Jetter AG
Programming | 7
JX3-BN-EC User Manual
32 / 92
For each connected JX3 I/O module, the following entries are added with an off-
set of 0x10:
Index
Description/
Name
Type of access
0x1600 RxPDO Map Module
RO
0x1A00 TxPDO Map Module
RO
0x6000 Inputs Module
RO
0x7000 Outputs Module
RW
0x8000 Parameter Module
RW
0xA000 Status Module
RO
Example
The following JX3 I/O modules are connected to a JX3-BN-EC:
Position
Module
Offset
1
JX3-BN-EC
2
JX3-DIO16
0x00
3
JX3-AI4
0x10
4
JX3-MIX1
0x20
5
JX3-DIO16
0x30
The distance between the modules is always 0x10. If a JX3 I/O module does not
support a function (the JX3-AI4 module has no outputs), this index (here 0x7010)
is skipped.
Index
Description/
Name
0x60
00
Inputs Module: JX3-DIO16
0x60
10
Inputs Module: JX3-AI4
0x60
20
Inputs Module: JX3-MIX1
0x60
30
Inputs Module: JX3-DIO16
0x70
00
Outputs Module: JX3-DIO16
0x70
20
Outputs Module: JX3-MIX1
0x70
30
Outputs Module: JX3-DIO16