UMG 96-S2
www.janitza.com
56
17.4 Exceeding the measurement range
A measurement range exceedance
·exists when at least one of the three voltage or
current measurement inputs are outside of the
threshold values for the metering range.
·appears as long as it continues and cannot be
acknowledged.
An arrow “upward” marks the respective phase in
which the measurement range exceedance exists.
The unit “V” for voltage and “A” for current
shows whether the measurement range
exceedance exists in the voltage circuit or
current path.
A = current path
V = voltage circuit
Phase (L1/L2/L3)
for the measurement
range exceedance.
Threshold values for the measurement range
exceedance:
I
= 7 A
eff
U
L-N
= 300 V
rms
Examples
Fig. Display with measurement range exceedance
V = voltage circuit
Fig. Display of measurement range exceedance in the
voltage circuit L3.
A = current path
Fig. Display of measurement range exceedance in the current
path of the 2nd phase (I2).
17.5 Measurement range exceedance
parameter
A coded error description is in the measurement
range exceedance parameter (address 600) in
the following format:
0 0 0 0 0 0 0 0
0b
Voltage U1
Voltage U2
Voltage U3
Current I1
Current I2
Current I3
Frequency
Example 1
Error in the current path I of phase 2:
0 0 0 1 0 0 0 0
0b
Voltage U1
Voltage U2
Voltage U3
Current I1
Current I2
Current I3
Frequency
Example 2
Error in the voltage circuit U
L-N
of phase 3:
0 0 0 0 0 1 0 0
0b
Voltage U1
Voltage U2
Voltage U3
Current I1
Current I2
Current I3
Frequency