89
UMG 508
Current measurement
Connection capacity of terminal points
Connectable conductor (current measurement and voltage measurement). Only one conductor per
terminal point may be connected!
Single wire, multi-wire, fine wire
: 0.2 - 2.5mm2, AWG 24 - 12
Pin terminals, ferrules
: 0.25 - 2.5mm2
Tightening torque
: 0.5 - 0.6Nm
Insulation length
: 7mm
Rated current
: 5A
Resolution
: 0.1mA
Measuring range
: 0.001 .. 7.4Arms
Crest factor
: 2.4
Measurement category
: 300V CAT III
Measurement surge voltage
: 4kV
Power consumption
: ca. 0.2 VA, (Ri=5mOhm)
Overload for 1 second
: 120A (sinusoidal)
Scanning frequency
: 20kHz