Time programming
The door must be completely closed before starting time programming.
Press the PANEL PROG button for 1 second to enter programming. The red PRG pilot light will come on and the equipment will
emit an acoustic signal.
Use the START or TEST button to programme the run.
When START/TEST is pressed for the first time, the door will act as follows: Opens slightly, closes to the lower stop, opens to
the upper stop and stops moving. When START/TEST is pressed for the second time, the panel memorizes the automatic
standby time, closes to the lower stop, stops and exits the programming mode (the red pilot light goes out). The opening and
closing time will now have been programmed.
Option switch
ON position
OFF position (default position)
1- DM OP
Dead-man operation: The START button serves as
the Open button
Semi-automatic operation
2- DM CL
Dead-man operation: The TEST button on the board
serves as the Close button
Semi-automatic operation
3- AUTO-TEST OP
This carries out the auto-test for the security open
contact
No auto-test carried out
4- AUTO-TEST CL
This carries out the autot-est for the security open
contact
No auto-test carried out
5- OPEN-STOP-
OPEN
The panel always opens until the end of the opening
time
Alternative operation: open-
stop-close-stop
6- AUTO-CLOSE
Automatic closure
Does not close automatically
7- FLASH
Courtesy light acts as the signal with a 1.5 sec. pre-
warning during door movement
Courtesy light acts as the gar-
age light for 60 sec. after door
movement
Input switch
Option No.
Lower position – OFF
Upper position – ON (default option)
1- SEC.CL
Security Close contact connected
Security Close contact not connected
2- SEC.OP
Security Open contact connected
Security Open contact not connected
3 STOP
Stop button connected
Stop button not connected
Light indicators
POWER
Indicates power
PROG
Indicates programming
SAFETY FiXED
Indicates failure of safety or Radioband element autotest
SAFETY BLINKING
Indicates security edge inhibiting
Lock and end of run detection
The panel includes a function that automatically detects the end of the run or detects when the motor is mechanically blocked,
stopping movement in both cases.
In programming mode, this circuit saves on users having to press START/TEST.
In operating mode, the panel protects the motor in the event of becoming blocked.
The function does not replace sensitive edge protection.