Prophi
®
6T
23
Operating diagram (Brief programming)
Power Factor Controller Prophi-6T
MANUAL MODE
SERVICE
EXPERT MODE
STOPP C 1.00 IND
1 min/max VOLTAGE
0 / 250.0 V
1 PASSWORD ????
[ 6343 ]
1 PASSWORD ????
[ 2244 ]
2 max REACTIVE POWER
88.88 kvar
3 max ACTIVE POWER
88.88 kW
4 max APPARENT PWR
88.88 kVA
5 max TEMPERATURE
40.0 °C
6 max VALUES
RESET [ NO ]
ERROR MEMORY
E [ 1 ] 08H ....
2 BASIC SETTINGS
NEW ? [ NO ]
EXPERT-MODE 2
Activation / Deactivation
of the following
error- messages is
possible with next steps
[ YES/NO ]:
- MEAS.VOLTAGE ?
- OVERVOLTAGE
- OVER COMPENSAT.
- UNDERCOMPENSAT
- HARMONICS
- OVERTEMPERATURE
- OVERCURRENT
- UNDERVOLTAGE
- UNDERCURRENT
C1: AUTO (FIXED/TEST/OFF)
C2: AUTO (FIXED/TEST/OFF)
C3: AUTO (FIXED/TEST/OFF)
C4: AUTO (FIXED/TEST/OFF)
C5: AUTO (FIXED/TEST/OFF)
C6: AUTO (FIXED/TEST/OFF)
ERROR MEMORY
RESET [ NO ]
3 SWITCH. POWER
max [25] kvar
4 TRIGGER VALUE
[ 66 ] %
5 PROGRAM LOCK
[ NO ]
6 PHASE I 0°
[ L1 ] - L1-N
7 PHASE U 0°
L1 - [ L1- N ]
2 ERROR ME.RELAY
[ 120 ] sec.
8 POWER 1.STEP
[ 0...255 kvar ]
9 CONTROL
[ 3 ] PHASE
10 DISPLAY
[ COS PHI ]
11 HARMONICS
[ NO ]
BACK TO 1
BACK TO 1
3 UNDERVOLTAGE
[ 50 ] %
4 OVERVOLTAGE
[ 115 ] %
5 FREQUENCY
[ 40...80 Hz ]
Changing
of values
by buttons: