Jetter AG
Programming | 7
JVM-104-O09 User Manual
33 / 62
7.6.1 Status and instructions
R 6010x0000
Status register MFQEx
R 6010x0000 shows the status of the multi-purpose input MFQEx.
Property
Description
Type
Status register
Type of access
Read
Reset
Command: Activate multi-purpose input x
Meaning of the individual bits
Bit 0
Overcurrent
1 =
In current measurement mode triggered by a
current > 2500 mA.
Bit 7
Overtemperature
1 =
Overtemperature is present
Bit 14
Multi-purpose input MFQEx is ...
0 =
enabled
1 =
disabled
Tab. 34:
Status register of the multi-purpose input MFQEx
R 6010x0001
Command register MFQEx
The command register lets you set various operating modes and configure the in-
put MFQEx.
Property
Description
Type
Command register
Meaning of the individual bits
Bit 7 … 4
0000 =
Frequency measurement using gate time
0011 =
Counting mode
0100 =
Period time measuring, 10 s timeout
0101 =
Period time measuring, 1 s timeout
0110 =
Period time measuring, 100 ms timeout
Bit 9
0 =
Voltage measuring
1 =
Current measurement
Bit 12
0 =
Activate pull-up resistor
1 =
Deactivate pull-up resistor
Tab. 35:
Command register for multi-purpose input MFQEx, bit-coded