background image

 

 
 
Heating system 
 

 
The  boiler’s  standard  equipment  includes  a  4-way  mixing  valve  which  is  connected  to  the 
flange on top of the boiler. 

 

The  pipe  entering  the  radiator  network  is  connected  to  the  left  (seen  from  the  front)  and  the 
return pipe to the right side of the valve. 
 
The temperature of the outflow water that is needed in the network varies considerably. Thus 

 

Circulating water pump 

 

care of. 
 

 

The  boiler  should  be  connected  to  an  energy  accumulator  (with  volume  250-1500  litres)  if 

coupling which ensures that the returning water temperature does not fall below 60 °C.

 

 

Electricity connection 

 

The boiler’s electricity connections must only be performed by a qualified electrician. 
 
The connections are made according to the following scheme. 

 

S2

1

c

c

N L1 1 2 3

IMIT 2

TG 1

THERMOSTAT

S1

FEED FROM BURNER SWITC
MAX.240V/10A

CUT-OFF
THERMOSTAT

BURNER

BURNER

BURNER

X1
4mm°

***6kW 30A 3x10mm°

**4kW 20A 3x6mm°

 * 2kW 10A 3x1,5mm°

11/R

S3

21/S

31/T

12/U

22/V

32/W

H

X2

N L1

6mm°

HEATING ELEMENT
(SPL 3x2kW 230V)

6mm°

THERMOSTAT

FEED 230-240V 1~ FROM MAINSWITCH OF HEATING ELEMENT

Signal lamp

CUT-OFF
THERMOSTAT

2,5mm°

10mm°

2

00

0W

2

00

0W

2

00

0W

*

*

*

 

 
 
 
 
  

 

 
 

Central heating mixing valve 

we recommend adding a motorised controller to the valve. 

The best location for the circulating water pump is the radiator network flow pipe. To ensure 
the pump’s good functioning, removal of the accumulated air from the network should be taken 

Energy accumulator (Thermal storage tank) 

firewood burning is frequent. A reliable loading valve (e.g. Termovar) should be used in the 

WWW.JASPI.UK

Содержание TRIPLEX

Страница 1: ...USER MANUAL INSTALLATION AND J A S P I K N O W S H E A T I N G Multifuel boilers JASPI TRIPLEX WWW JASPI UK...

Страница 2: ...Expansion Container Systems 3 Driving Water System 3 Heating System 4 Electricity Connections 4 BOILER INTRODUCTION 5 Burner choice 5 Burner installation 5 Burner adjustment 5 Wood side equipment inst...

Страница 3: ...one in accordance with good engineering practices In Raisio Finland 5 6 2002 Raimo Aaltonen General Manager powerful hot water coil flange chimney extension liner Recommend chimney brick 250 cm steel...

Страница 4: ...o the amount of water The safety valve is installed unclamped to the boiler s boiling aggregate The valve s exhaust pipe should not be reduced from it s nominal size and it should be directed thus tha...

Страница 5: ...electrician The connections are made according to the following scheme S2 1 c c N L1 1 2 3 IMIT 2 TG 1 THERMOSTAT S1 FEED FROM BURNER SWITC MAX 240V 10A CUT OFF THERMOSTAT BURNER BURNER BURNER X1 4mm...

Страница 6: ...sis is taken on the first time of usage and the burner is adjusted accordingly Thus unnecessary smutting is avoided if ventilation is not sufficient The final adjustment is performed when boiler water...

Страница 7: ...h nr 3 figure 3 and cleansing hatch nr 1 figure 3 are opened and the exit gas control found behind the latter hatch is removed nr 4 figure 3 The chambers are cleansed by removing and extracting the sm...

Страница 8: ...and tightly so that the billets touch the rear wall of the furnace Then put a new charge of billets onto remaining coals When coals burn down close the air dampers in order to avoid heat losses from t...

Страница 9: ...the boiler water temperature has remained unchanged for 45 minutes after the beginning of combustion Secondary air is adjusted by changing the clearance of the air damper on the maintenance hole lower...

Страница 10: ...sed temperature limiter can be retuned by pressing the temperature limiter nr 21 24 figure 1 button strongly pressing with a narrow tipped stick on the control panel WARRANTY Boiler warranty is two ye...

Отзывы: