background image

438335-UIM-C-1209

Johnson Controls Unitary Products

23

SECTION VII: COMBUSTION AIR AND 

VENT SYSTEM

COMBUSTION AIR AND VENT SAFETY

This Category IV, dual certified direct vent furnace is designed for resi-
dential application. It may be installed without modification to the con-
densate system in a basement, garage, equipment room, alcove, attic
or any other indoor location where all required clearance to combusti-
bles and other restrictions are met. The combustion air and the venting
system must be installed in accordance with Section 5.3, Air for Com-
bustion and Ventilation, of the National Fuel Gas Code Z223.1/NFPA 54
(latest edition), or Sections 7.2, 7.3 or 7.4 of CSA B149.1, National Gas
and Propane Codes (latest edition) or applicable provisions of the local
building code and these instructions.

COMBUSTION AIR/VENT PIPE SIZING

The size of pipe required will be determined by the furnace model, the
total length of pipe required and the number of elbows required.

Table 8 lists the maximum equivalent length of pipe allowed for each
model of furnace. The equivalent length of elbows is shown in Table 10.
The equivalent length of the vent system is the total length of straight
pipe PLUS the equivalent length of all of the elbows.

The following rules must also be followed:

1.

Long radius (sweep) elbows are recommended. Standard elbows
may be used, but since they have a longer equivalent length, they
will reduce the total length of pipe that will be allowed. Short radius
(plumbing vent) elbows are not allowed. The standard dimensions
of the acceptable elbows are shown below.

2.

The maximum equivalent length listed in Table 8 is for the vent pip-
ing and the air intake piping separately. For example, if the table
allows 65 equivalent feet for a particular model, then the vent can
have 65 equivalent feet of pipe, AND the combustion air intake can
have another 65 equivalent feet of pipe. 

3.

Three vent terminal elbows (two for the vent and one for the com-
bustion air intake) are already accounted for and need not be
included in the equivalent length calculation.

4.

All combustion air and vent pipe must conform to American
National Standards Institute (ANSI) and American Society for
Testing and Materials (ASTM) standards D1785 (Schedule 40
PVC), D2665 (PVC-DWV), F891 (PVC-DWV Cellular Core),
D2261 (ABS-DWV) or F628 (Schedule 40 ABS). Pipe cement and
primer must conform to ASTM Standard D2546 (PVC) or D2235
(ABS). If ABS pipe is to be used, any joint where ABS pipe is
joined to PVC pipe must be glued with cement that is approved for
use with BOTH materials. Metallic materials must not be used for
venting or air intake.

5.

If a flexible connector is used in the vent system, it must be made
of a material that is resistant to acidic exposure and to at least
225°F (107.2°C) temperature. Flexible connectors are also
allowed in the combustion air pipe. 

6.

All models are supplied with 2" (5.1 cm) vent connections. When
the pipe must be increased to 3" (7.6 cm) diameter, the transition
from 2" to 3" must be done as close to the furnace as possible. For
upflow models, the transition from 2" to 3" should be done immedi-
ately above the furnace. For downflow or horizontal models, the
transition from 2" to 3" pipe should be done immediately after exit-
ing the furnace.

7.

In Canada, vents shall be certified to ULC S636, Standard for
Type BH Gas Venting Systems.

8.

In Canada, the first three feet (91.4 cm) of the vent must be readily
accessible for inspection.

9.

For single pipe systems it is recommended to install the combus-
tion air coupling provided and install approximately 18” of PVC
pipe on the furnace.

10. Minimum vent length for all models is 5 feet (1.5 m).

Dimensions are those required in Standard ASTM D-3311.

The VENT SYSTEM must be installed as specified in these instruc-
tions for Residential and non-HUD Modular Homes. The direct vent
system is the only configuration that can be installed in a non-HUD
Modular Home.

 This furnace may not be common vented with any other appliance,
since it requires separate, properly sized air intake and vent lines.
The furnace shall not be connected to any type of B, BW or L vent
or vent connector, and not connected to any portion of a factory-
built or masonry chimney
The furnace shall not be connected to a chimney flue serving a sep-
arate appliance designed to burn solid fuel.

When combustion air pipe is installed above a suspended ceiling or
when it passes through a warm and humid space, the pipe must be
insulated with 1/2” Armaflex or other heat resistant type insulation if
two feet or more of pipe is exposed.
Vent piping must be insulated if it will be subjected to freezing tem-
peratures such as routing through unheated areas or through an
unused chimney.

TABLE 8: 

Maximum Equivalent Pipe Length

Model Input 

BTUH (kW)

Pipe Size 

Inches (cm)

Maximum 

Equivalent 

length feet (m)

60,000 (17.6)

2 (5.1)

65 (19.8)

60,000 (17.6)

3 (7.6)

90 (27.4)

80,000 (23.4)

2 (5.1)

65 (19.8)

80,000 (23.4)

3 (7.6)

90 (27.4)

100,000 (29.3)

2 (5.1)

30 (9.2)

100,000 (29.3)

3 (7.6)

90 (27.4)

120,000 (35.1)

2 (5.1)

30 (9.2)

120,000 (35.1)

3 (7.6)

90 (27.4)

 FIGURE 28:  

Dimensions

TABLE 9: 

Elbow Dimensions

Elbow

"A" Dimension

2" Standard

2-5/16"

3" Standard

3-1/16"

2" Sweep

3-1/4"

3" Sweep

4-1/16"

A

A

A

A

STANDARD ELBOW

LONG (SWEEP) ELBOW

Содержание TM9V*MP

Страница 1: ...wo Stage HP with Two Stage Variable Speed Furnace Hot Heat Pump or Conventional 16 Typical Condensate drain vertical installation 17 Typical Combustion Pipe Drain Tee 18 Upflow Configuration 19 Downfl...

Страница 2: ...ce Air filters in place Set furnace input rate and temperature rise per rating plate marking Means for providing outdoor air required for combustion Return air temperature maintained between 55 F 13 C...

Страница 3: ...al codes the installation must comply with the national codes listed below and all authorities having jurisdiction In the United States and Canada follow all codes and standards for the following usin...

Страница 4: ...FOR FURNACES INSTALLED IN THE COMMON WEALTH OF MASSACHUSETTS ONLY For all side wall horizontally vented gas fueled equipment installed in every dwelling building or structure used in whole or in part...

Страница 5: ...his access cover shall be attached in such a manner as to prevent leaks DUCT FLANGES Four flanges are provided to attach ductwork to the furnace These flanges are rotated down for shipment In order to...

Страница 6: ...ould always be installed on the side desig nated as top side See Figures 4 5 FURNACE ASSEMBLY PC SERIES COILS These upflow coils are designed for installation on top of upflow fur naces only If the co...

Страница 7: ...e unit BOTTOM RETURN AND ATTIC INSTALLATIONS Bottom return applications normally pull return air through a base plat form or return air plenum Be sure the return platform structure or return air plenu...

Страница 8: ...ists Refer to Figure 11 for typical crawl space installation When moving or handling this furnace prior to installation always leave the doors on the furnace to provide support and to prevent damage o...

Страница 9: ...let Gas Pipe Entry Electrical Entry Condensate Drain Optional Return Air Cutout Either side 29 5 For Cladded door add appoximately an additional 75 C SUPPLY END 56 56 20 B 3 23 8 56 Combustion Air Inl...

Страница 10: ...ither side of the furnace using any of the gas pipe entry knockouts on both sides of the furnace Refer to Figure 13 All filters and mounting provision must be field supplied All installa tions must ha...

Страница 11: ...86 TABLE 6 Nominal Manifold Pressure Low Fire First Stage Manifold Pressures in w c First Stage Manifold Pressures kPa Altitude feet Altitude m 0 7999 8000 8999 9000 9999 0 2437 2438 2742 2743 3048 Ga...

Страница 12: ...e common wire to be connected Apply strain relief to thermostat wires passing through cabinet If air condition ing equipment is installed use thermostat wiring to connect the Y and C terminals on the...

Страница 13: ...E STAGE AIR CONDITIONER Part Numbers SAP Legacy 265904 031 09169 449572 1 C 24 Volt Common R 24 Volt Hot Y1 Single Stage Compressor TWO STAGE VARIABLE SPEED FURNACE CONTROL G Fan TWO STAGE VARIABLE SP...

Страница 14: ...Stage Heat B O Switch on Thermostat must be in the O position 24VAC Humidifier Optional External Humidistat Optional Open on Humidity Rise Part Number S1 2HU16700124 O Reversing Valve Energized in Co...

Страница 15: ...M Dehumidification HM Humidistat Step 1 of Thermostat User Configuration Menu must be set to MLTISTG E W1 First Stage Heat 24VAC Humidifer Optional Optional Harness Part Numbers SAP Legacy 265904 031...

Страница 16: ...Legacy 126768 031 09137 18395 031 01996 340512 031 09178 1 1 Part Numbers SAP Legacy 265904 031 09169 449572 2 C 24 Volt Common R 24 Volt Hot Y1 Single Stage Compressor TWO STAGE VARIABLE SPEED FURNA...

Страница 17: ...er drains are combined with the furnace drain then the open stand pipe could be raised higher above the 5 minimum The Figures 24 27 show the condensate drain arrangement for the various possible furna...

