5 Adjusting the Switching Unit
Flow switch
5 Adjusting the Switching Unit
5.1 Contact type
5.1.1 Standard contact
The switching unit of the control switch enables 2 contact types:
1. Make contact (normally open):
“RED” arrow on the switching unit
2. Break contact (normally closed):
“WHITE” or “BLUE” arrow on the switching unit
The following table explains the two contact types:
Contact type
Setting
Flow rate:
Electric contact
increasing
closing
Make contact
RED arrow
decreasing
opening
increasing
opening
Break contact
WHITE or BLUE arrow
decreasing
closing
If not otherwise agreed with the customer, the switching unit is factory set as a make contact, i.e. the reed
contact opens if the set switching point is exceeded.
5.1.2 Change-over contact (only for VH3...)
For flow switches with a change-over contact a fine adjustment can only be carried out within the red arrow.
The contact switches after reaching the set switching point.
5.2 Flow switch version VH...X
The flow switch version VH...X is supplied ex works with a fixed switching point. Adjustment of the switching
point for flow switch version VH...X is not permitted.