YCCS TEC2603-4 BACnet® MS/TP Networked Multi-Stage Thermostat Controllers Installation Instructions

4

Figure 5: Wiring the TEC2603-4 Thermostat Controller

F

IG:

wr

n

g

24 VAC

Thermostat Power

Y2

Y1

RC

C

If using the same power source
for the thermostat and heating loads,
install a jumper across RC and RH.

Heat 1 Heat 2

RH

W1

W2

Aux

Aux

Cool 1

Energizes on a Call for First-Stage Cooling
Energizes on a Call for Second-Stage Cooling
Energizes Fan in Accordance with the Selected Fan Mode
24 VAC from Equipment Transformer
24 VAC (Common) from Equipment Transformer
24 VAC for Heating Stages
Energizes on a Call for First-Stage Heating
Energizes on a Call for Second-Stage Heating
Auxiliary Output
Digital Input 1 (Filter Only)
Digital Input 2 (Disabled)
Remote Room Sensor
Sensor Common
Auxiliary/Outdoor Air Sensor
Remote Monitoring Supply Temperature Sensor
CCS System Bus

Function

Y1
Y2

G

RC

C

RH
W1
W2

Aux

DI1
DI2

RS

Scom

OS
MS

+, -, REF

Terminal

DI2

DI1

Remote

Monitoring

Supply

Temperature

Sensor

Auxiliary/

Outdoor

Air Sensor

-

+

REF

Supervisory

Controller

Cool 2

Y2

Y1

G

RC

C

RH

W1 W2

DI1 DI2 RS

Scom

Five-Pole
Left Top Connector

Three-Pole
Right Top
Connector

Seven-Pole Bottom Connector

REF

-

+

MS

OS

Aux

G

Fan

Scom

RS

MS

OS

Aux Contact (High Side Common)
• Lighting
• On/Off Actuation
• Exhaust Fan

Remote

Room

Sensor

Содержание YCCS TEC2603-4 BACnet

Страница 1: ...ler Skip this step if the screw is not installed on the bottom of the cover 2 Pull the bottom edge of the thermostat controller cover and open the thermostat controller as illustrated in Figure 1 IMPO...

Страница 2: ...rs and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mount appl...

Страница 3: ...tat controller continue in a daisy chained fashion to the next YCCS System Bus device Note The bus wiring must be twisted pair lines Do not run the bus wiring in the same conduit as line voltage wirin...

Страница 4: ...ipment Transformer 24 VAC for Heating Stages Energizes on a Call for First Stage Heating Energizes on a Call for Second Stage Heating Auxiliary Output Digital Input 1 Filter Only Digital Input 2 Disab...

Страница 5: ...128 O N 24V COM 24V CO M COM J2 COM AI1 AI2 COM AI3 AI4 1 64 32 1 6 8 4 2 128 O N 24V COM 24V CO M Drain Wire Drain Wire Tape back Drain Wire Drain Wire Address 4 Address 6 Address 7 VAV Rooftop Unit...

Страница 6: ...AI 4 Monitored Contact To Temperature RH CO2 Sensor Building Pressure Light Sensor Refrigerant Sensor To 24VAC BO 3 BO 2 BO 1 BO 4 COM Monitored Contact To Scheduled Item 1 To Scheduled Item 2 To Sch...

Страница 7: ...NO key to decline a parameter change and to advance to the next menu item Use the MENU key to access the Main User Menu or to exit the menu see the Main User Menu section access the Installer Configu...

Страница 8: ...he configured password is required to proceed Use the UP DOWN arrow keys to enter the configured password then press the MENU key to proceed through the Installer Configuration Menu parameters 2 Once...

Страница 9: ...eadband between the heating and cooling setpoints Default 2 0 Deg F 1 0 Deg C Options 2 0 Deg F 3 0 Deg F 4 0 Deg F 1 0 Deg C 1 5 Deg C 2 0 Deg C Cooling Unocc Setpoint Sets the unoccupied cooling set...

Страница 10: ...removed and reapplied before any operation fan heating or cooling is authorized Also can be used to sequence the startup of multiple units in one location Default 10 0 sec Range 10 0 to 120 0 sec Fro...

Страница 11: ...ables the thermostat controller to activate the fan in response to a call for heating Fan del Fan delay extends fan operation after a heating or cooling cycle has ended Default off Note The fan delay...

Страница 12: ...the fan output is also disabled Requires that an outside air temperature sensor be installed and connected Default 120 F 49 C Range 15 F 26 C to 120 F 49 C adjustable in 5F 5C increments C lock Disabl...

Страница 13: ...ne where communication is unreliable partition disconnect and isolate a portion of the system Bus for testing purposes and test the Bus portion connected to the System Manager Correcting Physical Comm...

Страница 14: ...om Probable Causes Multiple Symptoms The baud rate may have been changed on some devices on the network but not all devices A download may be in progress There may be a fault at a device A repeater ma...

Страница 15: ...on Repair Information If the TEC2603 4 Thermostat Controller fails to operate within its specifications replace the unit For a replacement thermostat controller contact the nearest Johnson Controls re...

Страница 16: ...F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditions Operating 32 to 122 F 0 to 50 C 95...

Отзывы: