Page 8: ON INPUT #8 function.
Selects immediate action when the photoisolated input # 8 is activated.
Line 1: Display only.
Line 2: Select programmer action.
DO NOTHING, RUN PROG # STEP # or
DISABLE CONTROLLER
Input 8 is ignored.
Page 8A
Line 1: Display only.
Line 2: RUN PROGRAM selected.
Line 3: Select Prog # and Step # to run.
Line 4: Blank
Program 98 step 1 is immediately executed upon a low input signal to Input 8.
Page 8B
Line 1: Display only.
Line 2: DISABELE CONTROLLER selected.
Line 3: Blank
Line 4: Blank
When the signal to input 8 goes low. CH1 and CH2 controller outputs are “killed” (disabled) and the
program step timer holds.
When the input signal to input 8 is removed the controller outputs and step timer are re-activated.