The basis of the MTP-V heater is always the BK heat exchanger selected according to
the required output; the required output is then the nominal output of the heater. The heat
exchanger table is below. The heat exchanger may be extended or shortened according to
the spatial disposition. Depending on customer requirements or specific needs, the heat
exchangers are made of steel of class 11 and stainless-steel materials.
Each heater has a nominal amount of air determined. With less air, the heater
cannot be operated for the required output.
The optimal air dT passing through the heat exchanger is c. 30 °C, so as to avoi
d
unwanted excessive condensation, so that the flue gas temperature is relatively low, and
the resistance of the heat exchanger on the side of the air is not too high. Basically, the
bypass is designed to keep “excess” heated air in the heater out of the h
eat exchanger.
The specific technical parameters of the supplied heater are always included in this
documentation in the “Certificate of product quality and completeness” and on the
nameplate.
Table of MTP-V technical parameters
BK
maximum heat
output
standard
design
minimum air
flow standard
design
kW
m
3
/h
P1
45
2400
P2
60
3300
37
50
2700
65
85
4600
100
130
7100
150
180
9800
225
300
16300
400
500
27100
525
650
35300
650
790
42900
1000
1100
59700
4.
MTP Specifications:
MTP heaters are always supplied as a composition of a heat exchanger unit and
radial fan. The heat exchanger unit is not fitted with a bypass. The frame consists of welded
steel profiles, usually in a compact monoblock design.
MTP air heaters are delivered in an upright or horizontal design. Both versions can be
equipped with a wide range of accessories such as e.g. blind shutters, filters, elastic
connections, etc. that do not affect the function of the gas heater.
The heaters are supplied with fans and engines as required by customers with the
required disposition pressure for connection to air-conditioning piping.