Jason International, Inc. •
501.771.4477
Page 14 of 20
Customer Service : 800.255.5766
Copyright © 2018 Jason International, Inc.
Dpoutpm Cpz
Keypad Cable
Difdl Wbmwf
Cmpxft
Cmpxft Npvou
Htpvoe - Htffo aktf
Pfvutbm - aikuf aktf
Ipu - Cmbdl aktf
Ffekdbufe
120W, 50 pt 60 I
-
HGDM Stpufdufe
Vftwkdf
1-1/2" SWD Skrf
gpt Cmpxft Smvnckoh
1" SWD Skrf pt
Dpoevku
gpt aktkoh
INSTALLATION INSTRUCTIONS (cont.)
These instructions are written assuming 60Hz, 120V power
supply. Verify the electrical requirements of the bath unit
before installation. Refer to the equipment labels for volt-
age and frequency requirements.
Note:
This bath is designed for indoor use only. The
electrical equipment must not be exposed to direct or indi-
rect water or moisture contact. The electrical equipment
must also be protected from dust and other airborne debris
before, during and after installation.
A licensed electrician must provide the “dedicated” electri-
cal service protected by a GFCI. The location of the GFCI
must be at least five (5) feet [152cm] away from the inside
surface of the bath, accessible for regular testing. Use
copper conductors only.
DANGER - RISK OF ELECTRIC SHOCK:
Connect only
to a circuit protected by a Ground Fault Circuit Interrupter
(GFCI). In the unlikely occurrence of a current imbalance
in the power conductors, the GFCI will interrupt the power
to the bath.
WARNING: The electrical service to the GFCI must not
be interrupted by any control device. Likewise, the
electrical service from the GFCI to the bath control
should be direct and not interrupted by a switch. Nev-
er use a switch in conjunction with a control device.
This will VOID THE MANUFACTURER’S WARRANTY.
ELECTRICAL INSTALLATION
The pumps are supplied with an electrical bonding lug to
allow connection of a solid copper bonding conductor be-
tween the unit and other electrical equipment and exposed
metal in the area as may be required by local code.
Note:
The air blower’s exterior housing is made of all plastic ma-
terials and does not require a bonding conductor.
Grounding is required. The unit should be installed by a
qualified service representative and properly grounded.
Install the service connection at least six (6) inches [15cm]
above the sub floor.
All local and state electrical and plumbing codes
must be observed.
Where there are no local codes, the
National Electric Code (NEC) and Uniform Plumbing Code
(UPC) shall be observed. It is the responsibility of the
installer/owner to determine specific code compliance prior
to installation of the product.
Note:
In the Commonwealth of Massachusetts, installa-
tion is to be done by a Massachusetts licensed plumber.
DANGER - Do not alter the factory installed wiring. All
building materials and wiring should be routed away
from the equipment or other heat-producing compo-
nents of the unit.
CONTROL BOX CONNECTIONS
All power cords must be connected into the proper 20 amp 120VAC GFCI dedicated circuit for the system. All controls
should be located to permit access for inspection and servicing. Depending on the options ordered on the bath, more than
one outlet may be required.
Droutrn Crz
Mkhiu Dbcng
Digdl Wbnwg
Cnrxgt
Cnrxgt Nrvou
Keypad Cable
Htrvoe - Htggo aktg
Pgvutbn - aikug aktg
Iru - Cnbdl aktg
Fgekdbuge
120W, 50 rt 60 I
)
HGDL Strugduge
Vgtwkdg
Figure 6 - Below Floor Installation
Figure 6a - Above Floor Installation