background image

YCCS TEC2603-4 BACnet® MS/TP Networked Multi-Stage Thermostat Controllers Installation Instructions 

13

676292-YIM-A-0111

YCCS System Communication Problems

Several factors may influence the behavior of the 
System Communication Bus. In addition, certain 
problems can affect the Bus in multiple ways and have 
multiple symptoms, which makes the exact diagnosis 
difficult. For example, duplicate addresses on the Bus 
can degrade performance, make the device go offline, 
or stop communication completely. 

Incomplete Address

The TEC2603-4 Thermostat Controller must have the 
address set between 42–65 on the System 
Communication Bus; other settings prevent the 
thermostat controller from communicating on the 
System Communication Bus.

Duplicate Addresses

Two or more devices on a communication Bus cannot 
have the same address. For example, two thermostat 
controllers cannot both have an address of 42. If two 
devices on the same Bus have the same address, 
performance can degrade or serious communication 
problems may occur. These problems include the 
devices not coming online and all communication 
stopping completely. Take care when adding or 
changing devices that addresses are not duplicated.

Check for duplicate addresses, in the following ways, 
depending on the severity of the situation:

If the Bus performance is degraded, check the 
address settings at the devices with unreliable 
communications.

If a specific device is not communicating, remove 
the device with communication problems and 
check if the device address remains online at the 
System Manager.

If the Bus communication problems are severe, 
and no communication is present, or you cannot 
determine where communication is unreliable, 
partition (disconnect and isolate a portion of the 
system Bus for testing purposes) and test the Bus 
portion connected to the System Manager.

Correcting Physical Communication Bus Problems

The communication bus is subject to a number of 
physical factors that can affect performance. Consider 
the following list of common physical problems that 
affect the communications bus:

Check status LED to verify power at the controller

Check wires

-

Verify wire is 22 AWG (0.6 mm) 3-conductor, 
twisted, shielded cable.

-

Verify shield is continuous and hard-grounded 
at one end. 

Check wiring

-

Check for and eliminate T-Taps (wire 
configurations that create a T shape) and star 
configurations.

-

Ensure bus is wired in daisy-chain fashion.

-

Verify that appropriate devices have three 
wires entering and exiting each terminal 
(devices at the ends of the trunk do not have 
this wiring).

Check EOL switch settings

-

Verify the System Bus EOL switch on the 
System Manager is set to ON and the System 
Manager is located at the end of the zone bus 
trunk.

-

Verify that only the EOL switch at the end of 
the system bus is set to ON and all other 
system bus EOL switches are set to OFF.

Check connections, polarity, and lengths

-

Verify communications loops are less than 
approximately 304 m (1,000 ft) total in length.

-

If you are using one transformer to power 
multiple devices, verify the device 24 VAC 
power connection follows the polarity of the 
common and 24 V terminations.

Check for opens and shorts

Check terminations

Check for sources of interference

Table 3:  Status LEDs

LED

Description 

Green

The controller is receiving power from the 
24 VAC power supply; alarms are not present.

Red

The controller is receiving power from the 
24 VAC power supply; alarms are present.

Off

Controller is not receiving 24 VAC power or the 
controller is in startup mode.

Содержание YCCS TEC2603-4 BACnet

Страница 1: ...ler Skip this step if the screw is not installed on the bottom of the cover 2 Pull the bottom edge of the thermostat controller cover and open the thermostat controller as illustrated in Figure 1 IMPO...

Страница 2: ...rs and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mount appl...

Страница 3: ...tat controller continue in a daisy chained fashion to the next YCCS System Bus device Note The bus wiring must be twisted pair lines Do not run the bus wiring in the same conduit as line voltage wirin...

Страница 4: ...ipment Transformer 24 VAC for Heating Stages Energizes on a Call for First Stage Heating Energizes on a Call for Second Stage Heating Auxiliary Output Digital Input 1 Filter Only Digital Input 2 Disab...

Страница 5: ...128 O N 24V COM 24V CO M COM J2 COM AI1 AI2 COM AI3 AI4 1 64 32 1 6 8 4 2 128 O N 24V COM 24V CO M Drain Wire Drain Wire Tape back Drain Wire Drain Wire Address 4 Address 6 Address 7 VAV Rooftop Unit...

Страница 6: ...AI 4 Monitored Contact To Temperature RH CO2 Sensor Building Pressure Light Sensor Refrigerant Sensor To 24VAC BO 3 BO 2 BO 1 BO 4 COM Monitored Contact To Scheduled Item 1 To Scheduled Item 2 To Sch...

Страница 7: ...NO key to decline a parameter change and to advance to the next menu item Use the MENU key to access the Main User Menu or to exit the menu see the Main User Menu section access the Installer Configu...

Страница 8: ...he configured password is required to proceed Use the UP DOWN arrow keys to enter the configured password then press the MENU key to proceed through the Installer Configuration Menu parameters 2 Once...

Страница 9: ...eadband between the heating and cooling setpoints Default 2 0 Deg F 1 0 Deg C Options 2 0 Deg F 3 0 Deg F 4 0 Deg F 1 0 Deg C 1 5 Deg C 2 0 Deg C Cooling Unocc Setpoint Sets the unoccupied cooling set...

Страница 10: ...removed and reapplied before any operation fan heating or cooling is authorized Also can be used to sequence the startup of multiple units in one location Default 10 0 sec Range 10 0 to 120 0 sec Fro...

Страница 11: ...ables the thermostat controller to activate the fan in response to a call for heating Fan del Fan delay extends fan operation after a heating or cooling cycle has ended Default off Note The fan delay...

Страница 12: ...the fan output is also disabled Requires that an outside air temperature sensor be installed and connected Default 120 F 49 C Range 15 F 26 C to 120 F 49 C adjustable in 5F 5C increments C lock Disabl...

Страница 13: ...ne where communication is unreliable partition disconnect and isolate a portion of the system Bus for testing purposes and test the Bus portion connected to the System Manager Correcting Physical Comm...

Страница 14: ...om Probable Causes Multiple Symptoms The baud rate may have been changed on some devices on the network but not all devices A download may be in progress There may be a fault at a device A repeater ma...

Страница 15: ...on Repair Information If the TEC2603 4 Thermostat Controller fails to operate within its specifications replace the unit For a replacement thermostat controller contact the nearest Johnson Controls re...

Страница 16: ...F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditions Operating 32 to 122 F 0 to 50 C 95...

Отзывы: