background image

Component Testing

To avoid risk electrical shock, personal injury, or death,

always disconnect electrical power source to the freezer

before attempting to service, unless test procedures require

power to be connected. When removing any wiring from terminals they must be replaced on the same terminals.

Ensure all ground wires are connected before certifying unit as repaired and/or operational.

WARNING

!

©2003 Maytag Appliances Company

16022217   Rev. 0

9

 Refrigeration System Test Procedures

The following should always be practiced with any sealed

system that is opened. Only open the sealed system as

the final diagnosis. Check all basic areas such as wiring,

water supply, drain setup, proper airflow first. Many times

these areas can resemble sealed system problems. The

diagnosis of a sealed system problem can be determined

by accurate pressure and temperature measurements.

1. Use a leak detection system that will detect R-134A

refrigerant. Leaks need to be found on any leaking

system 

before

 repair takes place.

2. The drier must be replaced anytime the sealed

system is opened.  Failure to use correct part will

result in repeated sealed system failure in the near

future.

3. Limit time the system is opened. 

DO NOT EXPOSE

OPEN SYSTEM FOR MORE THAN 15 MINUTES.

This will result in sealed system failure. Leave

replacement parts sealed and/or pressurized until

ready to install.

4. The compressor must be replaced if there is a low

side leak. Moisture has been drawn into the system if

the unit has been running for extended period of time.

Be sure to flush the system with dry nitrogen gas and

evacuate to 50 microns before re-charging.

5. A new evaporator assembly must be ordered  if the

capillary tube is found to be plugged or severely

restricted. Restrictions cannot be flushed out.

6. Be sure to purge the system after final brazing. This

will flush out any air or moisture that may have

entered the system before being absorbed into the

ester oil.

Low Side Leaks

Low side leaks consist of a break in the system at the

evaporator, low side (suction) return line, or accumulator.

If a leak is found in any of these areas, moisture has

probably entered the system. The compressor, drier, and

hot gas valve will have to be replaced and the system will

need to be flushed thoroughly with nitrogen gas and

evacuated to 50 microns before recharging.

High Side Leaks

High side leaks consist of a break in the system at the

condenser, high side tubing, drier, or capillary tube. If a

leak is found in any of these areas, the system can be

flushed with nitrogen gas, evacuated to 50 microns, and

recharged.

Restricted Capillary Tube

Moisture or other contaminants that enter the system can

cause deposits in the system. These deposits will usually

collect in the capillary tube and form a restriction that

cannot be completely removed by flushing. If the

capillary tube is found to be restricted, the evaporator,

compressor, condenser and drier should all be replaced.

Access Valves

A temporary access valve can be used to service or

evaluate the system. The access valve can be installed

on the compressor’s process tube (this will also be a low-

pressure side). Be sure to cap off access valve while

servicing. This will prevent contamination of the system

and/or refrigerant from leaking. 

After servicing, the

access valve should be removed

.  A pinch-off tool can

be used to close the system to remove the access valve

and then braze the hole for the access valve to seal the

system. Be sure to leak check after brazing.

Pressures and Temperatures

There are three ways to measure the temperature of the

evaporator plate.

1. Use a thermocouple to measure the temperature of

the evaporator. The thermocouple must be secured

to the evaporator. The best and accurate location for

the thermocouple end is where the thermistor is

secured to the evaporator. Allow anywhere from 5°-

8°F of variation in measured temperatures if you

measure on the plate because of the thermal

conductivity of stainless steel thermistor in

comparison to the thermocouple.

2. If it has been determined that there is proper contact

between the thermistor and the evaporator plate, the

thermistor resistance value can be corresponded to

the temperature .

Содержание JIM1550ARB

Страница 1: ...manual includes but is not limited to the following Jenn Air JIM1550ARB JIM1550ARW JIM1550ARS JIM1550ACX Service This manual is to be used by qualified appliance technicians only Maytag does not assu...

Страница 2: ...ING REPAIRS WARNING To avoid risk of severe personal injury or death disconnect power before working servicing on appliance to avoid electrical shock To locate an authorized servicer please consult yo...

Страница 3: ...tter Transformer 13 Grid Cutter 13 Reservoir 13 Circulation Pump 13 Troubleshooting 14 17 Disassembly Procedures Hot Gas Valve Removal 18 Hot Gas Valve Installation 18 Replacing the Evaporator 18 Comp...

Страница 4: ...identifications of individual units state complete serial number model and type This information is found on the serial plate located on front upper right hand corner of foodliner or on some models e...

Страница 5: ...loaded weight of the unit Refer toAppendix A owner s guide for additional information Electrical Requirements 115 VAC 60 Hz single phase power is needed Use outlet with a 15 amp delayed action fuse or...

Страница 6: ...ble tubing or poor ice production will result If installing a standoff gravity drain use Illustration below for location Standpipe can be up to 3 inches high above the floor Route tubing from ice make...

Страница 7: ...d for the first 35 minutes into the production cycle If during any production cycle or harvest cycle the selector switch is put into the CLEAN position any cycle in process will be immediately termina...

Страница 8: ...ch is moved from the CLEAN position all loads except the drain solenoid will de energize this includes the OFF position The drain solenoid will energize for 75 seconds and then de energize The unit wi...

Страница 9: ...in the system at the evaporator low side suction return line or accumulator If a leak is found in any of these areas moisture has probably entered the system The compressor drier and hot gas valve wil...

Страница 10: ...m with dry nitrogen gas and evacuate to 50 microns before re charging The method for recharging the unit is by weight using vapor refrigerant Using manifold gauge setup hook up charge hoses to the acc...

Страница 11: ...essor The compressor is the heart of the refrigeration system It also however relies on other parts of the system to function Make certain that the other parts of the system are correctly functioning...

Страница 12: ...e flow rate of the reservoir water line Using a stopwatch or a watch with a second hand see what amount of time it takes to fill up a one quart container The time should be 60 seconds to get the 25 gp...

Страница 13: ...d side of the transformer and reading the 12V side using a multimeter If no readout is found or readout is below 10VAC replace the transformer Grid Cutter The grid cutter is used to cut cubes from the...

Страница 14: ...for proper operation Distributor tube is restricted or not installed correctly See CLEANING YOUR ICE MACHINE section for cleaning the unit for proper operation Grid cutter is unplugged Plug in the gr...

Страница 15: ...o kinks or restrictions in the drain lines If using a drain pump check the inlet screen discharge line and vent line for any build or restrictions Leaking drain valve See CLEANING YOUR ICE MACHINE sec...

Страница 16: ...t for proper operation Build up of deposits on evaporator plate See CLEANING YOUR ICE MACHINE section for cleaning the unit for proper operation Inadequate drain system Restriction in drain lines will...

Страница 17: ...o side and front to rear Room temperature is too cold Move the unit to an area where temperature is above 55 deg F The selector switch is not in the ON position Set the rocker switch on the grille of...

Страница 18: ...itrogen gas and a leak detection system 9 Flush the system and recharge 10 Reassemble reversing steps 1 through 10 Replacing the Evaporator 1 Disconnect power water line and drain line If a drain pump...

Страница 19: ...ll need to disconnect the three wires from the old PTC starter and then connect the new one 12 Un braze and remove the capillary tube from the drier assembly 13 Un braze the tube from the hot gas valv...

Страница 20: ...r to the reservoir and observing for any leaks from the tubing connections or the valve itself Water Valve Removal 1 Disconnect power water line and drain line 2 Remove the access panel and rear panel...

Страница 21: ...the hot gas valve solenoid coil by removing the spring retainer rotating the coil 90 degrees and then lifting up 7 Take out the two screws that secure the top of the electrical bracket located in the...

Страница 22: ...1 Disconnect power to the icemaker 2 From inside the unit remove the escutcheon panel 3 Remove the grid cutter 4 Remove the ice deflector 5 Remove the reservoir 6 Unplug the circulation pump at the re...

Страница 23: ...23 BLACK RIBBED NEUTRAL OV LD COMPRESSOR GRID CUTTER TRANSFORMER THERMISTOR THERMISTOR EVAPORATOR THERMISTOR THERMISTOR SOLENOID BIN CLEAN GRID SOLENOID SOLENOID DRAIN WATER HOT GAS CUTTER FAN CONDEN...

Страница 24: ...2003 Maytag Appliances Company 16022217 Rev 0 A 1 Appendix A...

Страница 25: ...Introduction 2 Safety 3 Installation 4 9 Operation 10 Care and Cleaning 11 12 Before Calling for Service 13 18 Warranty 20 Guide du Propri taire 21 Gu a del Propietario 41 OWNER S GUIDE 41007621 4100...

Страница 26: ...need future assistance with your ice maker a complete model and serial number recorded in the spaces below will be extremely helpful These numbers are found on the data plate inside on the lower front...

Страница 27: ...apors and liquids Children should not climb hang or stand on or in this refrigeration product Read and follow manufacturer s warnings on ice machine cleaner products Personal injury can result when us...

Страница 28: ...rs Ideal Ambient Temperature Range Built In 55 80 F NOTE Ice maker will not perform correctly in ambient temperatures less than 55 F Cabinet Clearance The ice maker may be enclosed on the sides rear a...

Страница 29: ...nstallation WARNING The ice maker should remain upright at least 30 minutes prior to plugging it in CAUTION Level the Ice Maker Using a carpenter s level check to be sure the ice maker is level from s...

Страница 30: ...drain is not accessible NOTE Avoid kinks and check for proper water drainage after ice maker installation OBSERVE AND FOLLOW ALL LOCAL CODES WHEN INSTALLING ICE MAKER Failure to use adequate drainage...

Страница 31: ...a shut off valve between the ice maker and the water supply The shut off should be a drilled saddle valve Do not use a self tapping valve The valve should be installed in a vertical water pipe NOTE If...

Страница 32: ...ness maximum 1 Turn off the ice maker and disconnect the power 2 Remove 1 8 set screw A from the top hinge Remove the door off of the lower hinge noting washer location 3 Remove the door seal B to exp...

Страница 33: ...m wood panel and tighten 6 Reinstall the door seal by pressing it into the door channel Making certain the corners are fully inserted 7 Install the door back on to the ice maker using the supplied pla...

Страница 34: ...electronic control switches to the harvest cycle to harvest the ice slab During the harvest cycle the ice slab falls from the evaporator to the ice grid cutter Here the ice slab is cut into 3 4 square...

Страница 35: ...r panel and close door 7 Switch selector switch on the grill of the machine to the CLEAN position Three quarts of water will automatically be added to ice maker cleaner 8 The total cleaning time will...

Страница 36: ...eansers bleach or cleaners containing bleach These products can scratch and erode the paint finish DO NOT wax plastic or vinyl parts Use a soft cloth or sponge Always wipe with the grain of the stainl...

Страница 37: ...proper ice quality production and unit life 6 If ice maker is to be left unattended for a month or longer turn off its water supply switch the control to OFF and disconnect the power supply Remove an...

Страница 38: ...cycle can take up to 11 2 hours Initial startup cycles can be longer The selector switch is in the OFF or CLEAN position No water in the reservoir Distributor tube is restricted Build up of deposits o...

Страница 39: ...discharge line and vent line for any buildup or restrictions Remove the front cover panel and plug the grid cutter into the receptacle on the side of the liner Ice is slowly melting on the ice bin an...

Страница 40: ...nit to make sure there are no restrictions or kinks in the line Check all filters to make sure they are not restricted or plugged Make sure that the reservoir drain plug is installed properly Check th...

Страница 41: ...and front to rear Set the rocker switch on the grille of the ice machine to the ON position Remove the front cover panel and plug the grid cutter into the receptacle on the side of the liner It can ta...

Страница 42: ...nks or restrictions in the drain lines If necessary consult a qualified plumber Foreign material is restricting or blocking the ice bin drain located at the right rear corner of the ice bin The drain...

Страница 43: ...19 Notes 41007621 JA Ice Maker ENG 4 28 03 2 18 PM Page 19...

Страница 44: ...vicer 6 Consequential or incidental damages sustained by any person as a result of any breach of these warranties Some states do not allow the exclusion or limitation of consequential or incidental da...

Отзывы: