Prophi
®
6T
20
Annex 2: Default settings
No.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Parameter
LANGUAGE
I CONVERTER prim.
I CONVERTER sec.
END STOPP
CONTROL SERIES
CONTROL PRINCIPLE
POWER 1. STAGE
TARGET COS-PHI
MEASURING VOLTAGE
V- CONVERTER RATIO
SWITCH- IN TIME
SWITCH- OFF TIME
DISCHARGE TIME
ALARM TEMP.
DELAY ERROR MESSAGE
Capacitor stages
Password Expert mode 1
Password Expert mode 2
Trigger value
Max.simult.switch.power
Operating lock
Phase shift U/I
Power 1. stage
Control
Default setting
ENGLISH
1000 A
5 A
6
1
INTELLIGENT
25.00 kvar
0.98 IND
230 V L-N
- NO -
1 sec.
1 sec.
0.2 sec.
55 °C
20 sec.
AUTO
6343
2244
66%
4 x smallest stage
- NO -
0 °
0...255 kvar
3 - phase
Programmed values of this
system (to be entered by
manufacturer or operator)
Cannot be changed
Cannot be changed
Note: The following values for the default settings apply only if the controller is supplied
directly from the manufacturer. Otherwise, these values may have been replaced by
settings made by the manufacturer of the compensation network (optimal values for the
relevant network).
- 19 -
Содержание Prophi 6T
Страница 21: ...Prophi 6T 21...