Jetter AG
Technical specifications | 4
JX3-BN-EC User Manual
14 / 92
4.5.2 DC power supply inputs and outputs
Emitted interfer-
ence
Parameter
Values
Standards
Signal and control line connections, DC voltage supply inputs and - out-
puts
Frequency band
0.15 … 0.5 MHz
DIN EN 61000-6-3
Limit value
40 to 30 dB
Frequency band
0.5 … 30 MHz
Limit value
30 dB
Class B
Tab. 8:
Emitted interference of the DC mains inputs and mains outputs
Immunity to inter-
ference
Parameter
Values
Standards
RF field, asymmetric, amplitude modulated
Frequency band
0.15 … 80 MHz
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-6
Test voltage
3 V
AM 80 % with 1 kHz
Source impedance
150 Ω
Criterion A
Bursts
Test voltage
2 kV
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-4
tr/tn 5/50 ns
Repetition frequency
5 kHz
Criterion A
Surge voltages, symmetric, line to cable
Series-mode interference tr/th 1.2/50 µs
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-5
0.5 kV
Surge voltages, asymmetric, line to earth
Common-mode interfer-
ence
tr/th 1.2/50 µs
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-5
1 kV
Tab. 9:
Interference immunity of the DC mains inputs and outputs