UMG 96-S2
www.janitza.com
64
Modbus
address
Address via
display
Format
RD/WR
Unit
Remark
19100
-
float
RD
varh
Reactive energy, inductive, L1..L3
19102
-
float
RD
varh
Reactive energy, capacitive, L1
19104
-
float
RD
varh
Reactive energy, capacitive, L2
19106
-
float
RD
varh
Reactive energy, capacitive, L3
19108
-
float
RD
varh
Reactive energy, capacitive, L1..L3
19110
836
float
RD
%
Harmonic, THD, U L1-N
19112
838
float
RD
%
Harmonic, THD, U L2-N
19114
840
float
RD
%
Harmonic, THD, U L3-N
19116
908
float
RD
%
Harmonic, THD, l L1
19118
910
float
RD
%
Harmonic, THD, l L2
19120
912
float
RD
%
Harmonic, THD, l L3
18.5 Number formats
Type
Size
Minimum
Maximum
short
16 bit
-2
15
2
15
-1
ushort
16 bit
0
2
16
-1
int
32 bit
-2
31
2
31
-1
uint
32 bit
0
2
32
-1
float
32 bit
IEEE 754
IEEE 754
18.6 Note on saving measured values
and configuration data
NOTE
Note on saving measured values
and configuration data:
• Since the following measured values are
saved in a non-volatile memory every 5
minutes, the recording may
be interrupted
for a
maximum of 5 minutes in case the
operating voltage fails:
• Comparator timer
• S0 counter statuses
• Min. / Max. / mean values
(without the date and time)
• Energy values
• Configuration data is saved immediately.
A detailed Modbus address and parameter list
can be found at www.janitza.com