8

Fig. 2

Worked example of equivalent flue height

6

5.1.12 Special consideration must be given to external flues with a view to prevention of condensation and weathering

problems.

5.1.13 An approved terminal should always be used; a ridge terminal or “GC1” terminal is specifically recommended.

The latter should be positioned in a free air space where it is not shielded by any structure. A minimum of 1m

(3ft.) from any vertical or inclined roof structure must be allowed for.

5.1.13 Where flue blocks are used, builders should ensure that no obstruction is created during erection. The installer

should ensure that the connection flue does not project beyond the internal wall of the flue blocks and that there

is provision for examination and servicing.

5.1.13

Important:  

Before installing the appliance, carry out a visual check of the flue system as directed in the relevant

section of BS5440 Pt.1, then check the flue performance as follows:-
a.

Close all doors and windows in the room in which the appliance is to be installed.

b.

Introduce some heat into the flue, using a blow torch or other means.

c.

Carry out a flow visualisation check with a smoke pellet at the intended position for the appliance. Ensure

that there is discharge of smoke from the correct terminal only, and no spillage into the room.

Smoke coming out of other than the correct terminal only, or a down draught or ‘no flow’ condition,

indicates that the flue has failed the test, and the appliance shall not be connected until the defect has been

found and rectified, and the test satisfactorily completed.

23

1.6m

4.6m

H

a

 = 6.2m

STET Terminal

2 x 300 mm lengths

4 x 1000 mm lengths

45

O

 bend

45

O

 bend

2 x 300 mm lengths

300 mm length

Appliance draught

diverter

100 mm dia flue pipe

Fig. 5a, MODAIRFLOW CIRCUIT DIAGRAM

14

15

Содержание 42-451-15

Страница 1: ...N G H O T W AT E R V E N T I L AT I O N HI SPEC J90 Warm Air Heater with Modairflow or Non Modairflow Control Hi Spec J90 G C No 42 451 15 These instructions are to be left with the User Publication...

Страница 2: ...ill be required in the event of any warranty work and as supporting documentation relating to home improvements in the optional documents section of the Home Improvements In the interest of continuous...

Страница 3: ...ate Plate 12 Fan delay control non Modairflow 13 Airflow sensor Modairflow models 14 Piezo unit 15 Electronics module MODAIRFLOW 16 Time control 2 3 5 6 7 8 9 10 11 13 12 14 15 16 4 1 Fig 1 1 1 HI SPE...

Страница 4: ...ee BS 5440 Part 1 2 5 In under stairs installations the compartment must comply with the relevant section of BS 5864 provided that in addition all internal surfaces including the base are non combusti...

Страница 5: ...led shall be mechanically secured and sealed with ducting tape 4 2 WARM DELIVEREDAIR 4 2 1 All duct work including riser ducts should be fully insulated with 50mm 2in fibreglass or similar If short ex...

Страница 6: ...ans Where this is not practicable the existing flue system may be used providing there is no evidence of spillage from the old appliance see 5 1 9 above Every effort must be made however to ensure tha...

Страница 7: ...ck Any 0 50 Chimney 213 x 213 0 02 Terminal 100 mm ridge 2 5 125 mm ridge 1 0 90O Bend 100 mm pipe 1 22 per 150 mm ridge 0 48 125 mm pipe 0 50 fitting 100 mm GCI 0 6 150 mm pipe 0 24 125 mm GCI 0 25 1...

Страница 8: ...Important Before installing the appliance carry out a visual check of the flue system as directed in the relevant section of BS5440 Pt 1 then check the flue performance as follows a Close all doors a...

Страница 9: ...x 1 5m 5ft from the floor b Avoid the following locations i In a room where temperature is greatly affected by the sun or any other heat source e g radiant fire wall light fittings or TV set ii Near a...

Страница 10: ...t point cover and fit a pressure test gauge refer fig 4 6 3 3 Turn the heater Gas supply ON test for gas soundness and purge the whole gas pipe as described in BS 6891 6 3 4 Referring to Fig 4 press a...

Страница 11: ...6 7 2 Turn the Thermista stat or room thermostat slowly clockwise until the Main Burner ignites 6 7 3 Ensure that the Air Circulation Fan starts to operate after a short period approx 1 2 minutes MOD...

Страница 12: ...the gas supply at the service cock and ensure that the Multifunctional Control fail safe operates within 60 secs indicated by loud click from Multifunctional Control 6 8 4 Turn gas supply ON at the S...

Страница 13: ...ts 7 2 6 How to obtain summer air circulation 7 2 7 That the air grilles on the heater or heater compartment grilles and ventilators in the walls windows or doors of the building must not be obstructe...

Страница 14: ...n switches on check for any air leaks between the air heater and the Base Plenum paying particular attention to heaters with rear Draught Diverters Rectify any air leaks before continuing with this pr...

Страница 15: ...8 2 8 6 2 Disconnect the Thermocouple at the Multifunctional Control including the adapter avoiding damage to the capillary 8 6 3 Disconnect the Pilot Feed Pipe from the Multifunctional Control 8 6 4...

Страница 16: ...that the electrical supply is isolated 8 12 2 Release the securing screw situated on the lower face of the Time Control and remove the Time Control by partially withdrawing the bottom and then liftin...

Страница 17: ...Bracket to the TTBAssembly and withdraw the bracket 8 14 10 Disconnect the TTB from its conductors 8 14 11 Refitting or replacement is in reverse order 8 15 HEATEXCHANGERACCESS 8 15 1 Ensure that the...

Страница 18: ...d Clear pilot orifice or replace pilot injector iv Piezo system faulty Check igniter lead and electrode v Excessive gas supply pressure Check that mains gas pressure is 20mbar and reduce if necessary...

Страница 19: ...ocouple Capillary 8 5 7 Release the Electrode securing nut from the Pilot BurnerAssembly and withdraw the Electrode 8 5 8 Release the Pilot Feed Pipe securing nut from the Pilot Burner Assembly and wi...

Страница 20: ...LE Y N IS FUSE OK REPLACE FUSE N Y CHECK FOR VOLTAGE AT FAN LIVE TO NEUTRAL Y REPLACE FAN DOES FAN START N BRIDGE OUT AIRFLOW SENSOR Y REPLACE AIRFLOW SENSOR REPLACE TRANSFORMER REPLACE MULTIFUNCTIONA...

Страница 21: ...N TURN GAS ON N LIGHT PILOT Y Y SWITCH ON 230 V N Y N Y REPLACE FUSE N Y REPLACE MULTIFUNCTIONAL CONTROL SET CONTROLS CORRECTLY Y N CHECK POLARITY OF THERMISTA STAT CONNECTIONS Y IS POLARITY CORRECT...

Страница 22: ...HEATERIS LESS THAN 60 c Y Y CHECKMAINBURNER PRESSURESETTINGS ARECORRECT SET TO CORRECT PRESSURE SETTING N Y SET FAN BALANCING SCREW Y DOES FAN SPEED UP N Y REPLACE ELECTRONIC MODULE REPLACE ELECTRONIC...

Страница 23: ...SENSOR Y DOES FAN STILL RUN REPLACE ELECTRONICS MODULE Y IS PILOT FLAME TOO BIG N Y ADJUST PILOT FLAME TO CORRECT SETTING REPLACE AIRFLOW SENSOR N MAIN BURNER ONLYFIRES FOR SHORT PERIODS DEFECT IS IN...

Страница 24: ...www johnsonandstarley co uk 24 23 Fig 5a MODAIRFLOW CIRCUIT DIAGRAM 11 WIRING DIAGRAMS Fig 5a MODAIRFLOW CIRCUIT DIAGRAM...

Страница 25: ...25 Sales Spares Replacement Help Line 01604 762881 Fig 5b Non MODAIRFLOW CIRCUIT DIAGRAM...

Страница 26: ...www johnsonandstarley co uk 26 12 FUNCTIONAL DIAGRAMS Fig 6a Non MODAIRFLOW FUNCTIONAL DIAGRAM...

Страница 27: ...27 Sales Spares Replacement Help Line 01604 762881 Fig 6b Non MODAIRFLOW FUNCTIONAL DIAGRAM...

Страница 28: ...www johnsonandstarley co uk 28 13 DIMENSIONS Fig 7 HI SPEC J90 DIMENSIONS...

Страница 29: ...29 Sales Spares Replacement Help Line 01604 762881 14 NOTES...

Страница 30: ...971 B300 0706000 Igniter Bracket 1 23 230 394 BOS 00836 Gasket for heat exchanger cap 3 24 E02 557 J652 0161000 Lower Compartment Door 1 MODAIRFLOW MODELS 25 E02 951 J903 0156000 Fan Compartment Door...

Страница 31: ...31 Sales Spares Replacement Help Line 01604 762881 16 EXPLODED DIAGRAM Fig 8 HI SPEC J90 EXPLODED DIAGRAM...

Страница 32: ...PAK65 4 Free Standing Kit FS90 5 Return Air Kit RAK65 6 Cleanflow Electronic Air Cleaner CF 90H 7 Replacement Pads A0354X0357 Warm Air Heating fully complies with PART L OF THE BUILDING REGULATIONS by...

Страница 33: ...to the customer any remedial or improvement work identified during the course of commissioning or servicing work Refer to the manufacturer s helpline where assistance is needed Report product faults...

Страница 34: ...Automatic bypass system Fitted Not required Warm Air Unit Interlock Yes No If YES Volume Litres FOR WARM AIR HEATERS ONLY Has the system been balanced in accordance with the heater manufacture s instr...

Страница 35: ...Comments Signature SERVICE 05 Date Engineer name Company name Telephone No Operative ID No Comments Signature SERVICE 07 Date Engineer name Company name Telephone No Operative ID No Comments Signatur...

Страница 36: ...sales johnsonandstarley co uk marketing johnsonandstarley co uk Reception Customer Service 01604 762881 Fax 01604 767408 Anniversary 1922 2012 In the interest of continuous development Johnson Starley...

Отзывы: