88
UMG 96RM
Address
Format
RD/WR
Unit
Note
Adjustment Range Default
143
SHORT
RD/WR
s
Comparator 2C, lead time
0..32000
0
144
SHORT
RD/WR
-
Comparator 2C, Operator
0,1
0
“>=” = 0 “<” = 1
200
SHORT
RD/WR
-
Select the source for
Digital output 1
0..4
*1
0
201
SHORT
RD/WR
-
Digital output 1 inverter
0..1
*2
0
202
SHORT
RD/WR
-
Select the source for
Digital output 2
0..4
*1
0
203
SHORT
RD/WR
-
Digital output 2 inverter
0..1
*2
0
500
SHORT
RD/WR
-
Terminal assignment, I L1
-3..0..+3
+1
501
SHORT
RD/WR
-
Terminal assignment, I L2
-3..0..+3
+2
502
SHORT
RD/WR
-
Terminal assignment, I L3
-3..0..+3
+3
503
SHORT
RD/WR
-
Terminal assignment, U L1
0..3
1
504
SHORT
RD/WR
-
Terminal assignment, U L2
0..3
2
505
SHORT
RD/WR
-
Terminal assignment, U L3
0..3
3
506
SHORT
RD/WR
-
Clear min. and max. values
0..1
0
507
SHORT
RD/WR
-
Clear energy meter
0..1
0
508
SHORT
RD/WR
-
Force write EEPROM.
0..1
0
Note: Energy values and minimum and maximum values are written to the EEPROM every 5 minutes.
509
SHORT
RD/WR
-
Voltage connection diagram
0..7
0
510
SHORT
RD/WR
-
Current connection diagram
0..8
0
511
SHORT
RD/WR
-
Relative voltage for
THD and FFT
0, 1
0
The voltages for THD and FFT can be shown on the display as L-N or L-L values. 0=LN, 1=LL
*1
0 =comparator group, 1=pulse output, 2=value from an external source (Modbus), 3=reserved, 4=reserved
*2
0=not inverted, 1=inverted