line voltage wirin...

Страница 4: ...ipment Transformer 24 VAC for Heating Stages Energizes on a Call for First Stage Heating Energizes on a Call for Second Stage Heating Auxiliary Output Digital Input 1 Filter Only Digital Input 2 Disab...

Страница 5: ...128 O N 24V COM 24V CO M COM J2 COM AI1 AI2 COM AI3 AI4 1 64 32 1 6 8 4 2 128 O N 24V COM 24V CO M Drain Wire Drain Wire Tape back Drain Wire Drain Wire Address 4 Address 6 Address 7 VAV Rooftop Unit...

Страница 6: ...AI 4 Monitored Contact To Temperature RH CO2 Sensor Building Pressure Light Sensor Refrigerant Sensor To 24VAC BO 3 BO 2 BO 1 BO 4 COM Monitored Contact To Scheduled Item 1 To Scheduled Item 2 To Sch...

Страница 7: ...NO key to decline a parameter change and to advance to the next menu item Use the MENU key to access the Main User Menu or to exit the menu see the Main User Menu section access the Installer Configu...

Страница 8: ...he configured password is required to proceed Use the UP DOWN arrow keys to enter the configured password then press the MENU key to proceed through the Installer Configuration Menu parameters 2 Once...

Страница 9: ...eadband between the heating and cooling setpoints Default 2 0 Deg F 1 0 Deg C Options 2 0 Deg F 3 0 Deg F 4 0 Deg F 1 0 Deg C 1 5 Deg C 2 0 Deg C Cooling Unocc Setpoint Sets the unoccupied cooling set...

Страница 10: ...removed and reapplied before any operation fan heating or cooling is authorized Also can be used to sequence the startup of multiple units in one location Default 10 0 sec Range 10 0 to 120 0 sec Fro...

Страница 11: ...ables the thermostat controller to activate the fan in response to a call for heating Fan del Fan delay extends fan operation after a heating or cooling cycle has ended Default off Note The fan delay...

Страница 12: ...the fan output is also disabled Requires that an outside air temperature sensor be installed and connected Default 120 F 49 C Range 15 F 26 C to 120 F 49 C adjustable in 5F 5C increments C lock Disabl...

Страница 13: ...ne where communication is unreliable partition disconnect and isolate a portion of the system Bus for testing purposes and test the Bus portion connected to the System Manager Correcting Physical Comm...

Страница 14: ...om Probable Causes Multiple Symptoms The baud rate may have been changed on some devices on the network but not all devices A download may be in progress There may be a fault at a device A repeater ma...

Страница 15: ...on Repair Information If the TEC2603 4 Thermostat Controller fails to operate within its specifications replace the unit For a replacement thermostat controller contact the nearest Johnson Controls re...

Страница 16: ...F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditions Operating 32 to 122 F 0 to 50 C 95...