www.janitza.com
37
UMG 512-PRO
7.8.2
Example: Isolation of the residual
current transformers
A residual current transformer is used to mea-
sure on insulated mains wiring in a 300 V CAT III
network.
Provide basic insulation for 300 V CAT III for the
isolation of the network wiring and the isolation of
the residual current transformer.
ATTENTION
Transmission error and material damage due to
electrical malfunction.
With a cable length of more than 30 m, there is an
increased probability of transmission errors and
damage to the device due to atmospheric dis-
charge!
Use a shielded cable for the connection to the
residual current transformer inputs.
L1 L2 L3 N
I1
I2
I3
L1
L2
L3
PEN
N
PE
UMG 512-PRO
M
3~
I5
I6
I4
Fig. Example UMG with residual current monitoring via measurement inputs I5/I6.
Residual current transformer
Residual
current
transformer
WARNING
Risk of injury due to electrical voltage!
The Profibus, RS-485, temperature measurement
input and residual current measurement input are
not galvanically isolated from each other.
It is therefore essential to note that dangerous
voltages at these inputs can have an effect on
the respective other connections.
Содержание UMG 512-Pro
Страница 23: ...www janitza com 23 UMG 512 PRO ...
Страница 27: ...www janitza com 27 UMG 512 PRO ...
Страница 47: ...www janitza com 47 UMG 512 PRO ...
Страница 89: ...www janitza com 89 UMG 512 PRO ...
Страница 96: ...UMG 512 PRO www janitza com 96 Fig IEC 61000 2 4 Watchdog parameters with traffic light principle report ...
Страница 97: ...www janitza com 97 UMG 512 PRO Fig IEC61000 2 4 PQ indicator parameters with traffic light principle snapshot ...
Страница 111: ...www janitza com 111 UMG 512 PRO 15 9 Dimensional drawings Fig View from the side Fig View from below ...
Страница 119: ...www janitza com 119 UMG 512 PRO ...