background image

 

– 4 – 

PART NO. 100266523 

 CIRCULATOR  PUMP

A circulator pump is not supplied. Use only a bronze body 
model rated for 110/120 volts, 60Hz. Install in accordance 
with the pump manufacturer’s instructions using standard 
plumbing practices. Size the circulator pump taking into 
account the pressure loss through the tankless coil boiler or 
instantaneous water heater as well as pressure losses through 
the connecting pipes that are part of the circulating loop.

 SIZING THE HOT WATER SYSTEM

Temperature of the system is controlled by the temperature 
set point of the instantaneous water heater or boiler coil.
Given the limited storage capacity of the storage tank and the 
maximum output of the tankless coil boiler or instantaneous 
water heater, large hot water draws signi

fi

 cantly exceeding 

the circulating loop 

fl

 ow rate may lead to a reduction in 

temperature of hot water delivered.

 PLUMBING  CONNECTIONS

The water heating source piping and components 

connected to the tank must be suitable for potable water 

use. TOXIC chemicals such as used for boiler treatment 

must not be introduced into the tank.

Toxic Chemical Hazard

WARNING

For a temperature controlled instantaneous water heater it is 
recommended to install the plumbing as shown in Figure 2. 
It is also recommended to set-up and control the IWH outlet 
temperature to be at least 11°C (20°F) above tank thermostat 
temperature. The recommended plumbing installation for a 
tankless coil boiler is shown in Figure 3. In this case, because 
the tankless coil boiler is able to control only the differential 
between inlet and outlet temperature, the cold water entering 
the tankless coil boiler must be tempered with hot water from 
the storage tank. As there is a large variety of heat sources 
and control systems, please contact your local distributor for 
the plumbing system to identify the solution that best suits 
your application.

Do not apply heat directly to tank fittings when making 

sweat connections. They contain non-metallic material.

Property Damage Hazard

CAUTION

FROM IWH

TO IWH & 

CIRCULATOR 

PUMP

T&P VALVE

HOT 

WATER 

PIPE INSULATION

COLD IN

THERMOSTAT 

WITH HIGH-

LIMIT SWITCH

DRAIN VALVE

FLOOR DRAIN

DRAIN PAN

PRESENT ON 

SOME MODELS 

ONLY (NOT USED)

Figure 1.   Main Parts and Features for Connection to a 

Temperature Controlled IWH

1.  Ensure the storage tank is level before starting installation.
2.  Install a circulation loop as shown using 19mm (3/4 in.) 

copper piping.

3.  If the heating source is a tankless coil boiler go to Step 4. 

If a temperature controlled IWH is used as a heat source, 
install the combination inlet/drain valve in one “arm” of a 
tee connected to the lower storage tank fitting. Connect 
the cold water supply piping to the inlet of the combination 
inlet/drain valve. Connect the other “arm” of this tee to 
the IWH inlet line and place the circulating pump in this 
line. Connect the IWH outlet to the upper storage tank 
side fitting (see Figure 2). Proceed to Step 5.

4.  

For a tankless coil boiler install the combination inlet/drain 
valve in the lower storage tank fitting. Connect the inlet 
of a combination inlet/drain valve to the hot outlet of the 
tankless coil boiler. In this instance the “leg” of a tee should 
connect to the cold water supply line, one “arm” connects 
to the circulator pump and the other “arm” to the inlet of 
the tankless coil boiler. The circulator pump connects to 
the upper side fitting of storage tank (see Figure 3).

Содержание FlowThru GST

Страница 1: ...ouch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas sup plier s instructions If you cannot reach your gas supplie...

Страница 2: ...irculator Pump 4 Sizing The Hot Water System 4 Plumbing Connections 4 Electrical Wiring 6 Filling 6 OPERATION 6 Temperature Adjustment 6 Initial Temperature Adjustment 7 Temperature Limit Control 7 MA...

Страница 3: ...rom the valve will exit within 152mm 6 in above or any distance below the structural floor and cannot contact any live electrical part The end of the relief pipe opening should terminate near the floo...

Страница 4: ...ater entering the tankless coil boiler must be tempered with hot water from the storage tank As there is a large variety of heat sources and control systems please contact your local distributor for t...

Страница 5: ...al Set the mixing valve outlet temperature to 49 C 120 F to avoid scalding 7 Acheck valve may be installed in the cold water line before the connecting tee Note The check valve can often be noisy and...

Страница 6: ...suitable drain Open the drain valve and let water run to flush out any foreign matter that may have entered the system Once flushed close the drain valve and disconnect hose OPERATION 1 Follow boiler...

Страница 7: ...etely reset and continues to release water immediately turn OFF the electrical supply to the tank close the cold water supply valve and call a qualified service technician TEMPERATURE AND PRESSURE REL...

Страница 8: ...e generally two weeks or more Hydrogen gas is extremely flammable and explosive To prevent the possibility of injury under these conditions we recommend the hot water faucet located farthest away be o...

Страница 9: ...y period shown in the table above after the original installation the Manufacturer will furnish the Owner with a replacement for the defective part s This Warranty is limited to one replace ment compo...

Страница 10: ...tingency beyond the control of the Manufacturer or s The water heater is installed in a closed system without adequate provision for thermal expansion 3 Except when specifically prohibited by the appl...

Отзывы: