It  is  recommended  that  the Temperature-Pressure  Relief  Valve 

should be checked to ensure that it is in operating condition every 

6 months.

When checking the Temperature-Pressure Relief Valve operation, 

make sure that (1) no one is in front of or around the outlet of the 

Temperature-Pressure Relief Valve discharge line, and (2) that 

the water discharge will not cause any property damage, as the 

water may be extremely hot. Use care when operating valve as 

the valve may be hot.
To  check  the  relief  valve,  lift  the  lever  at  the  end  of  the  valve 

several times, see Figure 20. The valve should seat properly and 

operate freely.
If after manually operating the valve, it fails to completely reset 

and  continues  to  release  water,  immediately  close  the  cold 

water inlet to the water heater and drain the water heater, see 

Draining And Flushing on page 25. Replace the Temperature-

Pressure Relief Valve with a properly rated/sized new one, see 

Temperature-Pressure Relief Valve on page 11 for instructions 

on replacement.

DISCHARGE PIPE

TEMPERATURE-PRESSURE

RELIEF VALVE

FIGURE 20.

If the Temperature-Pressure Relief Valve on the water heater 

weeps or discharges periodically, this may be due to thermal 

expansion.

NOTE:

 Excessive water pressure is the most common cause 

of  Temperature-Pressure  Relief  Valve  leakage.  Excessive 

water  system  pressure  is  most  often  caused  by  “thermal 

expansion” in a “closed system.” See Closed Water Systems 

and Thermal Expansion on page 10. The Temperature-

Pressure Relief Valve is not intended for the constant relief of 

thermal expansion.
Temperature-Pressure Relief Valve leakage due to pressure 

build  up  in  a  closed  system  that  does  not  have  a  thermal 

expansion  tank  installed  is  not  covered  under  the  limited 

warranty.  Thermal  expansion  tanks  must  be  installed  on  all 

closed water systems.

DO NOT PLUG THE TEMPERATURE-PRESSURE RELIEF 

VALVE OPENING. THIS CAN CAUSE PROPERTY DAMAGE, 

SERIOUS INJURY OR DEATH.

Explosion Hazard

Temperature-Pressure Relief Valve

must comply with ANSI Z21.22-

CSA 4.4 and ASME code.

Properly sized temperature-

pressure relief valve must be

installed in opening provided.
Can result in overheating and

excessive tank pressure.
Can cause serious injury or death.

HOUSEKEEPING

Fire and Explosion Hazard

Do  not  obstruct combustion air 

openings at the bottom of the 

water heater.

Do not use or store flammable vapor

products such as gasoline, solvents

or adhesives in the same room or area 

near water heater or other appliance.
Can cause serious injury or death.

Vacuum around base of water heater for dust, dirt, and lint on a 

regular basis.

INSTALLED  IN  SUITABLE AREA: To  insure  sufficient  ventilation 

and combustion air supply, proper clearances from the water heater 

must be maintained. See “Locating the New Water Heater” section. 

Combustible  materials  such  as  clothing,  cleaning  materials,  or 

flammable liquids, etc. must not be placed against or adjacent to 

the water heater which can cause a fire.

ANODE ROD INSPECTION

Property Damage Hazard

• 

Avoid water heater damage.

• 

Inspection and replacement of anode rod required.

CAUTION

The anode rod is used to protect the tank from corrosion. Most 

hot water tanks are equipped with an anode rod. The submerged 

rod sacrifices itself to protect the tank. Instead of corroding the 

tank, water ions attack and eat away the anode rod. This does not 

affect water’s taste or color. The rod must be maintained to keep 

the tank in operating condition.
Anode deterioration depends on water conductivity, not necessarily 

water  condition. A  corroded  or  pitted  anode  rod  indicates  high 

water conductivity and should be checked and/or replaced more 

often than  an anode rod that appears to be intact. Replacement 

of a depleted anode rod can extend the life of your water heater. 

Inspection should be conducted by a qualified service agency, and 

at a minimum should be checked annually after the warranty period.
Artificially  softened  water  is  exceedingly  corrosive  because  the 

process substitutes sodium ions for magnesium and calcium ions.
The use of a water softener may decrease the life of the water 

heater tank.

The  anode  rod  should  be  inspected  after  a  maximum  of  three 

years and annually thereafter until the condition of the anode rod 

dictates its replacement. 

NOTE: 

Artificially  softened  water  requires  the  anode  rod  to  be 

inspected annually.

TEMPERATURE-PRESSURE RELIEF VALVE TEST

Burn hazard.

Hot water discharge.

Keep clear of Temperature-

Pressure Relief Valve

discharge outlet.

Содержание JW375T75N-AV

Страница 1: ...ructions and safety messages could result in death or serious injury This manual must remain with the water heater 599 Hill Street West Fergus ON Canada N1M 2X1 Low Lead Content WARNING If the informa...

Страница 2: ...Heater 12 Air Requirements 12 Unconfined Space 13 Confined Space 13 Fresh Air Openings for Confined Spaces 13 Outdoor Air Through Two Openings 13 Outdoor Air Through One Opening 13 Outdoor Air Throug...

Страница 3: ...ifornia to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical known to the State of Califor...

Страница 4: ...4 GENERAL SAFETY INFORMATION...

Страница 5: ...nd then the entire manual carefully If you don t follow the safety rules the water heater will not operate properly It could cause DEATH SERIOUS BODILY INJURY AND OR PROPERTY DAMAGE This manual contai...

Страница 6: ...1 1 4 3 2 1 NPT 1 2 NPT 11 15 16 30 3 RECOVERY RATINGS Models Input Approx Gal Cap Approx Liter Cap Temp Rise C 17 22 28 33 39 44 50 56 61 67 72 78 Rating Btu Hr Rating kW F 30 40 50 60 70 80 90 100 1...

Страница 7: ...cing and proper operation of the water heater Installation of water heater must be accomplished in such a manner that if the tank or any connections should leak flow will not cause damage to the struc...

Страница 8: ...sult in improper and inefficient operation of the water heater producing carbon monoxide gas in excess of the safe limits This could result in serious injury or death Contact your local gas supplier f...

Страница 9: ...ertain it does not sag thereby obstructing the combustion air flow HARD WATER Where hard water conditions exist water softening or the threshold type of water treatment is recommended This will protec...

Страница 10: ...to manufacturer s specifications If a positive lock up regulator is required follow these instructions 1 Positive lock up gas pressure regulators must be rated at or above the input Btu hr rating of...

Страница 11: ...y sized thermal expansion tank must be installed on all closed systems to control the harmful effects of thermal expansion Contact a local plumbing service technician to have a thermal expansion tank...

Страница 12: ...ature Pressure Relief Valve discharge line and 2 the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot If after manually operating th...

Страница 13: ...eater and the risk of fire or explosion may result It can also create a risk of asphyxiation LOUVERS AND GRILLES Thefreeareasofthefreshairopeningsintheinstructionsthatfollowdonot takeintoaccountthepre...

Страница 14: ...e provided with two permanent vertical ducts one commencing within 12 inches 300 mm of the top and one commencing within 12 inches 300 mm of the bottom of the enclosure The vertical ducts shall commun...

Страница 15: ...ter heater unless it is vented to the outdoors and has adequate air supply to avoid risks of improper operation explosion or asphyxiation For proper draft hood attachment the draft hood legs may be an...

Страница 16: ...IN INCHES MAXIMUM CAPACITY OF PIPE IN CUBIC FEET PER HOUR LENGTH IN FEET NOMINAL IRON PIPE SIZES INCHES INPUT IN THOUSANDS BTU HR 1 2 3 4 1 1 1 4 1 1 2 2 2 1 2 3 4 10 175 360 680 1400 2100 3960 6300 1...

Страница 17: ...allation shown in the Figures 15 and 16 Contaminants in the gas lines may cause improper operation of the gas control valve that may result in fire or explosion Before attaching the gas line be sure t...

Страница 18: ...18...

Страница 19: ...ian or gas supplier If the pilot will not stay lit after several tries turn the gas control knob to OFF Figure A and call your service technician or gas supplier 9 Replace inner and outer burner doors...

Страница 20: ...g valves are available at plumbing supply or hardware stores see Figure 2 Follow manufacturer s instructions for installation of the valves Before changing the factory setting on the thermostat read t...

Страница 21: ...s of combustion and water vapor SMOKE ODOR It is not uncommon to experience a small amount of smoke and odor during the initial start up This is due to burning off of oil from metal parts and will dis...

Страница 22: ...f the flue and vent system may occur if air for combustion contains certain chemical vapors Spray can propellants cleaning solvents refrigerator and air conditioner refrigerants swimming pool chemical...

Страница 23: ...sult in overheating and excessive tank pressure Can cause serious injury or death HOUSEKEEPING Fire and Explosion Hazard Do not obstruct combustion air openings at the bottom of the water heater Do no...

Страница 24: ...RAGE TANK 1 Turn off the electrical supply to the water heater 2 Ensure the cold water inlet valve is open 3 Open a nearby hot water faucet and let the water run until the water is no longer hot Then...

Страница 25: ...ch can condense on the cooler surfaces of the tank Droplets form and drip onto the burner or run on the floor This is common at the time of start up after installation and when incoming water is cold...

Страница 26: ...mbly and or thermocouple Defective Gas Control Replace Gas Control PILOT OUTAGE Dirty pilot burner Clean pilot assembly Thermocouple malfunction Replace pilot assembly and or thermocouple Defective Ga...

Страница 27: ...s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control SINGLE FLUE 1 UNIT LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSU...

Страница 28: ...mostat should be set 5 degrees F higher than the Tank Temperature Control SINGLE FLUE 1 UNIT WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP...

Страница 29: ...ermostat should be set 5 degrees F higher than the Tank Temperature Control SINGLE FLUE 1 UNIT WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING P...

Страница 30: ...set 5 degrees F higher than the Tank Temperature Control SINGLE FLUE 1 UNIT WITH MIXING VALVE TWO TEMPERATURE LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPE...

Страница 31: ...ating thermostat should be set 5 degrees F higher than the Tank Temperature Control SINGLE FLUE 2 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE...

Страница 32: ...er than the Tank Temperature Control SINGLE FLUE 2 UNITS TWO TEMPERATURE ONE PRE HEATER ONE BOOSTER HEATER LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERAT...

Страница 33: ...33 NOTES...

Страница 34: ...34 NOTES...

Страница 35: ...d by improper gas supply line sizing gas type venting connections combustion air voltage wiring or fusing Failure to follow applicable codes Failure to follow printed instructions Abuse misuse acciden...

Страница 36: ...rights reserved 599 Hill Street West Fergus ON Canada N1M 2X1 Should you have any questions please Email us at techsupport gsw wh com or Visit our website www johnwoodwaterheaters com or Call our Tech...

Отзывы: