Page 21
JXi
™
Gas Conversion / Replacement Instructions
STEP 7: Test Gas Orifice Offset Pressure
NOTE:
Test the gas orifice offset pressure with the heater running
using a digital differential pressure manometer.
1. . Reopen the gas shut-off valve.
2. Test the offset pressure with the heater running using a digital
differential pressure manometer. Connect a tee to the hose from
the fan inlet port (see Figure 20) on the blower.
3. Connect a shorter hose from the gas valve vent port to the
opposite side of the tee (see Figure 20).
4. The manometer has a positive (high pressure) port and a negative
(low pressure) port. Connect a hose on the third joint of the tee to
the positive (high pressure) side of the manometer
(see Figure 20).
5. Remove the NPT plug from the gas valve manifold port (labeled
“PRESS” “TAP”) and screw in the barbed adapter.