8
UMG 96RM
Product description
Intended use
The UMG 96RM is provided for the measurement
and calculation of electrical parameters such as voltage,
current, power, energy, harmonics, etc. for building
installations, to distributors, circuit breakers and busbar
trunking systems.
The UMG 96RM is suitable for installation in permanent,
weatherproof switchboards. Conducting switchboards
must be earthed. It can be mounted in any position.
Measurement voltages and measurement currents must
originate from the same grid.
The measurement results can be displayed and can
be read and processed over the RS485 interface.
The voltage measurement inputs are designed
for measuring in low voltage grids in which nominal
voltages up to 300V phase can occur in countercurrent
with ground and overvoltages of overvoltage category
III.
The UMG 96RM current measurement inputs are
connected via external ../1A or ../5A current transformers.
Measurements in medium and high voltage systems
generally use current and voltage transformers.
The UMG 96RM can be used in residential and industrial
areas.
Device characteristics
•
Installation depth: 45 mm
•
Supply voltage: 230 V (95 V-240 V AC)
•
Frequency range: 45-65 Hz
Device functions
•
3 voltage measurements, 300 V
•
3 current measurements (via current transformer)
•
RS485 interface
•
2 digital outputs