8. Connection
8.1 Connection to a PC
The following common connection methods are
described for the communication of the derive
with a PC (with installed GridVis
®
software).
1. Connection via interface converter:
PC with GridVis
®
UMG 96-S2
RS232
RS485
RS232
RS485
NOTE
In an RS485 bus structure, observe the address
settings for your master device in the respective
documentation.
PC with GridVis
®
UMG 96-S2
USB
RS485
USB
RS485
2. Connection via a master device
(UMG 512-PRO) as a gateway:
UMG 512-PRO
as gateway
(master device)
UMG 96-S2
Slave 1
UMG 96-S2
Slave 2
UMG 103
Slave 3
Ethernet
Modbus
Modbus
Modbus
Ethernet
PC with GridVis
®
RS485
RS485
RS485
ATTENTION
Property damage due to incorrect network
settings.
Incorrect network settings can cause faults in
the IT network!
Consult your network administrator for the
correct network settings for your device.
8.2 RS485 interface
(serial interface)
The RS485 interface for this device is designed
as a 3-pole plug contact and communicates via
the Modbus RTU protocol.
Recommended cable type:
·Unitronic Li2YCY(TP) 2x2x0.22 (Lapp Kabel).
Connection capacity of the terminal:
·0.2 - 1.5 mm
2
(see chap. „18. Technical data“
on page 58)
NOTE
CAT cables are not suitable for the bus wiring!
Use the recommended cable type (see above).
A segment of an RS485 bus structure can
contain up to 32 participants/devices. Use
repeaters to connect segments with more than
32 participants/devices.
To prevent the addition of residual current when
using several devices, mount the data GND as a
functional ground (see fig.)!
The device does not contain an integrated
termination resistor (see chap.„8.4 Termination
resistors“ on page 28).
e.g. connection
to a UMG 604
as a gateway
(master device)
connection of
additional slave
devices
RS485 bus
A
B
A
B
C
C
data GND
data GND
Fig. RS485 interface,
3-pole plug contact
Termination
resistor
120 Ω
RS485 bus
A
B
Fig. RS485 interface,
3-pole plug contact
with termination resistor
(120 Ω, item no. 52.00.008)
C
Functional ground
data GND
Functional ground