16
© JBG-HT (v.2.0)
SERVICE MANUAL
– HEAT PUMP
Set.compens.HP
: selecting the option allows the
heating curve to be started in CH mode.
HP set compens.
: four points are set, where X cor-
responds to the ambient temperature and Y to the
water temperature setpoint. The remaining points
are calculated by interpolation. The Y value does not
change below the first point and above the last point.
The Y4 value is equal to the SetPoint set in the main
screen.
User Pump 1 defrost req
: preset constant flow rate
during defrost expressed in percentage.
User circuit mode
: selection of use of Y1 and Y3
outputs
•
3WV2+3WV3
– two outputs for three-way
mixer valves controlled by 0-10V signal
•
Pmp2+3WV2
– Y1 output controlled by 0-10V
signal, supporting mixer valve; Y3 output con-
trolled by PWM signal, supporting circulating
pump
Manual Mode
: choice between automatic control
and manual setting of the mixer valve
Valve level/Manual set
: in the case of automatic
mode, displays the current position of the valve, in
the case of manual setting - a field for entering the
set opening value
Circ. Temp
: temperature measurement of the second
heating circuit
Set point
: Set temperature value of the second
heating circuit
Kp
: regulator gain
Ti
: integration constant of the regulator
Td
: differentiation constant of the regulator
Compens.
: four points are set, where X corresponds
to the ambient temperature and Y to the setpoint of
the feed water temperature of the second heating
circuit. The remaining points are calculated by inter-
polation. The Y value does not change below the first
point and above the last point.