SAFETY CHECKS

:

6.8.1

Check for gas soundness within the appliance.

6.8.2

Spillage test: 

Carry out a full spillage test as follows, and ensure that the flue operates effectively with all doors

closed and any extractor fans in operation.

NOTE: 

If an extractor fan is situated in an adjoining or adjacent room, carry out the spillage test with the interconnecting

doors open.

If the draught diverter is accessible:

a.

Introduce smoke into the Draught Diverter adjacent to an exit from the Heat Exchanger, by means a smoke

match or puffer.

b.

Ensure that there is no spillage present (indicated by displacement of smoke downwards and out of the

Draught Diverter).

If the Draught Diverter is not accessible:

a.

Introduce smoke, by means of 

part

 of a smoke pellet on a non-combustible support, into the Heat

Exchanger.

b.

Extinguish the Main and Pilot Burners.

c.

Ensure that there is no spillage evident by visually observing the Draught Diverter location on the air

heater.

d.

If spillage is evident, further investigation and rectification is required before re-testing the appliance.

e.

Repeat spillage tests but with the fan running, or Summer Airflow switch set to ON.

WARNING: The appliance shall not be left connected to the gas supply unless it has successfully passed

the above spillage test.

6.8.3

Turn OFF the gas supply at the service cock and ensure that the Multifunctional Control fail-safe operates within

60 secs (indicated by loud click from Multifunctional Control).

6.8.4 Turn gas supply ON at the Service Cock.
6.8.5 Switch the appliance electrical supply OFF.
6.8.6

MODAIRFLOW models

, disconnect the Air Circulation Fan at the flying socket

6.8.7

Non-MODAIRFLOW models

, disconnect the Air Circulation Fan at the Electrical Panel.

6.8.8

Switch the appliance electrical supply ON.

6.8.9

Ignite the Main and Pilot Burners as detailed in sub para 6.3.1 to 6.3.5

6.8.10 Ensure that the Limit Switch operates, indicated by the Main Burner extinguishing, within 120 and 180 seconds.
6.8.11 Switch the appliance electrical supply OFF.
6.8.12 Reconnect the Air Circulation Fan.
6.8.13 Switch the appliance electrical supply ON.
6.8.14 Ensure that the Main Burner re-ignites when the appliance temperature reduces, (

note:

with the fan disconnected,

there may be some delay before the Main Burner re-ignites).

Low Rate

Low Medium Rate

High Medium Rate

High Rate

kW

  MJ/h   Btu/h

kW

 MJ/h   Btu/h

kW

MJ/h   Btu/h

kW

MJ/h   Btu/h

INPUT

27.8 100.0   94,780

30.2 108.6   102,965

32.9 118.5 112,325

34.8

125.2 118,665

OUTPUT

20.5 73.9   70,000

22.6 81.2   77,000

24.6 88.6   84,000

26.4

95.0 90,000

Gas rate cv

2.65m

3

/h (93.58ft

3

/h)

  2.87

3

/h (101.66ft

3

/h)

3.14m

3

/h (110.90ft

3

/h)

3.31m

3

/h (117.17ft

3

/h)

1037Btu/ft

3

Burner setting

   11.0mbar (4.4 in wg)

  13.3mbar (5.3 in wg)

   14.8mbar (5.9 in wg)

17.0mbar (6.8 in wg)

pressure (hot)
Main Injector

BRAY CAT 23/700

Table 4

Main Burner Pressure Settings

19

REPLACE

ELECTRONIC

MODULE

WIRING DEFECT

BETWEEN HEATER

&

THERMISTA-STAT

MAIN BURNER NOT OPERATING

IS

PILOT

LIT ?

IS 230V

SUPPLY

ON ?

IS TIME

CONTROL &

THERMISTA-STAT

CORRECTLY

SET ?

CHECK

TERMINAL

D9 IS

18V

CHECK

TERMINAL

C8 IS

230V

CHECK

TERMINAL

C10 IS

24V

IS

GAS

ON ?

N

TURN GAS

ON

N

LIGHT

PILOT

Y

Y

SWITCH ON

230 V

N

Y

N

Y

REPLACE

FUSE

N

Y

REPLACE

MULTIFUNCTIONAL

CONTROL

SET CONTROLS

CORRECTLY

Y

N

CHECK POLARITY OF

THERMISTA-STAT

CONNECTIONS

Y

IS

POLARITY

CORRECT ?

N

RECTIFY

DEFECT

Y

BRIDGE THERMISTA-STAT

TERMINALS AT HEATER

BRIDGE THERMISTA-STAT

TERMINALS AT HEATER

IS

BURNER

LIT ?

IS

BURNER

LIT ?

N

Y

N

N

Y

N

CHECK, TTB

LIMIT SWITCH

&

CONNECTIONS

Y

N

CHECK 230V I/P

& TIME CONTROL

OPERATION

REPLACE

THERMISTA-STAT

REPLACE

TRANSFORMER

Y

IS

FUSE

OK ?

CHECK

24V AT

MULTIFUNC-

TIONAL

CONTROL

Содержание 42-451-15

Страница 1: ...N G H O T W AT E R V E N T I L AT I O N HI SPEC J90 Warm Air Heater with Modairflow or Non Modairflow Control Hi Spec J90 G C No 42 451 15 These instructions are to be left with the User Publication...

Страница 2: ...ill be required in the event of any warranty work and as supporting documentation relating to home improvements in the optional documents section of the Home Improvements In the interest of continuous...

Страница 3: ...ate Plate 12 Fan delay control non Modairflow 13 Airflow sensor Modairflow models 14 Piezo unit 15 Electronics module MODAIRFLOW 16 Time control 2 3 5 6 7 8 9 10 11 13 12 14 15 16 4 1 Fig 1 1 1 HI SPE...

Страница 4: ...ee BS 5440 Part 1 2 5 In under stairs installations the compartment must comply with the relevant section of BS 5864 provided that in addition all internal surfaces including the base are non combusti...

Страница 5: ...led shall be mechanically secured and sealed with ducting tape 4 2 WARM DELIVEREDAIR 4 2 1 All duct work including riser ducts should be fully insulated with 50mm 2in fibreglass or similar If short ex...

Страница 6: ...ans Where this is not practicable the existing flue system may be used providing there is no evidence of spillage from the old appliance see 5 1 9 above Every effort must be made however to ensure tha...

Страница 7: ...ck Any 0 50 Chimney 213 x 213 0 02 Terminal 100 mm ridge 2 5 125 mm ridge 1 0 90O Bend 100 mm pipe 1 22 per 150 mm ridge 0 48 125 mm pipe 0 50 fitting 100 mm GCI 0 6 150 mm pipe 0 24 125 mm GCI 0 25 1...

Страница 8: ...Important Before installing the appliance carry out a visual check of the flue system as directed in the relevant section of BS5440 Pt 1 then check the flue performance as follows a Close all doors a...

Страница 9: ...x 1 5m 5ft from the floor b Avoid the following locations i In a room where temperature is greatly affected by the sun or any other heat source e g radiant fire wall light fittings or TV set ii Near a...

Страница 10: ...t point cover and fit a pressure test gauge refer fig 4 6 3 3 Turn the heater Gas supply ON test for gas soundness and purge the whole gas pipe as described in BS 6891 6 3 4 Referring to Fig 4 press a...

Страница 11: ...6 7 2 Turn the Thermista stat or room thermostat slowly clockwise until the Main Burner ignites 6 7 3 Ensure that the Air Circulation Fan starts to operate after a short period approx 1 2 minutes MOD...

Страница 12: ...the gas supply at the service cock and ensure that the Multifunctional Control fail safe operates within 60 secs indicated by loud click from Multifunctional Control 6 8 4 Turn gas supply ON at the S...

Страница 13: ...ts 7 2 6 How to obtain summer air circulation 7 2 7 That the air grilles on the heater or heater compartment grilles and ventilators in the walls windows or doors of the building must not be obstructe...

Страница 14: ...n switches on check for any air leaks between the air heater and the Base Plenum paying particular attention to heaters with rear Draught Diverters Rectify any air leaks before continuing with this pr...

Страница 15: ...8 2 8 6 2 Disconnect the Thermocouple at the Multifunctional Control including the adapter avoiding damage to the capillary 8 6 3 Disconnect the Pilot Feed Pipe from the Multifunctional Control 8 6 4...

Страница 16: ...that the electrical supply is isolated 8 12 2 Release the securing screw situated on the lower face of the Time Control and remove the Time Control by partially withdrawing the bottom and then liftin...

Страница 17: ...Bracket to the TTBAssembly and withdraw the bracket 8 14 10 Disconnect the TTB from its conductors 8 14 11 Refitting or replacement is in reverse order 8 15 HEATEXCHANGERACCESS 8 15 1 Ensure that the...

Страница 18: ...d Clear pilot orifice or replace pilot injector iv Piezo system faulty Check igniter lead and electrode v Excessive gas supply pressure Check that mains gas pressure is 20mbar and reduce if necessary...

Страница 19: ...ocouple Capillary 8 5 7 Release the Electrode securing nut from the Pilot BurnerAssembly and withdraw the Electrode 8 5 8 Release the Pilot Feed Pipe securing nut from the Pilot Burner Assembly and wi...

Страница 20: ...LE Y N IS FUSE OK REPLACE FUSE N Y CHECK FOR VOLTAGE AT FAN LIVE TO NEUTRAL Y REPLACE FAN DOES FAN START N BRIDGE OUT AIRFLOW SENSOR Y REPLACE AIRFLOW SENSOR REPLACE TRANSFORMER REPLACE MULTIFUNCTIONA...

Страница 21: ...N TURN GAS ON N LIGHT PILOT Y Y SWITCH ON 230 V N Y N Y REPLACE FUSE N Y REPLACE MULTIFUNCTIONAL CONTROL SET CONTROLS CORRECTLY Y N CHECK POLARITY OF THERMISTA STAT CONNECTIONS Y IS POLARITY CORRECT...

Страница 22: ...HEATERIS LESS THAN 60 c Y Y CHECKMAINBURNER PRESSURESETTINGS ARECORRECT SET TO CORRECT PRESSURE SETTING N Y SET FAN BALANCING SCREW Y DOES FAN SPEED UP N Y REPLACE ELECTRONIC MODULE REPLACE ELECTRONIC...

Страница 23: ...SENSOR Y DOES FAN STILL RUN REPLACE ELECTRONICS MODULE Y IS PILOT FLAME TOO BIG N Y ADJUST PILOT FLAME TO CORRECT SETTING REPLACE AIRFLOW SENSOR N MAIN BURNER ONLYFIRES FOR SHORT PERIODS DEFECT IS IN...

Страница 24: ...www johnsonandstarley co uk 24 23 Fig 5a MODAIRFLOW CIRCUIT DIAGRAM 11 WIRING DIAGRAMS Fig 5a MODAIRFLOW CIRCUIT DIAGRAM...

Страница 25: ...25 Sales Spares Replacement Help Line 01604 762881 Fig 5b Non MODAIRFLOW CIRCUIT DIAGRAM...

Страница 26: ...www johnsonandstarley co uk 26 12 FUNCTIONAL DIAGRAMS Fig 6a Non MODAIRFLOW FUNCTIONAL DIAGRAM...

Страница 27: ...27 Sales Spares Replacement Help Line 01604 762881 Fig 6b Non MODAIRFLOW FUNCTIONAL DIAGRAM...

Страница 28: ...www johnsonandstarley co uk 28 13 DIMENSIONS Fig 7 HI SPEC J90 DIMENSIONS...

Страница 29: ...29 Sales Spares Replacement Help Line 01604 762881 14 NOTES...

Страница 30: ...971 B300 0706000 Igniter Bracket 1 23 230 394 BOS 00836 Gasket for heat exchanger cap 3 24 E02 557 J652 0161000 Lower Compartment Door 1 MODAIRFLOW MODELS 25 E02 951 J903 0156000 Fan Compartment Door...

Страница 31: ...31 Sales Spares Replacement Help Line 01604 762881 16 EXPLODED DIAGRAM Fig 8 HI SPEC J90 EXPLODED DIAGRAM...

Страница 32: ...PAK65 4 Free Standing Kit FS90 5 Return Air Kit RAK65 6 Cleanflow Electronic Air Cleaner CF 90H 7 Replacement Pads A0354X0357 Warm Air Heating fully complies with PART L OF THE BUILDING REGULATIONS by...

Страница 33: ...to the customer any remedial or improvement work identified during the course of commissioning or servicing work Refer to the manufacturer s helpline where assistance is needed Report product faults...

Страница 34: ...Automatic bypass system Fitted Not required Warm Air Unit Interlock Yes No If YES Volume Litres FOR WARM AIR HEATERS ONLY Has the system been balanced in accordance with the heater manufacture s instr...

Страница 35: ...Comments Signature SERVICE 05 Date Engineer name Company name Telephone No Operative ID No Comments Signature SERVICE 07 Date Engineer name Company name Telephone No Operative ID No Comments Signatur...