Control
Power
*
Use the two 4-20ma IN wires for analog current speed control.
Leave 4-20ma wires disconnected if not used, (less than 5.6ma is OFF).
White
Motor to
Power
Black
Green
L1
L2
Ground
Red
White
Black
Green
Motor to
Control
0-10V IN
+10V OUT
Signal Ground
STOP/RUN
Red
White
Black
Green
Motor to
Power
L1
L2
L3
Ground
White w/Green Stripe
Orange w/White Stripe
Motor to
Control
+10V OUT
0-10V IN
Green w/White Stripe
STOP/RUN
White w/Orange Stripe
Signal Ground
White w/Blue Stripe
+
4-20ma IN*
4-20ma IN*
Blue w/White Stripe
–
If installing the Single Phase AirBlaster proceed to Step 37.
If installing the Three Phase AirBlaster skip to Step 38.
If installing the Single Phase AirBlaster skip to Step 39.
Single Phase Wired for 190-240v
37
Three Phase Wired for 190-240v / 380-460v
38
Identify Cords Coming From Motor
36
General Wiring Instructions:
• Wiring should only be performed by a trained electrician to prevent injury
or death.
• Install manual disconnect switch inside building adjacent to fan.
• Route wire to motor with drip loop and secure. Drip loop will drain accumulated
moisture away from the motor.
• Use four conductor 26AWG (or heavier), shielded, dual twisted pair, signal wire
with drain wire from J&D control to Permanent Magnet fan.
35
DISCONNECT POWER
BEFORE INSTALLING OR SERVICING.
ALL ELECTRICAL WORK SHOULD BE COMPLETED BY QUALIFIED PERSONNEL
AND MEET NATIONAL (NEC), REGIONAL AND LOCAL ELECTRIC CODES.
!
!
IS297-22F
J&D Manufacturing • 6200 Hwy 12 • Eau Claire, WI 54701 • 1-800-998-2398 • www.jdmfg.com