background image

3

22

2.4

In airing cupboard installations, the part used as the air heater compartment must comply with the relevant section of BS
5864 and must be completely separated by either a non-combustible partition or a perforated metal partition with the
perforations not exceeding 13mm (1/2in). The secondary flue must be a tight fit where it passes through the partition and
must be suitably protected (see BS 5440: Part 1).

2.5

In under-stairs installations, the compartment must comply with the relevant section of BS 5864, provided that in addition all
internal surfaces (including the base) are non-combustible or lined with non-combustible material. This requirement is
applicable only to dwellings of  more than two storeys.

2.6

In free-standing installations, only one or two walls will be in close proximity to the air heater and these MUST be non-
combustible.

2.7

Where the air heater is to be installed onto a combustible surface and under-floor ducting used, a suitable base tray (BT65/
90) MUST be used in order to provide insulation. 

NB where a base plenum is used no base tray is required!

3.

VENTILATION  AIR

3.1

When installed in a compartment two permanent ventilation openings into the compartment are required, one at high level
and one at low level. The minimum effective areas specified in Table 1 are related to the rated heat input of the air heater.

4.

 DUCT SYSTEM

(See British Design Manual - Gas fired Warm Air Heating)

4.1

RETURN AIR

4.1.1

Room-sealed appliances may be installed without return air ducting, provided that the path between the return air
grille and the appliance return air inlet is protected in such a manner that the required air-flow will be maintained at all
times. The return air grille MUST have a free area of not less than 2118cm

 (328in

2

). It is recommended that the return

air duct not be routed directly from the main living area, but from a convenient central area serving the remainder of
the dwelling.

4.1.2

The return air system should be constructed of fire-resistant material. The flue shall not be run through an area
serving as a return air plenum. It is extremely important that the correct size of return air grilles and ducting is used.
For heaters on maximum output the return air duct size should not be less than the equivalent of 400mm x 300mm
(16" x 12"). If flexible duct is used the duct diameter should not be less than 406mm (16") dia. The return air grille
should have a free area of not less than 2118cm

2

 (328in

2

).

4.1.3

An adequate and unobstructed return air path is essential from areas not served by a directly ducted return and to
which warm air is delivered. All such rooms should be fitted with relief grilles which have a free area of 0.0088m

2

/kW

(1in

2

/250Btu/h) of heat supplied to the room. The only exceptions are kitchens, bathrooms and WC.’s.

4.1.4

The return air duct should allow for ease of removal for access to the flue.

4.1.5

All duct work in the room or internal space in which the heater is installed shall be mechanically secured and sealed
with ducting tape.

4.2

WARM  DELIVERED AIR

4.2.1

 All duct work, including riser ducts, should be fully insulated with 50mm (2in) fibreglass or similar. If short extended
duct runs are taken below floor level these should be similarly insulated and in addition wrapped with a sound
vapour proof barrier. They must also be protected from crushing.

4.2.2

The duct system should be carefully designed (as given in the guidelines in the British System Design Manual) to
suit the needs of specific heating requirements and building layout. The type of duct system (e.g. radial/extended
plenum/ stepped) should be installed
using the least number of fittings to
minimise airflow resistance. The base
duct, which equalises the air pressure
to supply ducts, must be constructed
to support the weight of the heater,
which must be sealed using self-
adhesive foam strip, ducting tape or
sealing compound. All ducting and
blanking plates must be mechanically
secured and sealed.

VENTILATED FROM INSIDE
BUILDING

Low level grille 297cm

(48in

2

)

High level grille 297cm

(48in

2

)

VENTILATED FROM OUTSIDE
BUILDING

Low level grille 149cm

(24in

2

)

High level grille 149cm

(24in

2

)

Table 1:

Minimum Effective Areas

WARM AIR HEATER AND CIRCULATOR
COMMISSIONING CHECKLIST

WARM AIR UNIT

BENCHMARK Number

HOT WATER GENERATOR

CONTROLS

 to comply with the Building Regulations, each section must have a tick on one or other of the boxes

APPLIANCE  SERIAL  NUMBER:  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NOTIFICATION  No:  . . . . . . . . . . . . . . . . . . . . . . . . . . . .

APPLIANCE  SERIAL  NUMBER:  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NOTIFICATION  No:  . . . . . . . . . . . . . . . . . . . . . . . . . . . .

REQUIREMENT

1. Time & temp control to heating

2. Time & temp control to hot water

3. Heating zone valves

4. Thermostatic Radiator Valves

5. Boiler interlock

MEASURES PROVIDED

Room stat & integral timer

Cylinder stat & Integral timer

Fitted

Not Required

Fitted

Not Required

Provided

Not Required

FOR WARM AIR HEATERS ONLY

Has the system been balanced in accordance with the heater manufacturer’s instructions?

YES

NO

Was an anemometer used?

YES

NO

Have balancing dampers been fitted?

YES

NO

FOR WARM AIR HEATING: MEASURE AND RECORD

Burner operating pressure

Mbar

Heat input

KW

Temperature differential between return air inlet and nearest outlet

o

C

FOR HOT WATER GENERATORS: MEASURE AND RECORD

Burner operating pressure

Mbar

Heat input

KW

Water flow temperature

o

C

Does the heating & hot water system comply with the appropriate building regulations?

YES

NO

Has the appliance and associated controls been installed & commissioned in accordance with manufacturer’s instructions?

YES

NO

Have you demonstrated the operation of the appliance & system controls to the customer?

YES

NO

Have you left all the manufacturer’s literature with the customer

YES

NO

Competent  person’s  signature  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Customer’s  Signature  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

(To confirm demonstration of equipment & receipt of appliance instructions)

COMMISSIONING ENGINEER’S DETAILS

Name  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Commissioning  Date  . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Address  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Tel  No  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CORGI  REGISTRATION  No  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CORGI  ID  SERIAL  No  . . . . . . . . . . . . . . . . . . . . . . . . . . .

FOR ALL PRODUCTS

Содержание ECONOMAIRE 90

Страница 1: ...7a 1000 0705350 Cross light injector Bray Cat 10 110 1 8 E39538 BOS02397 1 Ignition burner assembly 1 9 1000 0522250 Air pressure switch 1 10 E69632 1000 0520830 Clock mechanism 1 11 1000 0708860 Igni...

Страница 2: ...partment should be not less than 75mm 3 in However if clearances are less than 75mm the internal surface of the compartment must be lined with non combustible material and the compartment must be of a...

Страница 3: ...low for ease of removal for access to the flue 4 1 5 All duct work in the room or internal space in which the heater is installed shall be mechanically secured and sealed with ducting tape 4 2 WARM DE...

Страница 4: ...1 11 Where the total flue length exceeds these lengths the flue orifice MUST be removed 5 1 12 The heater is supplied with either a horizontal or vertical flue dependant upon your specification when...

Страница 5: ...minal positions 5 3 7 Reference should be made to Table 2 for the required terminal components Fig 16 ECONOMAIRE90 PrincipalDimensions SIDE VIEW PLAN VIEW FRONT VIEW BASE VIEW KNOCKOUT FOR GAS ENTRY B...

Страница 6: ...NTS COLOUR 1000 0016520 1 X 90 Standard Flue Elbow White 1000 0016530 1 X 45 Flue Elbows White 1000 0016550 1 X 500mm Extension White 1000 0016540 1 X 1000mm Extension White 1000 0016560 1 X Vertical...

Страница 7: ...pipe from the meter is to be preferred wherever possible Where this is not possible the pipe must be capable of taking the complete input of the heater and all other gas appliances being served by th...

Страница 8: ...imal point DP in the bottom right hand corner of the LED display will flash continuously 6 3 8 The igniter will spark for a maximum period of 60 seconds during which time the ignition and main burners...

Страница 9: ...0 seconds 6 6 10 Depress the RESET button on the Indicator Panel 6 6 11 The heater will go through its ignition procedure and the ignition and main burners SHOULD ignite 6 6 12 Set the AIR HEATER swit...

Страница 10: ...3 Burner Pressure Adjuster 4 Ignition Controller A Side view photograph With Ignition Controller in place B Rear view drawing With Ignition Controller removed 1 2 3 4 1 3 2 1 4 3 2 500 0 23 mbar 0 625...

Страница 11: ...as a complete unit together with the multifunction control PROCEDURE 8 2 1 Ensure that the gas and electrical supplies are switched OFF 8 2 2 Remove the front door from the heater 8 2 3 Remove the fix...

Страница 12: ...the electrical supply is isolated 8 7 2 Remove the appliance front door and release the 3 x securing screws on the electrical door assembly 8 7 3 Open the door assembly outwards on its hinges see fig...

Страница 13: ...the electrical supply is isolated 8 7 2 Remove the appliance front door and release the 3 x securing screws on the electrical door assembly 8 7 3 Open the door assembly outwards on its hinges see fig...

Страница 14: ...as a complete unit together with the multifunction control PROCEDURE 8 2 1 Ensure that the gas and electrical supplies are switched OFF 8 2 2 Remove the front door from the heater 8 2 3 Remove the fix...

Страница 15: ...3 Burner Pressure Adjuster 4 Ignition Controller A Side view photograph With Ignition Controller in place B Rear view drawing With Ignition Controller removed 1 2 3 4 1 3 2 1 4 3 2 500 0 23 mbar 0 625...

Страница 16: ...0 seconds 6 6 10 Depress the RESET button on the Indicator Panel 6 6 11 The heater will go through its ignition procedure and the ignition and main burners SHOULD ignite 6 6 12 Set the AIR HEATER swit...

Страница 17: ...imal point DP in the bottom right hand corner of the LED display will flash continuously 6 3 8 The igniter will spark for a maximum period of 60 seconds during which time the ignition and main burners...

Страница 18: ...pipe from the meter is to be preferred wherever possible Where this is not possible the pipe must be capable of taking the complete input of the heater and all other gas appliances being served by th...

Страница 19: ...NTS COLOUR 1000 0016520 1 X 90 Standard Flue Elbow White 1000 0016530 1 X 45 Flue Elbows White 1000 0016550 1 X 500mm Extension White 1000 0016540 1 X 1000mm Extension White 1000 0016560 1 X Vertical...

Страница 20: ...minal positions 5 3 7 Reference should be made to Table 2 for the required terminal components Fig 16 ECONOMAIRE90 PrincipalDimensions SIDE VIEW PLAN VIEW FRONT VIEW BASE VIEW KNOCKOUT FOR GAS ENTRY B...

Страница 21: ...1 11 Where the total flue length exceeds these lengths the flue orifice MUST be removed 5 1 12 The heater is supplied with either a horizontal or vertical flue dependant upon your specification when...

Страница 22: ...low for ease of removal for access to the flue 4 1 5 All duct work in the room or internal space in which the heater is installed shall be mechanically secured and sealed with ducting tape 4 2 WARM DE...

Страница 23: ...partment should be not less than 75mm 3 in However if clearances are less than 75mm the internal surface of the compartment must be lined with non combustible material and the compartment must be of a...

Страница 24: ...7a 1000 0705350 Cross light injector Bray Cat 10 110 1 8 E39538 BOS02397 1 Ignition burner assembly 1 9 1000 0522250 Air pressure switch 1 10 E69632 1000 0520830 Clock mechanism 1 11 1000 0708860 Igni...

Отзывы: