On exiting the Booth, the light & extractor should overrun for 1 minute. Once the light & extractor have switched off,
and a further minute has passed, the extractor will self-agitate to clean the large cannister filter. The agitate sequence
should also last 1 minute.
In the UK this product should be LEV tested & commissioned. The test required is based
on exceeding airflow speeds suggested in HSG258 - a smoke test is not required. Duct
velocities should be checked at; 1) The booth roof 2) The inlet of the duct to the extractor
& 3) The inlet to the extractor. Indicative velocities at these points would be determined
at the commissioning stage to the site conditions. If you have any questions or concerns,
please contact your distributor for more details.