3.2 Controller 

Troubleshooting

3.2.1 

Display Is Not Illuminated

Check the voltage between the red and green wires at the red terminal bar (terminals 1 and 4). If the voltage is 
between 8 and 10 VDC, check the polarity. The red wire is positive (+) and the green wire is negative (-). If the 
voltage and polarity are correct, replace the control panel. If the voltage is less than 8 VDC, go to the power center.

1.  At the power center, check the voltage between the red and green wires at the red terminal bar (terminals 1 and 4). 

See Figure 5. If the voltage is between 8 and 10 VDC and the polarity is correct, but there is less than 7 VDC at 
the indoor control, check the wires for the following:

a.  Broken or shorted red or green wires.
b.  Wire size. The minimum gauge for one control no more than 300 feet away from the power center is 22 AWG. 
To ensure a lower drop in current, use larger wire (16 to 20 AWG)

2.  If the voltage is less than 7 VDC, check the following:

a.  Transformer secondary wires (two yellows). See Figure 6. If the voltage is less than 22 VAC, check the 
incoming (primary power) to the system.
b.  If the power to the transformer primary is less than 105 VAC, contact the power supply company.
c.  If the voltage to the transformer primary is above 105 VAC, but the transformer secondary is less than 22 
VAC, replace the transformer.
d.  If the secondary voltage is 24 to 28 VAC, turn off the power.
e.  Remove the fuse from its holder and do a continuity test. If there is no continuity, unplug all the Jandy Valve 
Actuators (JVAs), replace the fuse (3.15 amp), and turn on the power. If the fuse blows with all JVAs unplugged, 
the circuit board is damaged and needs to be replaced. If the fuse does not blow, plug a JVA cord into the Intake 
JVA Socket. Test the JVA by switching to 

SPA

. If the fuse holds, remove the tested JVA and plug the next JVA 

into the Intake JVA Socket. Continue until all JVAs have been tested or the fuse blows.

Содержание AquaLink RS6

Страница 1: ...onal pool spa service technician The procedures in this manual must be followed exactly Failure to follow warning notices and instructions may result in property damage serious injury or death Pool Sp...

Страница 2: ...Page 2...

Страница 3: ...3 HP Relay 23 5 5 Two Speed Relay 25 5 6 Light Dimming Relay 27 Section 6 Jandy Valve Actuator 29 6 1 Operation 29 Section 7 Troubleshooting 31 7 1 Quick Check List 31 7 2 Controller Inoperable Displa...

Страница 4: ...regnant or possibly pregnant women should limit spa water temperatures to 100 F 38 C c Before entering a spa or hot tub the user should measure the water temperature with an accurate thermometer since...

Страница 5: ...our health Do not permit any electric appliance such as a light telephone radio or television within 5 feet 1 5 m of a spa or hot tub The use of alcohol drugs or medication can greatly increase the ri...

Страница 6: ...er pair is broken or misconnected but the power supply wires the outer pair are connected properly the controller will stop responding It may show a steady screen of information and stop responding to...

Страница 7: ...ted Bar Up or Down Selects Highlighted Items Figure 1 All Button Controller Front View Figure 2 All Button Controller Back View Figure 3 OneTouch Controller Front View Figure 4 OneTouch Controller Fac...

Страница 8: ...ster press an arrow key for example Up If you make a mistake select CANCEL before selecting ENTER again When done the controller will return automatically to its normal operating cycle 2 OneTouch From...

Страница 9: ...Side Switch SPA SW BOARD C Tele Link TELELINK 1 1 C Auxiliary Power Center REMOTE PWRCNTR 1 2 3 Yes LX Heater LX HTR 1 2 Yes H AquaPure Chlorinator AquaPure 1 I AquaPalm AQUAPALM 1 MMM RS InterLink N...

Страница 10: ...in current use larger wire 16 to 20 AWG 2 If the voltage is less than 7 VDC check the following a Transformer secondary wires two yellows See Figure 6 If the voltage is less than 22 VAC check the inco...

Страница 11: ...ONLY RS8 ONLY HEATER SOLAR POOL MODE SPA MODE SPA DRAIN SPA FILL AUTO Red Wire Green Wire Figure 5 Checking Voltage at Red Terminal Bar Figure 6 Transformer Primary and Secondary Voltages Check for b...

Страница 12: ...ure 7 2 The microprocessor was hit by a power surge Turn off all power to the system If the PCB is prior to Revision N disconnect the nine 9 volt battery Wait two 2 minutes and then turn the power on...

Страница 13: ...led but spa is circulating To eliminate the control system as the cause of the heating problem insert both wires to the heater into the same terminal of the green terminal bar as shown in Figure 8 If...

Страница 14: ...n located in the upper left hand corner of the power center bezel resets the power center micro controller This also changes the time and date to the default settings for PCBs prior to Rev N Pressing...

Страница 15: ...rimary check the supply source the circuit breaker 3 If there is 105 to 130 VAC on the primary and no voltage on the secondary replace the transformer Note the transformer and or its fuse can be damag...

Страница 16: ...ler Module Connector 7 Battery 3 Volt Lithium 8 Spare Auxiliary Operates with pool spa combo units only With firmware prior to Rev I this socket is on when the filter pump is on and the system is in p...

Страница 17: ...1 10 9 8 7 6 5 4 3 2 1 4 3 2 1 4 3 2 1 RESET SERVICE TIME OUT FIL TER PUM P A U X 1 A U X 2 A U X 3 A U X 4 A U X 5 A U X 6 A U X 7 RS6 RS8 ONLY RS8 ONLY HEATER SOLAR POOL MODE SPA MODE SPA DRAIN SPA...

Страница 18: ...umpers on the back side of the auxiliary power center board They identify the board and must be set correctly or the board will not respond properly to commands from the main power center PCB See belo...

Страница 19: ...down operates Heater cool down disabled 5 Normal operation Factory adjustment When this switch is on tem perature delays are eliminated and solar tempera ture is displayed Do not leave this switch in...

Страница 20: ...n reached the heater will remain off for five 5 minutes DIP Switch OFF ON 1 Aux 1 Any equipment Aux 1 Pool cleaner 2 Aux 2 Any equipment Aux 2 Low speed for a two speed filter pump Filter pump circuit...

Страница 21: ...Resistance Chart Temp Resistance Temp Resistance 50 F 19 898 K Ohms 78 F 9 735 K Ohms 51 F 19 435 K Ohms 79 F 9 483 K Ohms 52 F 18 871 K Ohms 80 F 9 284 K Ohms 53 F 18 382 K Ohms 81 F 9 079 K Ohms 54...

Страница 22: ...X 5 A U X 6 A U X 7 RS6 RS8 ONLY RS8 ONLY HEATER SOLAR POOL MODE SPA MODE SPA DRAIN SPA FILL AUTO To Solar Sensor To Air Sensor To Water Sensor Solar Sensor Part Numbers 7908 15 7932 50 7933 125 Ears...

Страница 23: ...elays may be wired to activate a 120 VAC circuit i e Line 1 Load 1 or a 240 VAC circuit i e Line 1 Load 1 and Line 2 Load 2 Note If a relay s coil wires are shortened or an AC relay coil is plugged in...

Страница 24: ...X 6 A U X 7 RS6 RS8 ONLY RS8 ONLY HEATER SOLAR POOL MODE SPA MODE SPA DRAIN SPA FILL AUTO S1 S2 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 4 3 2 1 4 3 2 1 RESET SERVICE TIME OUT FIL TER PUM P A U X 1 A U X 2 A...

Страница 25: ...g the two speed relay coil wires into the Auxiliary 2 socket Finally turn on DIP switch 2 to set the circuitry to two speed operation This will interlock the low speed and high speed together If low s...

Страница 26: ...SPA DRAIN SPA FILL AUTO S1 S2 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 4 3 2 1 4 3 2 1 RESET SERVICE TIME OUT FIL TER PUM P A U X 1 A U X 2 A U X 3 A U X 4 A U X 5 A U X 6 A U X 7 RS6 RS8 ONLY RS8 ONLY HEATER...

Страница 27: ...rcuit breaker for the light Un like a standard relay which receives a constant 24 VDC to its coil to hold the relay contacts closed and which opens when that voltage is removed the light dimming relay...

Страница 28: ...be installed in each power center S1 S2 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 4 3 2 1 4 3 2 1 RESET SERVICE TIME OUT FIL TE R PU MP AU X 1 AU X 2 AU X 3 AU X 4 AU X 5 AU X 6 AU X 7 RS6 RS8 ONLY RS8 ONLY HE...

Страница 29: ...is routed to the lower microswitch and that microswitch is closed the voltage passes through the motor to the black wire and then back to the other leg of the transformer secondary to complete the cir...

Страница 30: ...Page 30 Figure 23 JVA Internal Wiring...

Страница 31: ...installed incorrectly Dam aged communication chip All LEDs are on at the All Button Controller and the part and revision letter of the Controller software are displayed or with a OneTouch the screen s...

Страница 32: ...tton may be shorted See Troubleshooting the Spa Side Remote Controller model is Dual Equipment message scrolls Adjustable Freeze Sensor Not Installed Normal operation when a Dual Equipment model is co...

Страница 33: ...be tween the same two terminals Is the voltage 8 to 10 VDC The power supply is damaged and the PCB at the Power Center will need to be replaced Yes No Controller PCB will need to be replaced Wires ar...

Страница 34: ...gain Does Controller operate Yes No Replace the battery and recheck the system Replace firmware chip and try sys tem If system still does not operate replace the Power Center PCB No Turn off power Rem...

Страница 35: ...tion Part Rev C to Rev II Part Rev J to Rev MMM Part Rev N and Later AquaLink RS 16 24 32 P S Pool and Spa Combination 7202 8166 E0260811 AquaLink RS 12 P S Pool and Spa Combination 7201 8165 E0260810...

Страница 36: ...rn off power and remove both relay driver chips Replace the fuse and turn on power Does fuse fail again Check JVA cords Are JVA cords spliced Replace Power Center PCB Replace both relay driver chips Y...

Страница 37: ...re and Resistance Chart Is resistance within specifica tion Yes Replace the Power Center PCB Either the wires to the heater are not connected properly or the problem is actually the heater No Yes No R...

Страница 38: ...PA HEAT SET TIME SET MONTH DAY YEAR TIME DISPLAY LIGHT ON OFF 2 MIN DELAY LOCKOUTS SYSTEM SPA SWITCH SPA LINK DEVICES LOCK UNLK SELECT DEVICE SELECT DEVICE LOCK UNLK SET AQUAPURE SET POOL MAINTAIN HOU...

Страница 39: ...RZ PROTECT SPA LINK SPA SWITCH MAIN LABEL MENU SEE SECTION 8 FOR AN EXPANDED LIST SET DIMMERS SELECT EQUIPMENT ALL OFF LABEL AUX AQUAPURE DAYLIGHT SAVINGS DIAGNOSTICS IN FLOOR CLN SOLAR HEAT PRIORITY...

Страница 40: ...CH SPA LINK DEVICE UNLOCKED No JVAs assigned to AUXs Select AUX to remove label from Select device to be cancelled Press enter to remove all devices except pump from freeze protection or cancel to abo...

Страница 41: ...5 Aux 4 Relay Sockets 24 VDC output JVA Sockets 24 VAC output Battery 9Volt Red Black Not Used Not Used RESET SERVICE TIME OUT FIL TER PUM P A U X 1 A U X 2 A U X 3 A U X 4 A U X 5 A U X 6 A U X 7 RS6...

Страница 42: ...o not permit children to use this product unless they are closely supervised at all times Water temperature in excess of 100 F 38 C may be injurious to your health WARNING AVERTISSEMENT Pour r duire l...

Страница 43: ...x B 3 R elay Grounding Bar Wire Nut to 120 VA C P ower System Powe r Aux B 1 JV A Aux B 3 JV A Aux B 2 JV A Aux B 4 JV A Yellow Green Black Re d 4 3 2 1 Aux B 1 Aux B 2 Aux B3 Aux B 4 Relay Sockets 24...

Страница 44: ...E TIME OUT PO O L PUM P AUX 1 AUX 2 AUX 3 AUX 4 AUX 5 AUX 6 SPA PUM P PO O L HEATER SPA HEATER SO LAR 6762 RESET AUTO SERVICE TIME OUT PO O L PUM P AUX 1 AUX 2 AUX 3 AUX 4 AUX 5 AUX 6 SPA PUM P HEATER...

Страница 45: ...Page 45 Notes...

Страница 46: ...Page 46 Notes...

Страница 47: ...Page 47 Notes...

Страница 48: ...outside the published minimum and maximum specifications 7 Use of non factory authorized parts or accessories in conjunction with the product s 8 Chemical contamination of combustion air or improper u...

Отзывы: