SERVICE MANUAL
– HEAT PUMP
5.3. Compressor
Request
: compressor power demand in percent (%)
below which oil recovery mode can be activated
Speed
: compressor speed below which oil recovery
mode can be activated
Delay
: time for which conditions must be met for the
procedure to start
Duration
: duration of the procedure
Force
: compressor speed during the procedure
On cycles
: compressor run counter
Hours
: compressor run time since last application
reset
Next thr
: Time after which the component should be
replaced/maintained
Reset h.
: switch to reset the counter
Status
: the current control value set for the compres-
sor expressed as a percentage
Manual
: option to manually task the compressor with
a fixed speed value expressed in percentage
Startup
: compressor speed during the first three
minutes after startup
Max
: overall maximum permissible compressor
speed
Min
: minimum permissible compressor speed
Actual max rps
: maximum permissible compressor
speed for the current ambient temperature
Max rps level reg
: Option to enable the compressor
speed control curve in CH mode. Five points are set,
where X corresponds to the ambient temperature
and Y to the maximum compressor speed at that
temperature. The remaining points are calculated by
interpolation. The Y value does not change below the
first point and above the last point.
Max rps level reg
: Option to enable the compressor
speed control curve in DHW mode. Five points are
set, where X corresponds to the ambient tempera-
ture and Y to the maximum compressor speed at this
temperature. The remaining points are calculated by
interpolation. The Y value does not change below the
first point and above the last point.