Page 5
Jandy
®
UV Medium Pressure | Installation & Operation Manual
ENGLISH
2.2 Product Specifications
JUVMP120
JUVMP200
JUVMP320
JUVMP700
Flow (UVT 94%)
1
110 gpm
25.0 m
3
/h
175 gpm
39.7 m
3
/h
310 gpm
70.4 m
3
/h
600 gpm
136.2 m
3
/h
Material
Control panel
Metallic, polyester-epoxy resin coating RAL 7035 / IP-54
UV reactor
AISI-316L
Flanges Inlet/Outlet
4" (ANSI)
6" (ANSI)
Max. rated pressure
50 psi / 3.45 bar
Head loss
0.00 psi @ 110 gpm
0.00 psi @ 50 m
3
/h
0.01 psi @ 175 gpm
0.05 psi @ 39.7 m
3
/h
0.03 psi @ 310 gpm
0.03 psi @ 70.4 m
3
/h
0.03 psi @ 600 gpm
0.03 psi @ 136.2 m
3
/h
Voltage
240 VAC / 60 Hz. / 1-phase
Rated Power (W)
700
1000
3000
3000
Electronic ballasts
1
1
1
1
UV-C power (W)
105
150
450
450
Lamps
1
1
1
1
Lifetime (hours)
3,000
5,000
Cleaning
Manual
Automatic (optional with JUVMPAUTO module)
Cooling
Panel: fan + filter
Ballast: self-cooled aluminum heatsink
Control monitor
Radiation
Flow
Temperature
Lamp
3.4" TFT color touchscreen (320x240 pixels)
6 languages
UV-C sensor
Flow sensor (stainless steel)
Temperature sensor (PT-100, stainless steel)
Hour counter
•
•
•
•
Alarm log
•
•
•
•
Power control
•
•
•
•
Re-ignition control
•
•
•
•
Control inputs
Two (2) potential-free contacts: flow switch and remote stop
1
This product has been tested to confirm a minimum inactivation equivalent of 3 log (99.9%)
Cryptosporidium Parvum
in accordance with NSF 50 and the US EPA UV DGM. This product has met the requirements of NSF/ANSI 50, Annex
H.1: Disinfection Efficacy for the >= minimum of a 3 log (99.9%) reduction of
Enterococcus Faecium
[ATCC #6569] and
Pseudomonas aeruginosa
[ATCC #27313]. This product is intended for secondary disinfection and should be used with
EPA registered or approved disinfection chemicals to impart residual concentrations in accordance with state and local
regulations.