84
UMG 96RM
Table 1 - Parameter list
0
SHORT
RD/WR
-
Device address
0..255 (*1)
1
1
SHORT
RD/WR
kbps
baud rate (0=9.6kbps, 1=19.2kbps,
0..4
4
2=38.4kbps, 3= 57.6kbps,
4=115.2kbps)
2
SHORT
RD/WR
-
Modbus Master
0, 1
0
0=Slave,
1=Master
(only for version with Ethernet)
3
SHORT
RD/WR
-
Stopbits (0=1Bit, 1=2Bits)
0, 1
0
10
FLOAT
RD/WR
A
Current transformer I1, primary
0..1000000
(*2)
5
12
FLOAT
RD/WR
A
Current transformer I1, sec.
1..5
5
14
FLOAT
RD/WR
V
Voltage transformer V1, prim.
0..1000000
(*2)
400
16
FLOAT
RD/WR
V
Voltage transformer V1, sec.
100, 400
400
18
FLOAT
RD/WR
A
Current transformer I2, primary
0..1000000
(*2)
5
Address
Format
RD/WR
Unit
Note
Adjustment Range Default
Parameter and Modbus address list
The following excerpt from the parameter list contains
settings that are necessary for proper operation of the
UMG 96RM, such as current transformers and device
addresses. The values in the parameter list can be
written and read.
In the excerpt, the measured value list files the measured
and calculated measured values, output status data
and recorded values so that they can be read.
C
A complete overview of the parameters and
measured values is filed in the document
"Modbus Address List" on the CD or
Internet.
C
The addresses in the range from 0-999
listed in this document can be adjusted
directly on the device. The address range
over 1,000 can only be edited via Modbus!
(*1)
The values 0 and 248 to 255 are reserved and must not be used.
(*2)
The adjustable value 0 does not produce any sensible energy values and must not be used.
Содержание UMG 96 RM
Страница 3: ...3 UMG 96RM ...
Страница 13: ...13 UMG 96RM ...
Страница 33: ...33 UMG 96RM ...
Страница 75: ...75 UMG 96RM ...
Страница 93: ...93 UMG 96RM ...
Страница 95: ...95 UMG 96RM Bottom view 97 91 ...