MAINTENANCE INSTRUCTIONS
The maintenance of the heater is always carried out while it is out of service.
Maintenance service must be in accordance with the operating instructions.
The following activities are performed during maintenance:
a) To ensure at least once a year, in accordance with the valid Decree 85/1975 Coll.,
checking and adjusting of the burner by an authorized mechanic (preferably before
the start of the heating season). The operation of the heater is required for adjusting
the burner.
Inspections and revisions of gas equipment
Gas
Gas
Service
control
control
inspection
When:
1 year
3 years
1 year
Who:
operator
inspecting
service
technician technician
What is done:
Check of the location, functionality and tightness of the main
valve
X
X
Check of the location, functionality and tightness of branch
closures of ascending lines
X
X
Check of the location, functionality and tightness of gas meters
X
X
Check of the location, functionality and tightness of regulators
X
X
Check of the location, functionality and tightness of gas
appliances.
X
X
Check of the location of appliances in terms of space ventilation
X
Visual check of the location and condition of the common space
gas pipeline
X
X
Overall visual check of the location and condition of the domestic
gas pipeline
X
Check of the tightness of all detachable joints
X
X
Check of the presence of CO (carbon monoxide)
X
Cleaning, adjustment and check of gas appliance
X
b) Tightening the bolts of the burner plate and the tube plate cover, check after the
first month of operation, then regularly before the start of the heating season.
c) Cleaning the tube plate and the condensate drainage at least once a year (as
needed). For LFO (light fuel oils) and diesel burners, cleaning of the tube plate
must be carried out regularly whenever the heating efficiency decreases (even
once a month, if needed). After cleaning, the bolts at the tube plate must always be
tightened properly, or, if necessary, the seal should be replaced (check tightening of
the bolts repeatedly after a month of operation!)
If the heater contains the following, we also check: