57
UMG 508
Mode (delta)
If the difference of two neighbouring scanning
points exceeds the set limit value, a transient is
recognized.
• Off
- Transient monitoring is switched off.
• Automatic
- Factoring pre-setting. The limit
value is calculated automatically and is 0.2175
times the current 200ms effective value.
• Manual
- Transient monitoring uses the adjus-
table limit value under "Trns U“.
Accept L2-L4
Transient monitoring can be set per phase. You
can accept settings from phase L1 into phases
L2, L3 and L4.
• No
- The L1 phase settings are not transferred
to the stages L2, L3 and L4.
• Yes
- The settings from phase L1 are taken
over into phases L2, L3 and L4.
Mode (absolute)
If a scanning value exceeds the set limit value, a
transient is recognized.
• Off
- Transient monitoring is switched off
• Automatic
- Factory pre-setting. The limit va-
lue is automatically calculated and is 110% of
the current 200 ms effective value.
• Manual
- Transient monitoring uses the adjus-
table limit value under "Peak U“.