Jason International, Inc. · 501.771.4477 Page 10 of 12 Customer Service: 800.255.5766
Copyright © 2021 Jason International, Inc.
ELECTRICAL INSTALLATION
These instructions are written assuming 60Hz, 120V
power supply. Verify the electrical requirements of the
bath unit before installation. Refer to the equipment
labels for voltage and frequency requirements.
Note:
This bath is designed for indoor use only. The
electrical equipment must not be exposed to direct or
indirect water or moisture contact. The electrical
equipment must also be protected from dust and other
airborne debris before, during and after installation.
A licensed electrician must provide the “dedicated”
electrical service protected by a GFCI. The location of
the GFCI must be at least five (5) feet [152cm] away
from the inside surface of the bath, accessible for
regular testing. Use copper conductors only.
DANGER - RISK OF ELECTRIC SHOCK:
Connect
only to a circuit protected by a Ground Fault Circuit
Interrupter (GFCI). In the unlikely occurrence of a
current imbalance in the power conductors, the GFCI
will interrupt the power to the bath.
WARNING: The electrical service to the GFCI must
not be interrupted by any control device. Likewise,
the electrical service from the GFCI to the bath
control should be direct and not interrupted by a
switch. Never use a switch in conjunction with a
control device. This will VOID THE
M
ANUFACTURER’S WARRANTY.
The pumps are supplied with an electrical bonding lug to
allow connection of a solid copper bonding conductor
between the unit and other electrical equipment and
exposed metal in the area as may be required by local
code.
Note:
The air blower
’s exterior housing is made of
all plastic materials and does not require a bonding
conductor.
Grounding is required. The unit should be installed by a
qualified service representative and properly grounded.
Install the service connection at least six (6) inches
[15cm] above the sub floor.
All local and state electrical and plumbing codes
must be observed.
Where there are no local codes, the
National Electric Code (NEC) and Uniform Plumbing
Code (UPC) shall be observed. It is the responsibility of
the installer/owner to determine specific code
compliance prior to installation of the product.
Note:
In the Commonwealth of Massachusetts,
installation is to be done by a Massachusetts licensed
plumber.
DANGER - Do not alter the factory installed wiring.
All building materials and wiring should be routed
away from the equipment or other heat-producing
components of the unit.
INSTALLATION INSTRUCTIONS (cont.)
Whirlpool Connections
AirMasseur
®
Connections
Note: The air switch tubing
must also be installed to allow
for a “drop loop” to prevent
moisture from entering the air
switch control box from the
tubing.