Gb
Fr
324501E
revision02
- 57 -
De
Contactor
Physical unit switched by relay
Number of switching cycles for "on"
relay and function "relays"
Switching at 230VAC (70VA,cosphi=0,75)
2 x 10
6
Switching at 110VAC, (70VA,cosphi=0,75)
1 x 10
6
Switching at 48VAC (70VA,cosphi=0,75)
0,5 x 10
6
CA2DN
LC1D09
LC1D18
LC2D09
- Number of switching cycles on various contactors
4.3.2- Connection to relays
4.3.3- Relay characteristics
(«On» relay and function relays)
4.3.1- Maximum number of simultaneously controlled
relays according to industrial receiver model
)
)
)
)
)
The maximum number of relays activated at the same time is limited to :
On receivers, the connections are made on spring terminals with connection points
identified by numbers.
Flexible wires with wire section of between 0.08mm² and 2.5mm² can be used.
No common line is provided on the printed circuits (all contacts are potential-free).
-
4
for
ORRS
(industrial small model receiver) :
4 function relays actuated at the same time
or 3 function the "On" relay activated at the same time.
-
9
for
ORRA
(industrial large model receiver) :
9 function relays actuated at the same time
or 8 function the "On" relay activated at the same time.
• Contacts : AgNi 0,15
• Maximum power at cosphi=1 : 2000 VA
• Maximum current switching : 8 A
• Maximum voltage switching : 400 VAC
• Minimum current / voltage advised switching : 100 mA / 12 VDC
• 100 000 switching cycles at 250 VAC, 8 A, cosphi=1
• 50 000 switching cycles at 24 VDC, 8 A
• Tests per EN 60947-5-1 :
DC13 at 0,5 A / 24 VDC
AC15 at 3 A / 250VAC
Содержание ORION Series
Страница 2: ...2 324501E revision02...
Страница 123: ...Gb De 324501E revision02 123 Fr Annexes Appendix Anhang...
Страница 134: ...134 324501E revision02...
Страница 136: ...136 324501E revision02...
Страница 137: ...324501E revision02 137 NOTES...
Страница 138: ...138 324501E revision02 NOTES...
Страница 139: ...324501E revision02 139...