12
UMG 508
Assembly
Place of Installation
The UMG508 is suitable for installation in fixed,
weather protected switch boards. Conducting
switch boards have to be grounded.
Installation extradata
In order to achieve sufficient ventilation, the
UMG508 has to be installed vertically. The clea-
rance has to be at least 50mm at the top and
bottom and 20mm at the side.
Front Board Cutout
Cutout size
:
138
+0.8
x 138
+0.8
mm
Failure to maintain the minimum clea-
rances can destroy the UMG508 at
high environmental temperatures!
Wall
Airflow
Airflow
Ethernet
Connection
Illu. UMG508 installation extradata; view from
back.
m