UMG 512-PRO
www.janitza.com
58
Voltage transformers
You can assign voltage transformer ratios to the
main measurement and the auxiliary measure-
ment respectively.
For measurements without a voltage transformer,
select the 400/400 V setting.
Setting range:
Primary
1 .. 1000000
Secondary
1 .. 999
Factory default setting:
Primary
400
Secondary
400
Nominal voltage
The nominal voltage corresponds to the "Agreed
input voltage Udin" according to EN 61000-4-30.
The nominal voltage defines the reference point
for:
·Overdeviation (EN 61000-4-30)
·Underdeviation (EN 61000-4-30)
·Transients
·Events
·Automatic scaling of graphics.
·When the nominal voltage U
LN
is entered, the
nominal voltage U
LL
is calculated automatically.
Formula: U
LL
= U
LN
·
√
3
·When the nominal voltage U
LL
is entered, the
nominal voltage U
LN
is calculated automatically.
Formula: U
LN
=
U
LL
√
3
Setting range, U
LN
: 0 .. 999999 V
Setting range, U
LL
: 0 .. 999999 V
Factory default setting: 230 V (U
LN
),
398
V
(U
LL
)
Apply AUX / MAIN
These settings can be set separately for the main
and auxiliary measurement.
The menu item "Apply AUX / Main" allows you to
apply the settings from the auxiliary or main mea-
surement respectively, so that you do not have to
enter everything again.
·
No
- The settings from the auxiliary or main mea-
surement are not adopted.
·
Yes
- The settings from the auxiliary or main
measurement are adopted.
Connection
For voltage and current measurement, you can
choose between different connection schemes
using the "Connection" selection (see „7.7 Con-
nection variants“).
Factory default setting: 4w3m
Fig. Transformer, main measurement
Fig. Example of measurement in a three-
phase 4-conductor network with an asym-
metrical load
Содержание UMG 512-Pro
Страница 23: ...www janitza com 23 UMG 512 PRO ...
Страница 27: ...www janitza com 27 UMG 512 PRO ...
Страница 47: ...www janitza com 47 UMG 512 PRO ...
Страница 89: ...www janitza com 89 UMG 512 PRO ...
Страница 96: ...UMG 512 PRO www janitza com 96 Fig IEC 61000 2 4 Watchdog parameters with traffic light principle report ...
Страница 97: ...www janitza com 97 UMG 512 PRO Fig IEC61000 2 4 PQ indicator parameters with traffic light principle snapshot ...
Страница 111: ...www janitza com 111 UMG 512 PRO 15 9 Dimensional drawings Fig View from the side Fig View from below ...
Страница 119: ...www janitza com 119 UMG 512 PRO ...