UMG 512-PRO
www.janitza.com
102
15. Technical data
General
Net weight (with connectors)
approx. 1080 g (2.38 lbs)
Device dimensions
Approx. W = 144 mm (5.64 in), H = 144 mm (5.64 in),
D = 75 mm (2.95 in)
Battery
Type LMO CR2450, 3 V
(UL 1642 approved)
Clock - temperature range: -40 °C (-40 °F)
to +85 °C 185 °F)
+-5 ppm (equivalent to 3 minutes per year)
Impact resistance
IK07 according to IEC 62262
Transport and storage
The following information applies to devices that are transported or stored in their
original packaging.
Free fall
1 m (39.37 in)
Temperature
-25 °C (-13 °F) to +70 °C (158 °F)
Environmental conditions during operation
The device is intended for weather-protected, stationary use and must be connected to the ground
wire connection! Protection class I according to IEC 60536 (VDE 0106, Part 1).
Working temperature range
-10 °C (14 °F) to +55 °C (131 °F)
Relative humidity
5 to 95% at 25 °C (77 °F), no condensation
Operating elevation
0 .. 2000 m (6562 ft) above sea level
Pollution degree
2
Mounting orientation
Vertical
Ventilation
Forced ventilation is not required.
Protection against foreign matter and
water
·Front
·Rear
IP40 according to EN60529
IP20 according to EN60529
15.1 Supply voltage
Supply voltage
Installation overvoltage category
300 V CAT III
Fuse protection of the supply voltage
(fuse)
6 A, type B (approved according to UL/IEC)
Option 230 V:
·Nominal range
·Operating range
·Power consumption
95 V .. 240 V (50/60 Hz) / DC 80 V .. 300 V
+-10% of nominal range
max. 7 W / 14 VA
Option 24 V:
·Nominal range
·Operating range
·Power consumption
48 V .. 110 V (50/60 Hz) / DC 24 .. 150 V
+-10% of nominal range
max. 9 W / 13 VA
Connecting capacity of the terminals (supply voltage)
Connectible conductors. Only connect one conductor per terminal point!
Single core, multi-core, fine-stranded
0.2 - 4.0 mm
2
, AWG 28-12
Wire ferrules (non-insulated)
0.2 - 2.5 mm
2
, AWG 26-14
Wire ferrules (insulated)
0.2 - 2.5 mm
2
, AWG 26-14
Tightening torque
0.4 - 0.5 Nm (3.54 - 4.43 lbf in)
Strip length
7 mm (0.2756 in)
Содержание UMG 512-Pro
Страница 23: ...www janitza com 23 UMG 512 PRO ...
Страница 27: ...www janitza com 27 UMG 512 PRO ...
Страница 47: ...www janitza com 47 UMG 512 PRO ...
Страница 89: ...www janitza com 89 UMG 512 PRO ...
Страница 96: ...UMG 512 PRO www janitza com 96 Fig IEC 61000 2 4 Watchdog parameters with traffic light principle report ...
Страница 97: ...www janitza com 97 UMG 512 PRO Fig IEC61000 2 4 PQ indicator parameters with traffic light principle snapshot ...
Страница 111: ...www janitza com 111 UMG 512 PRO 15 9 Dimensional drawings Fig View from the side Fig View from below ...