 REMOTE CONTROL

 

The remote On/Off function. This contact can be used 
to  control  the  device  via  building  automation/PLC/
External Switches.

 

To use this feature, selected scenario must be contain 
remote control contact.

 

10.2 ELECTRICAL HEATER CONTROL

 

1. Controlled Depending on Room Temperature :

Electrical heater is controlled by sensor on the panel or 
return air temperature sensor. Control is active without 
any adjustment. ( Default Control Type )

 

2. Controlled Depending on Outdoor Temperature: 

If

outdoor temperature value less than value set in the 
service menu, the heater stages is activated.

 

Note: Control according to the outdoor air temperatu-
re to be active, parameter settings must be made of 
appropriate. (See. Service Menu Operations)

 

10.

4

 ENTRANCE DAMPER CONTROL

 

Fresh air and/or exhaust air damper motors are cont-
rolled. Damper motor is controlled considering the ne-
cessary delays ( The device On/Off moments, alarm 
moments... ).

 

10.

3

 BYPASS DAMPER CONTROL

 

The working conditions of the bypass damper is as fol-
low;

 

Fan Mode;

 

Bypass damper is always closed.

 

Heating Mode;

 

1.

Outdoor Air Temp. < Room Temp. + 3 and
Setpoint <  Room Temp. + 2 and

Outdoor Air Temp. > 15  

°C

damper is open,

2.

Outdoor Air Temp.  > Room Temp. 

-

 3 and

Setpoint > Room Temp. 

-

 2 and

Outdoor Air Temp. < 35  

°C

damper is open, closed in the other conditions

Cooling Mode;

 

1.

Outdoor Air Temp. > Room Temp. + 3 and
Setpoint >  Room Temp. 

-

 2 and

Outdoor Air Temp. < 32  

°C

damper is open,

2.

Outdoor Air Temp. < Room Temp. 

-

 3 and

Setpoint < Room Temp. 

-

 2 and

Outdoor Air Temp. > 10  

°C

damper is open, closed in the other conditions

11. SERVICE MENU OPERATIONS

11.1 MENU DESCRIPTION

 

While the device is  in the Off Position, press together 

MODE

 and 

▼ 

key for 5 seconds.

 

In  the  service  menu 

Main  Parameter

” 

is  replaced  by 

the 

MODE

  and  

FAN

 keys.

 

Auxiliary  Parameter

” 

is  replaced  by  the 

  and 

 

keys.

 

Main Parameter

 

Auxiliary Parameter

 

11.2 PASSWORD PARAMETER

 

While the device  is in the Off Position, press together 

MODE

 and 

▼ 

key for 5 seconds.

 

To make changes in the parameters, password must be 

entered  as 

“137”

,  to 

99

parameter.

 

Firstly, 

Main  Parameter

” 

must  be replaced as 99, by 
the 

MODE

 and  

FAN

 keys.

 

Secondly, 

Auxiliary  Para-

meter

” 

must be replaced as 

137, by the 

 and 

 keys.

 

Otherwise, made changes won

’ 

t be saved.

 

Note:  This  process  is  part  of  the  entry  to  the  Service 
Menu and must be applied in all entries.

 

MANUAL

 

for

 JAKKA PRO 

C

ONTROL

L

ER

One relay output reserved into for damper. If there are 
more damper motor, must be connected in parallel. 

Note : Damper motor must be in the On/Off and 
spring return property.

 

Содержание Pro

Страница 1: ... this appli cation Room Temperature Supply Air Temperature Outdoor Air Temperature Exhaust Air Temperature sensors can be measured by main controller Note 1 If Room Temperature Sensor is not connected to main controller Temperature Sensor value of the panel is measured Note 2 Supply Air Temperature and Room Temperature value are measured by same input If user wants to get the Supply Air Temperatur...

Страница 2: ...ion if pressing FAN key for 5 seconds fan logic is changed Continious Fan Displayed as Cont on the panel Fans will work as long as the device is in the On position Default Auto Fan Displayed as Auto on the panel Fans will be active while heating or cooling In other cases the fan output is closed 7 CLOCK SETTINGS When pressing the MODE key for 6 7 seconds hour digit flashes on the panel While digit...

Страница 3: ...u re 8 and Exhaust Air Temperature 2 alarm happens Electrical Heater 1 stage opens during alarm When Exhaust Air Tempe rature 2 and time passed up to the OutdoorTempFrostOutTimerLimit BMS 331 parameter alarm is eliminating 9 6 AL 06 OUTDOOR TEMP SEN FROST ALARM 9 3 AL 03 FIRE CONTACT ALARM NO If contact is in the closed position or Room Tempe rature SetFireA larmTemp BMS 343 Service Menu 44 para m...

Страница 4: ... 15 C damper is open 2 Outdoor Air Temp Room Temp 3 and Setpoint Room Temp 2 and Outdoor Air Temp 35 C damper is open closed in the other conditions Cooling Mode 1 Outdoor Air Temp Room Temp 3 and Setpoint Room Temp 2 and Outdoor Air Temp 32 C damper is open 2 Outdoor Air Temp Room Temp 3 and Setpoint Room Temp 2 and Outdoor Air Temp 10 C damper is open closed in the other conditions 11 SERVICE ME...

Страница 5: ...vice menu to activate the control according to the outdoor air temperature Outdoor Control Activate Firstly Main Parameter must be replaced as 9 by the MODE and FAN keys Secondly Auxiliary Para meter must be replaced as 2 by the and keys 11 6 DATE SETTINGS 1 Firstly Main Parameter must be replaced as 12 by the MODE and FAN keys Secondly Auxiliary Para meter must be set to the desired day value 2 F...

Страница 6: ...ons as shown below to termi nals on the front panel 5 Attach the clip at the top first and then attach the clip at the bottom 13 CONTROL PANEL CABLE CONNECTIONS 2 x 2 x 0 34 0 75mm Shielded Twisted Pair RS485 Data Com munication Cable must be used Note Press the terminal buttons with the help of a fine tipped pen as shown in the figure Don t apply extreme pressure NOTE DON T USE THE SCREWDRIVER 12...

Отзывы: