www.johnsonandstarley.co.uk
8
FIGURE 4. TERMINAL POSITIONS
TABLE 3. TERMINAL DIMENSIONS
TERMINAL POSITION
MINIMUM DISTANCE
A
Directly below an opening, air brick, opening window etc
300mm
B
Above an opening, air brick, opening window, etc.
300mm
C
Horizontally to an opening, air brick, opening window etc.
300mm
D
Below gutters, soil pipes or drain pipes.
75mm
E
Below eaves.
200mm
F
Below balconies.
200mm
G
From a vertical drain pipe or soil pipe.
150mm
H
From an internal or external corner. Greater than 450mm protrusion.
300mm
I
Above ground, roof or balcony level.
300mm
J
From a surface facing the terminal.
600mm
K
From a terminal facing the terminal.
1,200mm
M
Vertically from a terminal on the same wall.
1,500mm
N
Horizontally from a terminal on the same wall.
300mm
Q
Above intersection with roof.
530mm
P
From a vertical structure on the roof
300mm
R
From the terminal to the boundary
300mm
Содержание 42-416-18
Страница 21: ...21 Sales Spares Replacement Help Line 01604 762881 FIGURE 14 CONTROL FLOWCHART 19 FAULT FINDING...
Страница 22: ...www johnsonandstarley co uk 22 FIGURE 15 AIR HEATER DIAGNOSIS FLOWCHART...
Страница 23: ...23 Sales Spares Replacement Help Line 01604 762881 FIGURE 16 WATER CIRCULATOR FLOW CHART...
Страница 24: ...www johnsonandstarley co uk 24 20 LOGIC DIAGRAM FIGURE 17 LOGIC DIAGRAM...
Страница 25: ...25 Sales Spares Replacement Help Line 01604 762881 3 21 SCHEMATIC DIAGRAM FIGURE 19 SCHEMATIC DIAGRAM...
Страница 27: ...27 Sales Spares Replacement Help Line 01604 762881 FIGURE 20 ECONOMAIRE 65 DIMENSIONS 23 DIMENSIONS...
Страница 29: ...29 Sales Spares Replacement Help Line 01604 762881 25 EXPLODED DIAGRAM FIGURE 21 ECONOMAIRE 65 EXPLODED DIAGRAM...