Страница 18: ...to tempera tures below freezing adequate measures must be taken to prevent the drain line from freezing Failure to provide proper protection from freezing can result in improper operation or damage t...

Страница 19: ...ff so that no sagging loops will collect and hold condensate which will cause the furnace to not operate Shorten pressure switch hose Re route and shorten pressure switch hose Shorten rain gutter hose...

Страница 20: ...ch hose to this position NOTE May require the longer hose that is provided with wider cabinets Move condensate drain hose to this position may exit either side of the cabinet Move rain gutter hose to...

Страница 21: ...ose to this position NOTE May require the longer hose that is provided with wider cabinets Change condensate drain connection to the 90 fitting provided Move condensate drain hose to this position Mov...

Страница 22: ...ting provided Move condensate drain hose to this position Move rain gutter hose to this position Change condensate drain connection to the 90 fitting provided Move condensate drain hose to this positi...

Страница 23: ...with cement that is approved for use with BOTH materials Metallic materials must not be used for venting or air intake 5 If a flexible connector is used in the vent system it must be made of a materia...

Страница 24: ...o prevent sagging 9 Seal around the openings where the combustion air and or vent piping pass through the roof or sidewalls COMBUSTION AIR VENTING TABLE 10 Equivalent Length of Fittings Fitting Equiva...

Страница 25: ...quirements of the gas supplier 12 30 5 cm or in accordance with local installation codes and the requirements of the gas supplier F Clearance to outside corner 12 30 5 cm or in accordance with local i...

Страница 26: ...m inside the building The vent for a single pipe system must be installed as specified in the venting section of these instructions with the vent terminating as shown in Figure 30 Each furnace must ha...

Страница 27: ...ace surrounding the appliance This may be from within the space in a non confined location or it may be brought into the furnace area from outdoors through permanent openings or ducts It is not piped...

Страница 28: ...Two per manent openings shall communicate directly or by means of ducts with the outdoors crawl spaces or attic spaces 2 One permanent openings commencing within 12 30 5 cm of the top of the enclosure...

Страница 29: ...following steps shall be followed for each appliance connected to the venting system being placed into operation while all other appliances connected to the venting system are not in operation 1 Inspe...

Страница 30: ...proper input rate using natural gas with a heating value of 1030 BTU Ft3 38 4 MJ m3 If the heating value of your gas is significantly different it may be necessary to replace the orifices Verify natur...

Страница 31: ...300 750 78 46 92 231 25 144 288 720 80 45 90 225 26 138 277 692 82 44 88 220 27 133 267 667 84 43 86 214 28 129 257 643 86 42 84 209 29 124 248 621 88 41 82 205 30 120 240 600 90 40 80 200 31 116 232...

Страница 32: ...screws on main gas valve 2 Turn gas and electrical supplies on and follow the operating instructions to place the unit back in operation 3 Adjust manifold pressure by adjusting gas valve regulator scr...

Страница 33: ...that cold air is blown into the heated space The fan off timing may be adjusted by positioning the jumper on two of the four pins as shown in Figure 41 MANIFOLD PRESSURE U TUBE CONNECTION FIGURE 40 R...

Страница 34: ...70 1364 931 C A 986 638 1232 808 D A 1062 685 1225 808 C C 866 576 1117 718 D C HIGH LOW HEAT CFM 060B12 80B12 Jumper Settings High Low High Low HEAT Tap ADJ Tap 1364 843 1433 945 A Any 1253 745 1320...

Страница 35: ...llations where the humidity is frequently very high during cooling season such as in the southern part of the country On a call for cooling the blower will ramp up to 50 of full capacity and will stay...

Страница 36: ...light will stay on continuously In this case the entire control should be replaced as the control is not field repairable Flash sequence codes 1 through 11 are as follows LED will turn ON for 1 4 sec...

Страница 37: ...This feature should only be used by a qualified service tech nician If more than five error codes have occurred since the last reset only the five most recent will be retained The furnace control boa...

Страница 38: ...ral 45 SIGHT GLASS OVAL 2 Req d GASKET FOAM Door 1 5 ft req d PAN CONDENSATE BRACKET DOOR HARNESS WIRING FERRULE 3 Req d GROMMET 3 Req d MOTOR MOUNT TUBING SILICON HOSE RAIN GUTTER HOSE CONDENSATE PLU...

Страница 39: ...438335 UIM C 1209 Johnson Controls Unitary Products 39 SECTION XII WIRING DIAGRAM FIGURE 43 Wiring Diagram...

Страница 40: ...ge without notice Published in U S A 438335 UIM C 1209 Copyright 2009 by Johnson Controls Inc All rights reserved Supersedes 438335 UIM B 0509 Johnson Controls Unitary Products 5005 York Drive Norman...

Отзывы: